JDZW-10R, JDZW2-10KV للخارج Pillar راتنج الإيبوكسي Voltage Transformers built-in fuse

JDZW-10R, JDZW2-10KV للخارج Pillar راتنج الإيبوكسي Voltage Transformers built-in fuse

3-10kV voltage transformers with integrated fuse حماية

  • Dual outputs: 100V قياس instrumentation, 220V circuit breaker control
  • Accuracy 0.2/0.5/1 قياس, 6P حماية, 15-60VA المخرج المقنن
  • Vacuum cast راتنج الإيبوكسي, fully-enclosed structure, sealed terminals
  • Integrated internal fuse, 1.2Un voltage factor, IEC and GB/T

Product Overview

Functional Definition

The JDZW-10R and JDZW2-10 series للخارج voltage transformers are precision electromagnetic instruments designed for accurate voltage measurement, energy قياس, and relay حماية applications in 10kV AC power systems. These transformers feature pillar-type structure with fully cast راتنج الإيبوكسي insulation, providing exceptional resistance to UV radiation, electrical arcing, and environmental aging. The compact, lightweight design enables flexible installation in any orientation, while secondary terminals include protective covers with anti-theft measures for enhanced security. These transformers are specifically engineered for للخارج service in ungrounded neutral systems operating at 50 Hz or 60 Hz.

Key Ratings

Item Specification (حسب الطلب / لوحة البيانات)
System voltage class 10 kV class (للخارج medium-voltage distribution applications)
Rated frequency 50 Hz or 60 Hz
Rated voltage ratio 10000/100 V, 10000/220 V, 10000/100/100 V, 10000/100/220 V
Accuracy classes Metering: 0.2, 0.5, 1st Class, 3rd Class / Dual core: 0.2/0.2, 0.5/0.5, 0.2/0.5 / حماية: 6P
Rated output 40 VA to 240 VA (single core), 25/25 VA to 40/40 VA (dual core), فئة الدقة dependent
Maximum output 100 VA (single core), 300/300 VA to 300/800 VA (dual core)
Insulation level 12/42/75 kV (Um / AC withstand / Lightning impulse)
Ambient temperature -25 °C to +40 °C
Vibration resistance 0.4g direct vibration test capability
Partial discharge Complies with GB20840.3-2013 and GB20840.1-2010
Applicable standards IEC186, GB1207-2006, GB20840.1-2010, GB20840.3-2013
Model variants JDZW-10R / JDZW2-10

Product Shows

PRESERVED url 171

PRESERVED url 170

Working Principle

Operating on Faraday’s law of electromagnetic induction, the محول الجهد features a laminated magnetic core with primary winding connected to system voltage and secondary اللفات providing standardized output voltages. The magnetic flux generated by primary voltage induces proportional voltage in secondary اللفات, delivering single-output (100V or 220V) or dual-output configurations (100V/100V or 100V/220V) through connected حمل impedance. The pillar-type البناء ensures optimal electromagnetic performance with minimal external interference.

System التطبيق Position

  • Medium Voltage Distribution: 10kV للخارج distribution networks and substations
  • Energy قياس: Revenue-grade electricity measurement systems in ungrounded neutral networks
  • Protection Circuits: Overvoltage, undervoltage, and distance حماية schemes
  • Relay حماية: Ground fault detection and relay coordination in ungrounded systems
  • SCADA Integration: Supervisory control and voltage monitoring for للخارج installations

Structural Overview

Fully cast راتنج الإيبوكسي البناء with pillar-type design ensures superior للخارج performance, UV resistance, arc resistance, and long-term aging stability. The sealed structure provides complete حماية against environmental factors including moisture, contamination, and temperature extremes. Steel channel base with four mounting holes enables secure installation on various support structures. Secondary terminals feature protective covers with integrated anti-theft mechanisms and convenient wiring access holes. The compact, lightweight design permits installation in any orientation, offering exceptional flexibility for للخارج distribution network configurations.

