Product Overview Functional Definition The LJ-2, LJ-4, and LJ-7 series zero-sequence current transformers are indoor-typ...

Product Overview

Functional Definition

The LJ-2, LJ-4, and LJ-7 series zero-sequence current transformers are indoor-type electromagnetic devices designed for residual (zero-sequence) current detection in low-current grounding systems. They are commonly applied for ground fault protection of generators, synchronous condensers, and motors, and are typically used in conjunction with DD-11/60 relays to form a complete ground fault protection scheme.

During normal three-phase operation, the vector sum of phase currents passing through the core window is approximately zero and the secondary output is minimal. When a ground fault occurs within the protection zone, the residual current produces net magnetic flux in the toroidal core, inducing a secondary current signal that drives relay operation for fault indication or tripping.Key Ratings

LJ 2 LJ 4 LJ 7 Indoor Zero Sequence Current Transformers show

Item Specification
Application Residual (zero-sequence) current detection for ground fault protection in low-current grounding systems
Installation environment Indoor installation only
Typical system scope AC 50/60 Hz systems, commonly applied in ≤35 kV class networks (project-dependent)
Protected equipment Generators, synchronous condensers, motors, and cable feeders (residual current protection)
Typical relay pairing DD-11/60 ground fault relay (or equivalent residual-current relay per project design)
Primary insulation Provided by the passing cable insulation; the transformer is typically assessed for secondary winding insulation performance only
Secondary winding insulation 3 kV power frequency withstand voltage to ground (1 min)
Supported cable outside diameter ≤ 50 mm (for larger diameters, select a larger-window model)

Working Principle

Zero-sequence current transformers operate on electromagnetic induction. All phase conductors of the protected circuit (and neutral where required by the protection scheme) pass through the CT window. Under balanced conditions, the resultant magnetic flux is near zero. Under ground fault conditions, residual current produces net flux in the toroidal core and induces a secondary current proportional to the residual component, enabling sensitive ground fault detection by connected relays.

System Application Position

  • Generator Protection: Ground fault protection for generator stator or feeder circuits
  • Motor Protection: Ground fault detection for medium and large motors
  • Synchronous Condenser Protection: Residual current monitoring in reactive power compensation equipment
  • Cable Feeder Protection: Residual current detection on multi-core or parallel cable feeders

Structural Overview

The LJ series adopts a ring-type (toroidal) magnetic core to provide uniform flux distribution and high sensitivity. The secondary winding is evenly distributed to ensure stable output characteristics. A mounting bracket with pre-positioned fixing holes supports fast installation and reliable mechanical fixation in indoor panels, switchgear rooms, or cable trenches.

Ký hiệu model

LJ 247LJ1 Zero sequence current transformer typ

Giải thích mã model

  • L — Máy biến dòng (CT)
  • J — Ứng dụng bảo vệ dòng thứ tự không / chạm đất
  • 2 / 4 / 7 — Số lượng cáp được hỗ trợ (tham chiếu ứng dụng điển hình)

Các biến thể model

Dòng LJ cung cấp ba biến thể tiêu chuẩn dựa trên khả năng chứa cáp và kích thước lỗ thông:

  • LJ-2: Dành cho 1–2 cáp; tỷ số điển hình 20/1
  • LJ-4: Dành cho 3–4 cáp; tỷ số điển hình 20/1
  • LJ-7: Dành cho 5–7 cáp; tỷ số điển hình 40/1

Điều kiện vận hành

Dòng biến dòng thứ tự không LJ được thiết kế để vận hành trong nhà dưới các điều kiện vận hành thông thường.

