JSZV12-10R Combined محول الجهد, 10kV Dual الإخراج, Fused

JSZV12-10R Combined محول الجهد, 10kV Dual الإخراج, Fused

10kV combined VT with fuses, dual outputs, epoxy cast

  • Dual الإخراج: 100V القياس and 220V الطاقة المساعدة combined unit
  • 0.2/0.5 accuracy, 20-60 VA burden per GB/T 20840.4-2015 المعيار
  • راتنج الإيبوكسي cast with integrated A/B/C phase حماية الصمامات
  • V-connection design, 12/42/75 kV insulation per GB 311.1-2012

 

Product Overview

Functional Definition

The JSZV12-10R series combined voltage transformers are precision electromagnetic instruments designed for accurate voltage measurement, قياس الطاقة, and الطاقة المساعدة supply in medium-voltage AC power systems. These combined transformers integrate voltage transformation with built-in high-voltage حماية الصمامات on each phase, utilizing electromagnetic induction principles to provide galvanically isolated الجهد الثانوي signals proportional to الجهد الأولي.

Key Ratings

Item Specification (per order / nameplate)
System voltage class 10 kV class (للداخل معدات التبديل and distribution applications)
Rated frequency 50 Hz (60 Hz available upon request)
Rated voltage ratio 10000/100 V (القياس) or 10/0.1/0.22 kV (dual الإخراج with الطاقة المساعدة)
Secondary voltage outputs 100 V (precision القياس) and 220 V (الطاقة المساعدة / control circuit supply)
Accuracy classes 0.2 and 0.5 as specified
Rated burden 20 VA (0.2 class), 60 VA (0.5 class), per ordered specification
Maximum output 500-600 VA (short-time)
Insulation level 12/42/75 kV (Um/Ud/Up)
Configuration Three-phase V-connection (two أحادي الطور units) with integrated fuses on A, B, C phases
Fuse protection Integrated high-voltage fuses on primary اللفات (A/B/C phases) with accessible secondary terminals for maintenance
Applicable standards GB/T 20840.3-2013, GB/T 20840.4-2015, GB 311.1-2012, JJG 314-2010

Product Shows

PRESERVED 180

Working Principle

Operating on Faraday’s law of electromagnetic induction, the combined محول الجهد features high-grade silicon steel laminated cores with primary اللفات connected to the جهد النظام and secondary اللفات delivering standardized الإخراج voltages. The dual-الإخراج configuration provides 100 V for precision القياس and energy measurement, while the 220 V الإخراج serves as الطاقة المساعدة for control systems, circuit breakers, and الحماية relays. Integrated high-voltage fuses on each phase primary winding provide short-circuit الحماية and prevent fault propagation.

System التطبيق Position

  • Medium Voltage Distribution: 10kV للداخل معدات التبديل, لوحات التوزيع, and ring main units
  • Energy القياس: Revenue-grade voltage measurement for electricity billing systems
  • Auxiliary Power Supply: 220 V AC power source for قواطع الدوائر control, الحماية relays, and monitoring equipment
  • Protection Circuits: Voltage-dependent الحماية schemes including فرط الجهد, انخفاض الجهد, and earth fault detection
  • SCADA Integration: Voltage monitoring and data acquisition in supervisory control systems

Structural Overview

Fully-enclosed راتنج الإيبوكسي cast البناء with premium cold-rolled silicon steel cores ensures superior insulation performance, moisture resistance, and long-term stability. The combined design integrates dual secondary outputs in a compact footprint suitable for للداخل معدات التبديل البيئات. Integrated حماية الصمامات on all three phases provides reliable short-circuit interruption with easy fuse replacement via accessible secondary terminals without affecting operation.

