LAJ-10Q, LFZBJ-10KV Cast Resin Current Transformers (Through-Wall)

LAJ-10Q, LFZBJ-10KV Cast Resin Current Transformers (Through-Wall)

نظرة عامة على المنتج التعريف الوظيفي The LAJ-10Q and LFZBJ-10 series current transformers are through-wall type, epoxy r...

نظرة عامة على المنتج

التعريف الوظيفي

The LAJ-10Q and LFZBJ-10 series current transformers are through-wall type, epoxy resin cast precision electromagnetic instruments designed for accurate current measurement, energy metering, and relay protection applications in medium-voltage AC power systems. The LAJ-10Q series is specifically engineered for demanding operational environments, providing stable and reliable performance under complex and harsh conditions. These transformers utilize electromagnetic induction principles to provide galvanically isolated secondary current signals proportional to primary current.

التصنيفات الرئيسية

البند المواصفات (حسب الطلب / لوحة البيانات)
System voltage class 10 kV class (indoor/outdoor distribution applications)
Rated frequency __PRESERV60 Hz0__ or 60 Hz
Rated secondary current 5 A (قياسي)
Accuracy classes قياس and/or protection cores: 0.2S, __PRE0.5VED_11_56__, 0.5, 10P10, 10P15
Rated burden Per core/winding كما هو محدد (VA): 10-15 VA typical
حمل power factor cosφ = 0.8 (lagging) ما لم يتم تحديده بخلاف ذلك
Short-circuit withstand Ith: Up to __PRESE1 s90 kA1__ (1 s); Idyn: Up to 90 kA (peak)
Primary current range __PRESE3000 A_0__ to 3000 A
Applicable standards __PRESERVED_4_IEC 61869EC 61869-2; GB/T 20840.1 / 20840.IEC 600448-1997; IEC 60044-1
Mechanical variants LAJ-10 / LAJ-10Q / LFZBJ-10 (Single-turn, multi-turn, busbar types)

عرض المنتج

LAJ 10Q LFZBJ 10KV pics

مبدأ العمل

Operating on Faraday’s law of electromagnetic induction, the transformer features a toroidal magnetic core with primary conductor passing through the window aperture and secondary windings wound around the core. The magnetic flux generated by primary current induces proportional voltage in the secondary winding, delivering standardized output current through connected burden. The epoxy resin encapsulation ensures complete insulation and protection against environmental factors.

System التطبيق Position

  • Medium Voltage Distribution: 10kV switchgear, distribution panels, and power distribution systems
  • Energy قياس: Revenue-grade electricity measurement systems with 0.2S class accuracy
  • حماية Circuits: Overcurrent, differential, and distance protection schemes (10P10, 10P15 class)
  • SCADA Integration: Supervisory control and data acquisition systems
  • Harsh Environment Applications: LAJ-10Q variant specifically designed for challenging operational conditions

نظرة عامة هيكلية

The LAJ-10Q series through-wall type current transformers are available in three structural configurations: single-turn, multi-turn, and busbar type arrangements, all featuring epoxy resin cast construction with fully-enclosed or semi-enclosed design. Products rated 300A and below utilize semi-enclosed structure for ease of installat800A while 400-800A ratings employ fully sealed construction for enhanced environmental protection and mechanical strength. The through-wall mounting configuration enables compact installation in switchgear while maintaining excellent electrical clearance and creepage distances.

تسمية الموديل

LAJ 10 LFZBJ 10KV high voltage CT products type

Model Code الشرح

LAJ-10 / LAJ-10Q

  • L = محول التيار (CT)
  • A = Bulkhead / Through-wall mounting (panel or wall-mounted)
  • J = Enhanced / reinforced design (mechanical & insulation robustness)
  • Q = All-condition (full-duty) variant — designed for complex/harsh operating conditions
  • 10 = Voltage class 10 kV

LFZBJ-10 (10 kV class)

  • L = محول التيار (CT)
  • F = Cast-resin insulated (epoxy resin casting)
  • Z = Busbar separated / busbar arrangement (structure-related code)
  • B = With protection function option (protection core configuration available)
  • J = Enhanced / reinforced design
  • 10 = Voltage class 10 kV

اختلافات المتغيرات

LAJ-10: المعيار through-wall current transformer for general indoor applications with normal environmental conditions.
LAJ-10Q: All-conditions enhanced variant designed specifically for harsh and complex operational environments. Features improved environmental resistance while maintaining all electrical specifications of the قياسي LAJ-10 series.
LFZBJ-10: للداخل support-type variant with enclosed construction, suitable for قياسي switchgear installations where through-wall mounting is not required.
All variants are electrically equivalent when specified with the same ratio, accuracy classes, burdens, and Ith/Idyn ratings. Selection between variants is based on mounting constraints and environmental conditions.