Model Designation

PRESERVED url 169

Model Code Explanation

  • J — محول الجهد (VT/PT)
  • D — للخارج configuration
  • Z — راتنج الإيبوكسي cast insulation
  • W — Pillar-type structure
  • 10 — Voltage class (10 kV)
  • R — Reinforced design variant (JDZW-10R)
  • 2 — Design series iteration (JDZW2-10)

Variant Differences

JDZW-10R and JDZW2-10 are electrically equivalent when specified with identical voltage ratios, accuracy classes, and rated outputs. Both variants utilize the same pillar-type structure with راتنج الإيبوكسي cast insulation. Selection between JDZW-10R and JDZW2-10 may depend on specific mechanical mounting requirements, terminal configurations, or regional المواصفات preferences. All electrical performance parameters, insulation levels, and environmental ratings are consistent across both الموديل designations.

Service Conditions

The JDZW-10R and JDZW2-10 series voltage transformers are designed for للخارج operation under specified ظروف الخدمة in 10kV medium-voltage power systems.

  • Installation environment: للخارج installation, suitable for ungrounded neutral systems
  • Altitude: Not exceeding 2000 m above sea level
  • Ambient temperature: −25 °C to +40 °C
  • Vibration resistance: Withstands direct vibration test intensity of 0.4g
  • Environmental حماية: UV resistant, arc resistant, aging resistant for extended للخارج service life
  • Pollution class: Class II pollution level per applicable standards
Engineering Note: These transformers are specifically designed for للخارج service with enhanced environmental resistance. High-altitude installations or extreme environmental conditions may require engineering consultation for proper المواصفات.

Construction

Construction Design

  • Structure: Pillar-type for للخارج distribution network installations
  • Insulation: Fully cast راتنج الإيبوكسي insulation with complete environmental sealing
  • Core: Laminated magnetic core design with high permeability silicon steel
  • Base: Steel channel البناء with four mounting holes for secure installation
  • Environmental حماية: UV resistant, arc resistant, aging resistant materials throughout
  • Secondary terminals: Protective covers with anti-theft features and wiring access holes
  • Installation flexibility: Compact, lightweight design permits installation in any orientation

The fully sealed راتنج الإيبوكسي cast البناء provides exceptional resistance to UV radiation, electrical arcing, moisture ingress, contamination, and environmental aging. This design ensures reliable long-term للخارج performance with minimal maintenance requirements.

Windings & Terminal Marking

PRESERVED url 168

  • Primary terminals: A / X (high-voltage side)
  • Secondary terminals (single output): a / x (100V or 220V)
  • Secondary terminals (dual output 100V/100V): a1 / x1 and a2 / x2
  • Secondary terminals (dual output 100V/220V): a / x (100V) and ad / xd (220V)

Terminal markings follow المعيار VT polarity conventions per IEC186 and GB1207-2006. Under normal operating conditions, when primary terminal A is positive with respect to X, secondary terminal ‘a’ is positive with respect to ‘x’. Correct terminal identification is critical for accurate قياس and حماية performance in ungrounded neutral systems.

Technical Data

This section provides selection-oriented البيانات الفنية for the JDZW-10R and JDZW2-10 series للخارج, pillar-type voltage transformers used in 10 kV class AC systems (50 Hz or 60 Hz). Data shown below is intended for preliminary selection of voltage ratio, فئة الدقة, المخرج المقنن capacity, and configuration.

Definitions: Accuracy class indicates قياس precision (0.2, 0.5, 1st Class, 3rd Class) or حماية performance (6P). Rated output (VA) is specified per فئة الدقة and secondary winding. Limit output is the maximum thermal capacity. Dual-core configurations are designated as accuracy1/accuracy2 with corresponding output1/output2.

Notation: مستوى العزل expressed as Um / AC withstand / Lightning impulse (BIL) per IEC186 and GB1207-2006. Partial discharge levels comply with GB20840.3-2013 and GB20840.1-2010.