Model Designation

PRESERVED 179

Model Code Explanation

  • J — Combined instrument transformer (voltage + الحماية)
  • S — للداخل النوع (室内)
  • Z — Cast-resin (epoxy) insulated, fully enclosed structure
  • V — محول الجهد function
  • 12 — Design series / platform iteration
  • 10 — Voltage class (kV)
  • R — Integrated حماية الصمامات (熔断器)

Configuration Options

The JSZV12-10R is available in multiple voltage class variants (10kV, 6kV, 3kV) and الإخراج configurations:

  • JSZV12-10R: 10kV class with dual الإخراج (100V القياس + 220V الطاقة المساعدة)
  • JSZV12-6R: 6kV class variant
  • JSZV12-3R: 3kV class variant
  • JSZV-10-10R: Alternative 10kV configuration with single 100V output

All variants feature integrated حماية الصمامات and fully-enclosed راتنج الإيبوكسي البناء. Selection depends on جهد النظام class and الإخراج requirements.

Service Conditions

The JSZV12-10R series combined voltage transformers are designed for للداخل operation under normal ظروف الخدمة in medium-voltage power systems.

  • Installation environment: للداخل التركيب only
  • Altitude: Not exceeding 1000 m above sea level (higher altitude configurations available upon engineering confirmation)
  • Ambient temperature: −5 °C to +40 °C
  • Relative humidity: ≤ 80% (without condensation)
  • Environmental conditions: Free from corrosive gases, vapors, or conductive deposits; free from explosive or flammable media; no conductive dust (carbon, metallic particles); no severe vibration, mechanical shock, or impact
Engineering Note: The التركيب location shall comply with applicable electrical safety regulations and provide stable operating conditions throughout the transformer’s service life. For applications exceeding المعيار ظروف الخدمة (higher altitude, extended temperature range, or corrosive البيئات), contact technical support for customized specifications.

Construction

Construction Design

  • Structure: Fully-enclosed combined النوع for للداخل معدات التبديل integration
  • Insulation: راتنج الإيبوكسي cast insulation system with superior dielectric properties
  • Core material: Premium cold-rolled silicon steel laminations for low losses and high accuracy
  • Fuse integration: High-voltage fuses on A, B, C phase primary اللفات with coordinated interrupting capacity
  • Secondary terminals: Accessible terminal blocks for easy fuse replacement without affecting operation
  • Configuration: ثلاثي الطور V-connection or two independent أحادي الطور units

The راتنج الإيبوكسي casting provides stable insulation properties and resistance to moisture, contamination, tracking, and aging for long-term للداخل service. The integrated fuse design prevents fault propagation and enhances system reliability.

Windings & Terminal Marking

  • Primary terminals (per phase): A / B / C (high-voltage side)
  • Secondary terminals (100V القياس): a / x (per phase)
  • Secondary terminals (220V auxiliary): a1 / x1 (where applicable)
  • Neutral/ground terminal: N or dedicated التأريض point

Terminal markings follow المعيار محول الجهد polarity conventions. Under normal operating conditions, when primary terminal A is positive, secondary terminal a is positive (additive polarity). Correct terminal identification shall be observed to ensure القياس accuracy and الحماية coordination.

Technical Data

This section provides selection-oriented البيانات الفنية for the JSZV12-10R series للداخل, fully-enclosed combined محول الجهد with integrated fuses, used in 10 kV class AC systems (50 Hz). Data shown below is intended for preliminary selection of voltage ratios, فئة الدقة combinations, rated burdens, and dual-الإخراج configurations.

Definitions: Accuracy class combination indicates available القياس accuracy grades per الإخراج. Rated burden (VA) is specified per secondary circuit. Maximum output is the short-time overload capability. Insulation level follows Um/Ud/Up notation per GB 311.1-2012.

Notation: Dual-الإخراج models provide both 100V (القياس) and 220V (الطاقة المساعدة); single-الإخراج models provide 100V only. Acceptance shall be based on nameplate values and the factory test report.