  • Môi trường lắp đặt: Chỉ lắp đặt trong nhà
  • Tần số định mức: 50 Hz hoặc 60 Hz
  • Độ cao: Không vượt quá 1000 m so với mực nước biển (độ cao lớn hơn cần được xác nhận bởi kỹ thuật)
  • Nhiệt độ môi trường: −5 °C đến +40 °C
  • Độ ẩm tương đối: Môi trường trong nhà có độ ẩm cao được chấp nhận, miễn là không xảy ra hiện tượng ngưng tụ trên các bộ phận mang điện
  • Điều kiện môi trường: Không có khí ăn mòn, môi chất nổ hoặc dễ cháy, rung động mạnh, va đập cơ học hoặc tác động cơ học
Ghi chú kỹ thuật: Đảm bảo lắp đặt chắc chắn và có đủ khoảng trống cho việc đi dây cáp. Tất cả các dây dẫn của mạch được bảo vệ phải đi xuyên qua cửa sổ của biến dòng (CT) để tránh báo sai dòng điện dư.

Kết cấu

Thiết kế kết cấu

  • Kết cấu: Thiết kế lõi hình xuyến dạng vòng
  • Lõi: Vật liệu từ có độ từ thẩm cao để đảm bảo độ nhạy
  • Dây quấn: Dây quấn thứ cấp được bố trí đều quanh lõi
  • Lắp đặt: Giá đỡ kèm các lỗ lắp đặt đã được định vị sẵn
  • Cách điện: Cách điện sơ cấp bằng lớp vỏ bọc cáp; dây quấn thứ cấp chịu được điện áp 3 kV tần số công nghiệp so với đất

Dây quấn & Ký hiệu đầu nối

  • Mạch sơ cấp: Các dây dẫn pha đi xuyên qua lỗ lõi (không có đầu nối sơ cấp)
  • Đầu nối thứ cấp: Được đánh dấu rõ ràng để nối vào đầu vào của rơ le dòng dư

Hãy tuân thủ đúng ký hiệu và yêu cầu về cực tính của các đầu nối thứ cấp để đảm bảo rơ le hoạt động chính xác và chức năng bảo vệ ổn định.

Technical Data

This section provides commonly used technical parameters for LJ-2, LJ-4, and LJ-7 zero-sequence current transformers used with residual-current relays. Final values shall follow the nameplate and factory test report for the specific order.

Electrical Parameters (Relay-Oriented)

Model Cable
Capacity
Secondary
Loop
Resistance (Ω)
Adjustment /
Setting
Current (A)
Sensitivity
(A)
Typical
Rated
Ratio (A)
LJ-2 1–2 10 0.03 1–3 20/1
LJ-4 3–4 10 0.03 1–3 20/1
LJ-7 5–7 10 0.03 1–3 40/1
Application Note: The above parameters are commonly used for residual-current relay applications (e.g., DD-11/60). Confirm the relay input requirements, wiring length, and total secondary burden during engineering design to ensure correct operation.

Dimensional Data

Model A (mm) B (mm) H (mm) ΦD (mm) Φd (mm)
LJ-2 150 200 295 230 110
LJ-4 220 280 335 285 140
LJ-7 220 300 375 300 180
Window Selection Note: Cable outside diameter shall be ≤50 mm. If the cable OD or the number of parallel conductors exceeds the window capacity, select a larger-window residual CT model to avoid installation stress and measurement deviation.

Standards & Normative References

Standard Title Application
IEC 61869-1 Instrument Transformers – Part 1: General Requirements General requirements
IEC 61869-2 Instrument Transformers – Part 2: Additional Requirements for Current Transformers CT requirements (replaces IEC 60044-1)
GB 1208-2006 Current Transformers National CT standard (where specified by project)
GB/T 20840.1 Instrument Transformers – Part 1: General Requirements National standard aligned with IEC 61869-1
GB/T 20840.2 Instrument Transformers – Part 2: Current Transformers National standard aligned with IEC 61869-2

Factory Test Compliance

  • Routine tests per applicable standards including marking verification and basic electrical checks
  • Secondary insulation test (power frequency withstand to ground) as specified
  • Visual and dimensional inspection including workmanship and mounting integrity
  • Type and special tests as required by project specification
Compliance Note: Nameplate data and factory test report govern acceptance for each supplied unit. Certificates are available per shipment with traceability.