Data Reference

Model Rated
Voltage
Ratio (V)
Rated Secondary Output (VA) Limit
Output
(VA)
Rated
Insulation
Level (kV)
Wiring
Diagram
0.2 0.5 1st
Class
3rd
Class
0.2/0.2 0.5/
0.5
6P
0.2/0.5
JDZW2-10
JDZW-10R
10000/100 40 80 200 240 / / / 100 12/42/75 Diagram 1-2
10000/220
10000/100/100 / / / / 25/25 40/40 / 300/300 Diagram 3-4
Technical Note: المخرج المقنن capacity must exceed total secondary حمل (connected instruments + cable losses). For dual-core configurations, each secondary winding has independent فئة الدقة and output capacity specifications. Maintain حمل within rated VA range for optimal accuracy performance.
Customization Support: JDZW-10R and JDZW2-10 series support التخصيص of voltage ratios, output configurations, فئة الدقة combinations, and insulation levels to meet specific project requirements. Engineering consultation available for حمل calculation, accuracy assessment, and system integration.

Standards & Normative References

Standard Title Application
IEC186 Voltage Transformers General VT requirements and performance specifications
GB1207-2006 Voltage Transformers National VT المعيار for design, performance, and testing
GB20840.1-2010 Instrument Transformers – Part 1: General Requirements General requirements including partial discharge limits
GB20840.3-2013 Instrument Transformers – Part 3: Voltage Transformers VT-specific requirements including partial discharge testing
IEC 60068-2-17 Environmental Testing – Salt Mist Optional (project-specific environmental validation)
IEC 60085 Electrical Insulation – Thermal Evaluation Insulation thermal class reference

Factory Test Compliance

  • Routine tests per IEC186 and GB1207-2006 requirements (including polarity/marking verification, ratio verification, accuracy verification per specified class and حمل, and dielectric withstand)
  • Partial discharge test per GB20840.3-2013 and GB20840.1-2010 acceptance levels
  • Dielectric tests per insulation coordination requirements (AC withstand 42 kV, lightning impulse 75 kV)
  • Vibration test to verify 0.4g vibration resistance capability
  • Environmental resistance tests including UV exposure, arc resistance, and aging performance (حيث تم تحديده)
  • Visual and dimensional inspection including marking accuracy, terminal حماية, and workmanship conformity
  • Type and special tests as required by project specification
Compliance Note: All variants maintain full compliance with listed المعايير. Factory test reports provided for each manufactured unit with traceability to accredited laboratories. Partial discharge levels verified per GB20840 requirements.

Installation & Dimensions

  • Outline dimensions and mounting details are provided in the dimensional drawings.
  • The transformer shall be securely mounted using the four mounting holes in the steel channel base.
  • Installation orientation is flexible; transformer may be installed in any position due to compact, lightweight design.
  • Primary connection per utility المعايير for 10kV للخارج systems.
  • Secondary terminals feature protective covers; wiring access through designated output holes.
  • Anti-theft measures integrated into secondary terminal covers per design.
  • Adequate clearance shall be maintained for insulation, heat dissipation, and maintenance access per applicable electrical safety codes.

Outlines

JDZW-10R / JDZW2-10 Installation Dimensions

PRESERVED url 167

PRESERVED url 166

Connection Diagrams

PRESERVED url 165

Wiring Diagram 1-2: Single Output Configuration (10000/100V or 10000/220V)

PRESERVED url 164

Wiring Diagram 3-4: Dual Output Configuration (10000/100/100V or 10000/100/220V)

Safety Notice: Primary voltage must be de-energized and grounded before any installation, wiring, or maintenance work. All work shall comply with local electrical safety regulations and utility practices for للخارج 10kV installations.

Safety Notes

  • Primary circuit must be de-energized, isolated, and reliably grounded before any work on the transformer.
  • Voltage transformer secondary circuits may be left open-circuit safely; however, proper حمل connection is required for accurate operation.
  • Secondary terminal protective covers shall be maintained in place except during authorized wiring work.
  • Anti-theft mechanisms shall be engaged after wiring completion to prevent unauthorized access.
  • Installation on للخارج support structures must ensure structural integrity and electrical clearances per applicable codes.
  • All installation and maintenance work shall comply with local electrical safety regulations and utility practices.

