LB-10W للخارج Oil-Immersed محول التيارs (للخارج)

LB-10W للخارج Oil-Immersed محول التيارs (للخارج)

نظرة عامة على المنتج Functional Definition The LB-10W series للخارج Oil-Immersed محول التيارs are precision electromagne...

نظرة عامة على المنتج

Functional Definition

The LB-10W series للخارج Oil-Immersed محول التيارs are precision electromagnetic instruments designed for accurate current measurement, energy metering, and relay protection applications in 10 kV medium-voltage AC power systems. These oil-immersed transformers utilize electromagnetic induction principles with steel-tank construction to provide galvanically isolated secondary current signals proportional to primary current, suitable for both indoor and outdoor installations.

التصنيفات الرئيسية

البند المواصفات (per order / nameplate)
System voltage class 10 kV class (indoor and outdoor applications)
مصنّف frequency 50 Hz
مصنّف secondary current 5 A
مصنّف primary current range 20 A to 400 A
Continuous thermal rating 120% of rated primary current (continuous operation)
فئة الدقةes قياس: 0.2, 0.5; حماية: 10P10
مصنّف burden 10 VA, 15 VA, 20 VA per core/winding as specified
حمل power factor cosφ = 0.8 (lagging) unless otherwise specified
Short-circuit withstand Ith: 1.8 kA to 30 kA (1 s); Idyn: 3.0 kA to 50 kA (peak) per rating
Thermal stability factor 187.5 (high thermal loading capability)
عزل medium Mineral insulating oil with vacuum filtration and vacuum oil-filling process
Applicable standards IEC 61869-1 / IEC 61869-2; GB/T 20840.1 / 20840.2; GB 1208-1997
تركيب location للداخل or outdoor

Product Shows

LB 10 current transformers 1

مبدأ العمل

Operating on Faraday’s law of electromagnetic induction, the transformer features a toroidal magnetic core with primary conductor passing through the aperture and secondary windings wound around the core. The magnetic flux generated by primary current induces proportional voltage in the secondary winding, delivering standardized output current through connected burden. The oil-immersed design provides superior insulation and thermal management for outdoor environments.

System التطبيق Position

  • Medium جهد Distribution: 10kV switchgear, distribution panels, and outdoor substations
  • طاقة قياس: Revenue-grade electricity measurement systems with 0.2 and 0.5 class accuracy
  • حماية Circuits: Overcurrent, differential, and distance protection schemes (10P10 class)
  • للخارج التطبيقs: Pole-mounted installations, overhead line monitoring, and exposed distribution equipment
  • High-Altitude تركيبs: Suitable for installations up to 4000 m above sea level with appropriate derating

Structural Form Overview

Steel-tank oil-immersed construction with fully-enclosed design ensures superior insulation performance, moisture resistance, environmental protection, and mechanical strength for outdoor service. The oil-filled tank provides effective cooling and long-term stability in harsh environmental conditions. Equipped with oil filling valve, weather-protective cap, pressure relief vent, and internal diaphragm to prevent oil oxidation. The post-type mounting configuration provides versatile installation options for both indoor switchgear and outdoor pole-mounting applications.

تعيين الموديل

LB 10W huganqi

Model Code Explanation

  • L — التيار transformer (CT)
  • B — Protective configuration (metering and protection application capability)
  • 10 — جهد class (kV)
  • W — للخارج service design (weather-resistant construction)

Configuration Options

LB-10W current transformers are available in multiple configurations to suit different application requirements:

  • Single ratio + single secondary winding: Basic configuration for simple metering or protection applications
  • Single ratio + dual secondary windings: Simultaneous metering and protection with independent accuracy specifications
  • Dual ratio + single secondary winding: Switchable primary current rating with single output
  • Dual ratio + dual secondary windings: Maximum flexibility with switchable ratios and independent metering/protection cores

ظروف الخدمة

The LB-10W series current transformers are designed for indoor and outdoor operation under the following normal service conditions in medium-voltage power systems:

  • تركيب environment: للداخل installation or outdoor installation (pole-mounted, wall-mounted, or outdoor switchgear)
  • Altitude: Standard rating up to 2000 m above sea level; extended altitude capability up to 4000 m with appropriate derating and engineering confirmation
  • Ambient temperature: −25 °C to +40 °C
  • Relative humidity: Maximum 95% (no condensation)
  • Pollution level: الفئة II per IEC 60815 (medium pollution)
  • Environmental conditions: Free from corrosive gases or vapors; free from explosive or flammable media; no severe vibration or mechanical shock that exceeds specified limits
  • Weather resistance: Designed to withstand rain, snow, ice, UV radiation, and temperature cycling in outdoor installations
Engineering ملاحظة: For installations exceeding standard service conditions (altitude >2000 m, extreme temperatures, or heavy pollution environments), consult factory engineering for rating adjustments, enhanced insulation specifications, or special construction requirements.