Lắp đặt & Kích thước

LJ 247LJ1 Zero sequence current transformer Overall

  • Sử dụng các lỗ bắt vít trên giá đỡ để lắp đặt chắc chắn lên các kết cấu ổn định.
  • Luồn tất cả các dây dẫn pha của mạch được bảo vệ qua cửa sổ của biến dòng (CT); bố trí dây dẫn gọn gàng và tránh tách rời không cần thiết bên trong cửa sổ.
  • Đối với các cáp đấu song song theo từng pha, đảm bảo tất cả các dây dẫn song song đều đi qua cùng một cửa sổ CT để tránh tạo ra dòng điện dư giả.
  • Đi dây thứ cấp đến rơ le với nhãn hiệu rõ ràng và có biện pháp bảo vệ cơ học.
Lưu ý an toàn (CT): Tuyệt đối không để hở mạch cuộn thứ cấp của biến dòng khi mạch sơ cấp đang có điện; điện áp nguy hiểm có thể xuất hiện. Trước khi tháo dây nối đến rơ le, hãy nối tắt các đầu cực thứ cấp của CT và tuân thủ quy trình khóa nguồn/gắn thẻ cảnh báo. Nối đất mạch thứ cấp tại duy nhất một điểm theo đúng quy định an toàn hiện hành.

Thông tin đặt hàng

Khi đặt hàng, vui lòng xác định các thông số sau theo yêu cầu hệ thống và đặc tả dự án:

  • Lựa chọn model: LJ-2, LJ-4 hoặc LJ-7 tùy theo số lượng cáp và kích thước cửa sổ
  • Số lượng cáp / cách bố trí dây dẫn: bao gồm cấu hình cáp song song cho từng pha
  • Đường kính ngoài lớn nhất của cáp: xác nhận ≤50 mm hoặc nêu rõ yêu cầu cửa sổ lớn hơn
  • Loại rơ le: ví dụ DD-11/60 hoặc yêu cầu đầu vào tương đương cho rơ le dòng rò
  • Môi trường lắp đặt: nhiệt độ trong nhà, độ ẩm, độ cao và các ràng buộc về lắp đặt
  • Yêu cầu đặc biệt: ngôn ngữ tài liệu, chứng chỉ, ghi nhãn hoặc các thử nghiệm đặc thù theo dự án

Hướng dẫn lựa chọn: (1) Xác nhận số lượng cáp cần luồn qua cửa sổ CT và đường kính ngoài (OD) lớn nhất của chúng; (2) Chọn LJ-2 (1–2 cáp), LJ-4 (3–4 cáp) hoặc LJ-7 (5–7 cáp); (3) Xác nhận yêu cầu đầu vào của rơ le và điều kiện mạch thứ cấp; (4) Kiểm tra yêu cầu cách điện thứ cấp (thông thường là 3 kV/1 phút so với đất); (5) Xác nhận các ràng buộc lắp đặt và yêu cầu tài liệu trước khi phê duyệt sản xuất.

FAQs

They are used for residual (zero-sequence) current detection and ground fault protection in low-current grounding systems, commonly for generators, motors, synchronous condensers, and cable feeders.
All phase conductors pass through the CT window; a ground fault produces residual current, generating net flux in the core and inducing a secondary signal to drive relay operation.
Typical application recommends cable OD ≤50 mm. For larger OD or more conductors, select a larger-window residual CT model.
Primary insulation is provided by the cable. The secondary winding insulation is typically verified by a 3 kV (1 min) power frequency withstand test to ground.
Selection is based on the number of cables and window size requirement: LJ-2 for 1–2 cables, LJ-4 for 3–4 cables, and LJ-7 for 5–7 cables (larger window and typical 40/1 ratio).
Never open-circuit the CT secondary when the primary is energized. Short the secondary before wiring changes and ground the secondary at one point only per safety regulations.