Ordering Information

When placing an order, the required configuration shall be specified according to the local grid requirements, applicable المعايير, and project technical specification. The following parameters shall be clearly stated for technical confirmation and production release:

  • Model designation (JDZW-10R or JDZW2-10)
  • Rated voltage ratio (10000/100V, 10000/220V, 10000/100/100V, 10000/100/220V, or custom)
  • Accuracy requirements (قياس: 0.2, 0.5, 1st Class, 3rd Class / dual-core: 0.2/0.2, 0.5/0.5, 0.2/0.5 / حماية: 6P as applicable)
  • Rated output capacity (VA) matched to connected حمل for each secondary winding
  • Insulation level (المعيار: 12/42/75 kV or project-specific requirements)
  • Environmental conditions (temperature range, altitude, pollution level, special environmental factors)
  • Custom requirements (if applicable): special voltage ratios, output configurations, terminal arrangements, mounting provisions, or additional protective features

If local utility or project requirements apply (e.g., custom voltage ratios, special insulation levels, unique terminal configurations, additional environmental حماية, specific mounting requirements, documentation language, or required certificates), specify them at the ordering stage. Custom configurations shall be confirmed by technical agreement and final data sheet prior to production.

Customization & Engineering Support

The JDZW-10R and JDZW2-10 series support extensive التخصيص to meet diverse project requirements. التخصيص options include:

  • Tailored voltage ratios beyond المعيار configurations
  • Custom فئة الدقة combinations for dual-core applications
  • Modified output capacity specifications
  • Enhanced insulation levels for high-altitude or severe pollution environments
  • Special terminal configurations and mounting provisions
  • Additional environmental حماية features

Engineering support available for حمل calculation and secondary circuit design, فئة الدقة selection for قياس and حماية applications, insulation coordination for challenging environmental conditions, system integration guidance for للخارج distribution networks, compliance documentation and certification support.

FAQs

A: These transformers are designed for voltage measurement, energy قياس, and relay حماية in 10kV للخارج distribution systems, making them ideal for medium-voltage power distribution networks with ungrounded neutral configurations.
A: The fully cast راتنج الإيبوكسي البناء provides exceptional resistance to UV radiation, electrical arcing, moisture ingress, and environmental aging. This sealed design ensures reliable long-term للخارج performance with minimal maintenance requirements, even in challenging environmental conditions.
A: These transformers operate reliably in ambient temperatures ranging from -25°C to +40°C, making them suitable for a wide variety of للخارج climatic conditions including cold regions and moderate temperature zones.
A: Yes. JDZW-10R and JDZW2-10 transformers can be extensively customized with tailored voltage ratios, secondary output capacities, فئة الدقة combinations, and insulation levels to meet unique system requirements. Contact our engineering team for custom configuration support.
A: Yes. JDZW-10R transformers are designed to comply with pollution class II المعايير, ensuring reliable performance in moderate pollution environments. The sealed راتنج الإيبوكسي البناء prevents contamination ingress and maintains insulation integrity.
A: These transformers require minimal maintenance. Recommended maintenance includes periodic visual inspection of physical condition, cleaning of surface contaminants from راتنج الإيبوكسي housing, verification of terminal cover security and anti-theft mechanisms, and checking mounting hardware tightness. No internal maintenance is required during normal service life.
A: Single-output configurations (10000/100V or 10000/220V) provide one secondary winding for dedicated قياس or control applications. Dual-output configurations (10000/100/100V or 10000/100/220V) feature two independent secondary اللفات, each with separate فئة الدقة and output capacity specifications, enabling simultaneous قياس and control/حماية functions from a single transformer.
A: The secondary terminal protective covers include integrated anti-theft mechanisms that prevent unauthorized access to wiring connections. These features are particularly important for للخارج installations in accessible locations, protecting against tampering and unauthorized disconnection of قياس circuits.
A: Compliance governed by IEC186, GB1207-2006, GB20840.1-2010, and GB20840.3-2013. Factory test reports provided for each unit including routine tests, partial discharge testing per GB20840 requirements, dielectric tests, vibration testing, and accuracy verification. All documentation traceable to accredited laboratories.
A: المعيار المواصفات is for altitudes up to 2000 meters. Installations above 2000m altitude require engineering review and may necessitate enhanced insulation levels or other modifications. Provide detailed altitude and environmental parameters at ordering stage for proper transformer المواصفات.