ظروف الخدمة

The LAJ-10Q series current transformers are designed for operation under normal and harsh service conditions in medium-voltage power systems.

المعيار Operating Environment

  • Installation environment: للداخل or outdoor installation (LAJ-10Q rated for harsh conditions)
  • Altitude: Not exceeding 1000 m above sea level (higher altitude applications require engineering confirmation)
  • Ambient temperature: −__PRESERV40 °C2__ to +40 °C
  • Relative humidity: ≤ 90% at +20 °C reference temperature
  • Environmental conditions: Free from corrosive gases, chemical contamination, or substances affecting insulation performance; no severe vibration, mechanical shock, or impact

Enhanced Environment Rating

  • Harsh environment capability: Specifically designed for complex and demanding operational conditions
  • Enhanced protection: Superior resistance to moisture, contamination, and thermal cycling
  • Operational reliability: Maintains performance under adverse environmental conditions
ملاحظة هندسية: The LAJ-10Q series is recommended for installations where environmental conditions exceed قياسي ratings or where enhanced operational reliability is required. The installation location shall comply with applicable electrical safety regulations and provide stable operating conditions throughout the transformer’s service life.

البناء

البناء Design

  • Structure: Through-wall (bushing) type for panel/wall mounting; Support type available (LFZBJ-10)
  • Insulation: راتنج الإيبوكسي cast insulation (fully enclosed or semi-enclosed depending on rating)
  • Core: High-quality silicon steel laminations in ring-type configuration
  • Primary winding: Single-turn, multi-turn, or busbar conductor through window aperture
  • Secondary winding: Precision-wound coils on toroidal core
  • Enclosure rating: Semi-enclosed (≤300A); Full800Aaled (400-800A)

The epoxy resin casting provides stable insulation properties, excellent mechanical strength, and resistance to moisture, contamination, and aging for long-term service. The LAJ-10Q variant features enhanced material formulation for superior performance in harsh environments.

اللفات & وضع العلامات على المحطات

  • Primary terminals: P1 / P2 (busbar exits from both ends for through-wall mounting)
  • Secondary terminals (Group 1): S1 / S2 (__PRES1S2ED_14_10__ / 1S2 for multi-core units)
  • Secondary terminals (Group 2): __PRES2S2ED_14_1__ / 2S2 (حيث ينطبق for dual-core configuration)
  • Terminal location: Secondary terminals positioned at bottom mounting side for convenient access
  • Terminal type: Exposed screw terminals for ease of connection

Terminal markings follow قياسي CT polarity conventions per IEC 61869-2 and GB 1208-1997. Under normal operating conditions, the reference current direction is defined from P1 to P2. Correct terminal identification shall be observed to ensure proper metering and protection performance.

البيانات الفنية

This section provides selection-oriented technical data for the LAJ-10Q and LFZBJ-10 series through-wall and support-type, cast-resin current transformers used in 10 kV clas__PRESER60 Hz_187__systems (50 Hz / 60 Hz). Data shown below is intended for preliminary selection of accuracy class combinations, rated burdens, and short-circuit withstand capability.

Definitions:
فئة الدقة combination indicates available metering/protection cores in one CT (multi-core configuration may apply).
Rated output (VA) is specified per secondary core.
Ith is the rated short-time thermal current (1 s duration).
Idyn is the rated dynamic current (peak value).

Notation: All values shown are per nameplate and factory test report. Customization is available for specific project requirements.

مرجع البيانات

Rated Primary
Current (A)
فئة الدقة
Combination
المخرج المقنن (VA) Rated Short-time
Current (kA/1s)
Rated Dynamic
Current (kA)
0.2S 0.2 0.5 10P10 10P15
5~100 0.__PRE2SRVED_9_2__/0.2S

0.210.2

0.2S/10P10

0.2/10P10

0.5/10P10

0.2/10P15

0.5/10P15

 

10 10 10 15 15 100|1n 250|1n
150 13.5 34
200 18 45
300 27 67
400 30 75
500 36 90
600
750 40
800
1000
2000~3000

المعايير & Normative References

المعيار العنوان التطبيق
IEC 61869-1 Instrument Transformers – Part 1: General Requirements General requirements for instrument transformers
IEC 61869-2 Instrument Transformers – Part 2: Additional Requirements for Current Transformers CT-specific requirements and testing procedures
GB/T 20840.1 Instrument Transformers – Part 1: General Requirements National قياسي (aligned with IEC 61869 framework)
GB/T 20840.2 Instrument Transformers – Part 2: Current Transformers National CT requirements (aligned with IEC 61869-2)
GB 1208-1997 Current Transformers National CT قياسي for electrical performance
IEC 60044-1 Instrument Transformers – Part 1: Current Transformers International قياسي reference
IEEE C57.13 المعيار Requirements for Instrument Transformers Optional (North America project reference)