البناء

البناء Design

  • Structure: Steel-tank oil-immersed design for indoor and outdoor service
  • عزل: High-grade mineral insulating oil with vacuum filtration and vacuum oil-filling process to maximize dielectric strength and thermal performance
  • Core: Ring-type (toroidal) magnetic core design for accurate current transformation
  • Tank design: Sealed steel enclosure with oil filling valve, weather-protective cap, and pressure regulation vent
  • Oil preservation: Internal diaphragm system prevents direct air contact with oil, significantly reducing oxidation rate and extending service life
  • Thermal management: Natural oil circulation cooling with thermal stability factor of 187.5, suitable for high thermal loading environments
  • Weatherproofing: Corrosion-resistant external finish, rain-proof cap, and sealed terminal chamber for outdoor durability

The oil-immersed construction provides stable insulation properties, excellent cooling characteristics, resistance to environmental contamination, and long-term reliability for outdoor service. The vacuum oil-filling process ensures elimination of moisture and air bubbles for maximum dielectric integrity.

اللفات & وضع العلامات على المحطات

  • ابتدائي terminals: P1 / P2 (bushing-type or through-hole configuration depending on current rating)
  • ثانوي terminals (Group 1): 1S1 / 1S2 (typically metering core)
  • ثانوي terminals (Group 2): 2S1 / 2S2 (typically protection core, when dual-core configuration is specified)

Terminal markings follow IEC 61869 standard CT polarity conventions. Under normal operating conditions, the reference current direction is defined from P1 to P2. Correct terminal identification and polarity shall be observed to ensure accurate metering and proper protection relay operation.

Terminal Configuration ملاحظة: Actual terminal arrangement and secondary core allocation shall be confirmed from nameplate and factory documentation. Multi-core CTs may have additional secondary windings with corresponding terminal designations (3S1/3S2, etc.).

البيانات الفنية

This section provides selection-oriented technical data for the LB-10W series outdoor oil-immersed current transformer used in 10 kV class AC systems (50 Hz). Data shown below is intended for preliminary selection of rated primary current, accuracy class combinations, rated burdens, and short-circuit withstand capability.

Definitions: فئة الدقة combination indicates available metering/protection cores in one CT (single or dual-core configuration). مصنّف output (VA) is specified per secondary core. Ith is the rated short-time thermal current (1 s duration). Idyn is the rated dynamic current (peak value).

Notation: Ith and Idyn values are expressed in kA (absolute current). Acceptance shall be based on nameplate values and factory test report for the ordered configuration.

Data Reference

مصنّف
ابتدائي
التيار (A)
الدقة
الفئة
Combination
مصنّف
المخرج (VA)
Short-time
Thermal
التيار Ith (kA, 1s)
مصنّف Dynamic
التيار Idyn
(kA, peak)
ملاحظةs
20 0.2/0.2
0.2/0.5
0.5/0.5
0.2/10P10
0.5/10P10
10/10
10/15
15/15
10/20
15/20
1.8 3.0 Single or dual secondary winding configuration available
30 2.7 4.5
40 3.6 6.0
50 4.5 7.5
75 6.75 11.25
100 9.0 15.0
150 13.5 22.5
200 18.0 30.0
300 27.0 45.0
400 30.0 50.0

المعايير & Normative References

Standard Title التطبيق
IEC 61869-1 Instrument محولs – Part 1: General Requirements General requirements for current transformers
IEC 61869-2 Instrument محولs – Part 2: Additional Requirements for محول التيارs CT-specific requirements including accuracy classes, burdens, and short-circuit withstand
GB/T 20840.1 Instrument محولs – Part 1: General Requirements National standard (aligned with IEC 61869 framework)
GB/T 20840.2 Instrument محولs – Part 2: محول التيارs National CT requirements (aligned with IEC 61869-2)
GB 1208-1997 محول التيارs National CT standard where specified by project requirements
IEC 60815 Selection and Dimensioning of High-جهد Insulators for Polluted Conditions Pollution level classification and creepage distance requirements
IEC 60068-2-11 Environmental Testing – Salt Mist Optional (coastal/marine environment validation)
IEC 60076-11 طاقة محولs – Dry-Type محولs Reference for thermal evaluation and cooling systems
IEEE C57.13 Standard Requirements for Instrument محولs Optional (North America project reference)