Data Reference

Auxiliary Power الإخراج Specifications (قواطع الدوائر Control / Relay Supply)

Application Note: The 220V الطاقة المساعدة الإخراج shall not exceed 115% of rated voltage under continuous operation. This الإخراج is suitable for قواطع الدوائر control coils, الحماية relays, and monitoring equipment power supply.
Type Rated Voltage
Ratio (V)
Accuracy Class
& Rated
الإخراج (VA)
Max
الإخراج (VA)
Rated
Insulation
Level (KV)
0.2 0.5 1 6p
JSZW3-10 10000/3/100/3/100/3 15 30 60 50 300 12/42/75
JSZW3-6 6000/3/100/3 7.2/32/60
JSZW3-3 3000/3/100/3 3.6/20/40
Application Engineering Support: التطبيق-specific recommendations may include burden calculation, voltage factor assessment, ferroresonance evaluation, thermal duty verification, and معدات التبديل integration guidance based on project المواصفة.

Standards & Normative References

Standard Title Application
GB/T 20840.3-2013 Instrument Transformers – Part 3: Electromagnetic Voltage Transformers Primary محول الجهد requirements
GB/T 20840.4-2015 Instrument Transformers – Part 4: Combined Transformers Combined instrument transformer specific requirements
GB 311.1-2012 Insulation Coordination for High-Voltage Transmission Equipment Insulation level المواصفة and coordination
JJG 314-2010 Verification Regulation of Voltage Transformers Accuracy verification and calibration procedures
IEC 61869-3 Instrument Transformers – Part 3: Additional Requirements for Inductive Voltage Transformers International محول الجهد requirements (reference)
IEC 61869-5 Instrument Transformers – Part 5: Additional Requirements for Combined Transformers International محول مجمع requirements (reference)
GB/T 16927 High-Voltage Test Techniques Dielectric test procedures
DL/T 866 Technical المواصفة for Voltage Transformers in Power Systems Power system التطبيق guidelines (where applicable)

Factory Test Compliance

  • Routine tests per applicable GB/IEC requirements (including polarity/marking verification, ratio accuracy, phase displacement, and burden accuracy per specified class)
  • Dielectric tests per insulation coordination requirements (power-frequency withstand, impulse withstand per GB 311.1-2012)
  • Partial discharge test where specified by project requirement or applicable standard
  • Temperature rise test to verify thermal performance under rated and maximum burden conditions
  • Fuse coordination test to verify integrated fuse interrupting capability and selectivity
  • Visual and dimensional inspection including marking conformity and workmanship verification
  • Type and special tests as required by project المواصفة or certification authority

Installation & Dimensions

Installation Environments

  • Outline dimensions and mounting details are provided in the dimensional drawings.
  • The محول مجمع shall be securely mounted using the designated fixing holes or bracket assembly.
  • Primary connection may be made via busbar or bolted cable terminals depending on معدات التبديل configuration.
  • Secondary circuits shall be wired to designated terminal blocks maintaining proper phase identification.
  • Adequate clearance shall be maintained for insulation coordination, heat dissipation, fuse accessibility, and الصيانة access.
  • Fuse replacement can be performed via secondary terminal access without de-energizing the التركيب (per manufacturer procedure).

Outlines

PRESERVED 178

Connection Diagrams

Three-phase V-connection (المعيار configuration):

  • Two أحادي الطور units connected in open-delta (V) configuration
  • Provides ثلاثي الطور voltage measurement capability with two transformers
  • Primary terminals: A-N, B-N (or A-B-C for wye-connected systems)
  • Secondary 100V terminals: a-x (per phase)
  • Secondary 220V terminals: a1-x1 (where applicable for الطاقة المساعدة)
Safety Notice: Secondary circuits must never be left open when energized. Before الصيانة or fuse replacement, follow manufacturer procedures and applicable electrical safety regulations. One point of each secondary circuit must be reliably grounded.

Safety Notes

  • Secondary circuits must never be left open when the transformer is energized, as dangerous جهد عالي may appear across open terminals.
  • During inspection or الصيانة, de-energize primary circuits or follow manufacturer lock-out/tag-out procedures.
  • Fuse replacement shall be performed only by qualified personnel following manufacturer instructions.
  • One point of each secondary circuit shall be reliably grounded in accordance with GB 50150 or applicable local المعايير.
  • The 220V الطاقة المساعدة الإخراج shall be protected by appropriately rated secondary circuit breakers or fuses per load requirements.
  • All التركيب and الصيانة work shall comply with DL 408 (Electric Power Safety Work Regulations) or local electrical safety regulations.