امتثال اختبار المصنع

  • Routine tests per applicable IEC/GB requirements (including polarity/marking verification, ratio verification, and accuracy verification per specified class and burden)
  • Dielectric tests per insulation coordination requirements and applicable قياسي (power frequency withstand voltage test)
  • Partial discharge test حيث تم تحديده by the project requirement
  • Visual and dimensional inspection including marking verification and workmanship conformity
  • Temperature rise test for rated continuous current
  • Short-circuit withstand test (Ith and Idyn) per project specification
  • Type and special tests as required by the project specification

Installation & Dimensions

  • Outline dimensions and mounting details vary by current rating and structural type (single-turn, multi-turn, busbar)
  • The transformer shall be securely mounted using the designated fixing holes and hardouware
  • Primary conductor connection is made via busbar passing through the window aperture
  • Adequate clearance shall be maintained for insulation coordination, heat dissipation, and maintenance access
  • Through-wall mounting requires proper panel cutout dimensions per rating
  • Consult factory dimensional drawings for specific current rating and variant

Outline

LAJ 10 LFZBJ 10KV high voltage CT outline 1

Mounting Configurations

Through-Wall Type (LAJ-10, LAJ-10Q):

  • Primary busbar passes through panel wall opening
  • Mounting flanges secure transformer to panel surface
  • Secondary terminals accessible from bottom mounting side

Support Type (LFZBJ-10):

  • Post-type mounting on switchgear base plate
  • Suitable for indoor enclosed switchgear applications
  • Compact footprint for space-constrained installations
إشعار السلامة: Secondary circuits must never be left open when energized. Before maintenance, short-circuit and reliably ground the secondary in accordance with local electrical safety regulations. Failure to follow proper procedures may result in dangerous high voltage on secondary terminals.
  • Secondary circuit must never be left open when the transformer is energized, as dangerous high voltage may appear across the secondary terminals
  • During inspection or maintenance, the secondary circuit shall be short-circuited before disconnecting any instruments
  • One point of the secondary circuit should be reliably grounded in accordance with applicable standards (IEC 61869, GB standards, local codes)
  • All installation and maintenance work shall comply with local electrical safety regulations
  • Proper personal protective equipment (PPE) shall be used during installation and servicing
  • Verify de-energization of primary circuit before performing any maintenance work

When placing an order, the required configuration shall be specified according to the local grid requirements, applicable standards, and project technical specification. The following parameters shall be clearly stated for technical confirmation and production release:

Required المواصفات Parameters

  • Rated primary current / transformation ratio (e.g., 100/__PRESER__PRESER5AD_9_20__D_9_12__, __PRESER600/5A_64__, 600/5A)
  • Rated secondary current (__PRESERVED_9_1 A قياسي; 1 A متاح عند الطلب)
  • التطبيق and accuracy requirements (metering and/or protection accuracy class combination)
  • Rated burden (VA) for each secondary core/winding
  • Short-circuit withstand requirements: Ith (1 s) and Idyn (peak) based on system fault level
  • Variant selection: LAJ-10 (قياسي), LAJ-10Q (harsh environment), or LFZBJ-10 (support type)
  • Structural type: Single-turn, multi-turn, or busbar configuration

Optional Specifications (if applicable)

  • Insulation level requirements beyond قياسي
  • Partial discharge limit (if specified)
  • Terminal arrangement preferences
  • Mounting constraints or dimensional requirements
  • Documentation language preferences
  • Required certificates (type test, routine test, material certificates)
  • Special environmental conditions (temperature, humidity, altitude)

If local utility or project requirements apply (e.g., specific insulation coordination, partial discharge limits, terminal arrangements, mounting constraints, documentation language, or certification requirements), specify them at the ordering stage. Special configurations shall be confirmed by technical agreement and final data sheet prior to production.

الأسئلة الشائعة

Select Ip based on feeder load current and measuring range, aiming for 25–100% of Ip in normal operation. Verify Ith and Idyn meet site fault levels and protection requirements.

Specify separate cores for metering and protection with their own accuracy class and rated burden (VA). Common combinations are 0.2S/10P10, __PRESERVED_110.24__/10P10, or 0.2/10P15.

Sum the meter/relay burdens and wiring losses. Use VA = Is² × (Rload + Rwiring) and add 20-30% margin. Select the nearest قياسي VA (e.g., __PRESER15VA9_158__ or 15VA).

Ith and Idyn must meet or exceed the prospective short-circuit levels. Acceptance is based on nameplate and routine test report, per IEC 61869-2.

LAJ-10 is the قياسي type. LAJ-10Q is enhanced for harsher environments. LFZBJ-10 is a support/post type for enclosed switchgear. Electrical ratings are the same; selection depends on mounting and environment.

Never open-circuit the secondary when energized. Short and ground the secondary before maintenance. Follow P1/P2, S1/S2 markings for correct polarity and ensure secondary grounding for safety.