Factory Test Compliance

  • Routine tests per IEC 61869-1/2 and GB/T 20840.1/2 requirements, including:
    • Polarity and terminal marking verification
    • Ratio and phase displacement verification
    • الدقة verification at specified class, burden, and rated frequency
    • عزل resistance measurement
    • Dielectric withstand test (power frequency and impulse)
  • Oil quality tests:
    • Dielectric strength of insulating oil (breakdown voltage test)
    • Moisture content verification
    • Visual inspection for contaminants
  • Mechanical tests:
    • Seal integrity test (pressure/vacuum holding)
    • Tank leak test
    • Mounting structure strength verification
  • Visual and dimensional inspection including nameplate data, terminal marking, and workmanship conformity
  • Type and special tests (where applicable):
    • Temperature rise test under rated burden
    • Short-circuit withstand test (Ith and Idyn verification)
    • Pollution level creepage distance verification per IEC 60815
    • Seismic qualification (where required by project specification)

تركيب & Dimensions

  • Outline dimensions and mounting details are provided in the dimensional drawings below.
  • The transformer shall be securely mounted using the designated fixing holes or mounting brackets suitable for the installation environment (indoor panel mounting or outdoor pole mounting).
  • ابتدائي conductor connection may be made via busbar pass-through, cable termination, or bolted terminals, depending on the current rating and application.
  • Adequate clearance shall be maintained for electrical insulation, heat dissipation, oil expansion, and maintenance access.
  • For outdoor installations, ensure proper weather sealing of all cable entry points and verify that the mounting structure can withstand wind loading and environmental stresses.
  • تركيب orientation shall follow manufacturer’s recommendations to ensure proper oil circulation and cooling performance.

Outlines

LB 10W التيار TransformeOil CT outline instalition

تركيب ملاحظة: Actual dimensions vary based on current rating and configuration. Refer to certified dimensional drawing provided with order acknowledgment for specific installation planning. Ensure compliance with local electrical codes for clearances and grounding.
سلامة Notice: Never leave secondary circuits open when the primary is energized. Always short-circuit and ground the secondary winding before maintenance, following safety regulations.

سلامة ملاحظةs

  • Open-circuit prohibition: ثانوي circuit must never be left open when the transformer primary is energized. Dangerous high voltage may appear across the secondary terminals, creating severe personnel hazard and causing core saturation and overheating.
  • صيانة procedures: During inspection, testing, or instrument replacement, the secondary circuit shall be short-circuited using appropriate shorting links before disconnecting any connected devices.
  • Grounding requirement: One point of the secondary circuit must be reliably grounded in accordance with IEC 61869 requirements and local electrical codes. This ground connection is essential for personnel safety and proper system operation.
  • Qualified personnel: All installation, commissioning, and maintenance work shall be performed only by qualified electrical personnel in accordance with applicable safety regulations and company procedures.
  • De-energization: ابتدائي circuit shall be de-energized, isolated, and verified safe before performing any work on primary connections or mechanical mounting.
  • Oil handling: Insulating oil shall be handled as flammable material. Avoid ignition sources during oil filling, sampling, or maintenance procedures.

معلومات الطلب

When placing an order for LB-10W current transformers, the required configuration shall be specified according to the project technical specification, local utility requirements, and applicable standards. The following parameters shall be clearly stated for technical confirmation and production release:

  • مصنّف primary current / transformation ratio (e.g., 100/5 A, 200/5 A)
  • مصنّف secondary current (standard: 5 A)
  • التطبيق and accuracy requirements:
    • قياس accuracy class (0.2, 0.5, or other)
    • حماية accuracy class (10P10 or other)
    • Specify if single-core or dual-core configuration is required
  • مصنّف burden (VA) for each secondary core/winding
  • Short-circuit withstand requirements:
    • Ith: مصنّف short-time thermal current (1 s duration, in kA)
    • Idyn: مصنّف dynamic current (peak value, in kA)
  • تركيب environment:
    • للداخل or outdoor installation
    • Altitude (if exceeding 2000 m, specify actual altitude for derating calculation)
    • Pollution level (if exceeding الفئة II, specify required creepage distance)
    • Special environmental conditions (coastal, desert, arctic, etc.)
  • Configuration options:
    • Single ratio or dual ratio
    • Single secondary winding or dual secondary windings
    • Terminal arrangement preferences

الأسئلة الشائعة

Select a ratio where the normal operating current falls within 25–100% of the rated primary current and verify it against maximum load and protection coordination requirements.

للداخل epoxy-resin CTs are for controlled environments, while outdoor oil-immersed CTs offer better weather resistance, a wider temperature range, UV protection, and improved cooling for high continuous ratings.

Specify independent accuracy and burden for each core based on the application for metering and protection, such as الفئة 0.2 or 0.5 for metering and الفئة 10P10 for protection.

The total burden is the sum of the instrument VA and wiring loss (I²R), and the CT burden rating should be at least 1.25 times the total burden for a safety margin.

Ith and Idyn should meet or exceed the system fault levels, with Ith being the symmetrical fault current and Idyn being 2.5 times Ith multiplied by √2 for asymmetry.

Never open the secondary circuit when the primary is energized, short-circuit the secondary before disconnecting instruments, and ensure proper grounding and periodic monitoring by qualified personnel.