Ordering Information

When placing an order, the required configuration shall be specified according to the local grid requirements, applicable المعايير, and project technical specification. The following parameters shall be clearly stated for technical confirmation and production release:

Selection Guidance

  • System voltage class (10kV, 6kV, or 3kV)
  • Voltage ratio (primary/secondary voltages)
  • Output configuration (dual 100V+220V or single 100V)
  • Accuracy requirements (0.2 or 0.5 class)
  • Rated burden (VA) per secondary circuit
  • Connection configuration (V-connection or أحادي الطور)
  • Insulation level (if non-المعيار)
  • Fuse rating (if specific coordination required)

For applications with extended temperature range, higher altitude operation, enhanced corrosion الحماية, specific fuse coordination, or special certificates, specify requirements at ordering stage. Custom configurations require technical agreement and final data sheet confirmation prior to production.

Customization Options

Available upon request:

  • Extended temperature range: Operation beyond −5°C to +40°C المعيار range
  • Custom voltage ratios: Non-المعيار primary or secondary voltages
  • Enhanced environmental الحماية: Conformal coating or special sealing for corrosive environments
  • Alternative الإخراج configurations: Custom الجهد الثانوي or burden combinations
  • Specific fuse coordination: Custom fuse ratings for project الحماية schemes
  • High-altitude operation: Enhanced insulation for installations above 1000m elevation

FAQs:

The JSZV12-10R is suitable for للداخل 10kV systems requiring both precision voltage measurement (100V الإخراج) and الطاقة المساعدة supply (220V الإخراج) for قواطع الدوائر control, الحماية relays, and monitoring equipment.

The 100V الإخراج provides precision القياس for revenue-grade energy measurement; the 220V الإخراج serves as الطاقة المساعدة for قواطع الدوائر control coils, الحماية relays, and SCADA equipment, eliminating the need for separate auxiliary transformers.

High-voltage fuses are integrated on A, B, C phase primary اللفات. In the event of internal transformer fault or severe overload, fuses interrupt current flow to prevent damage propagation. Fuses can be replaced via accessible secondary terminals without affecting normal operation.

Yes. The المعيار ثلاثي الطور V-connection uses two أحادي الطور units. These can also operate independently for أحادي الطور applications or phase-selective measurement requirements.

0.2 class for revenue القياس applications requiring high accuracy per JJG 314-2010; 0.5 class for general measurement and monitoring where lower accuracy is acceptable. Selection depends on utility القياس requirements and التطبيق criticality.

For 100V القياس الإخراج, sum the VA ratings of connected meters and calculate التوصيلات losses. For 220V auxiliary الإخراج, sum control equipment power consumption (قواطع الدوائر coils, relays, indicators). Ensure total burden per circuit does not exceed rated values (20-60 VA depending on configuration).

The notation 12/42/75 kV represents Um/Ud/Up per GB 311.1-2012: Um = maximum جهد النظام (12kV), Ud = power-frequency withstand voltage (42kV), Up = lightning impulse withstand voltage (75kV). This مستوى العزل is المعيار for 10kV class equipment.

Routine الصيانة is minimal. Periodic inspection includes visual examination, terminal tightness verification, and fuse condition check. Fuse replacement (if required) can be performed without de-energizing the التركيب per manufacturer procedure. Accuracy verification per JJG 314-2010 may be required based on utility regulations.

Nameplate and factory test report prevail. Primary المعايير are GB/T 20840.3-2013 (voltage transformers), GB/T 20840.4-2015 (combined transformers), GB 311.1-2012 (insulation coordination), and JJG 314-2010 (verification). Unit test certificates provide traceability to accredited laboratories.

The 220V الإخراج shall not exceed 115% of rated voltage under continuous operation per قواطع الدوائر control equipment requirements. Voltage tolerance depends on جهد النظام regulation and transformer design. If tighter regulation required, specify voltage stabilization or regulation equipment for the الطاقة المساعدة circuit.