JLSZW3-10KV للخارج راتنج الإيبوكسي محول مجمع (three-phase )

JLSZW3-10KV للخارج راتنج الإيبوكسي محول مجمع (three-phase )

نظرة عامة على المنتج Functional Definition The JLSZW3-6 and JLSZW3-10 series outdoor dry-type combined instrument transf...

نظرة عامة على المنتج

Functional Definition

The JLSZW3-6 and JLSZW3-10 series outdoor dry-type combined instrument transformers are integrated electromagnetic measurement devices that combine voltage transformer (VT) and current transformer (CT) functions in a single sealed enclosure. These transformers provide simultaneous voltage and current measurement for three-phase AC power systems rated at 50 Hz, with system voltage classes of 6 kV and 10 kV. The combined configuration delivers galvanically isolated secondary signals for energy metering, protection relaying, and supervisory control applications in urban/rural grids, outdoor substations, and industrial distribution networks.

التصنيفات الرئيسية

البند المواصفات (per order / nameplate)
System voltage class 6 kV / 10 kV class (outdoor distribution applications)
مصنّف frequency 50 Hz (60 Hz available upon request)
VT voltage ratios 3000/100 V, 6000/100 V, 10000/100 V
VT accuracy classes 0.2 / 0.5
VT rated output 15 VA / 30 VA per core
VT limit output 300 VA
CT current ratios 5~200/5 A
CT accuracy classes 0.2S / 0.2
CT rated output 10 VA per core
CT short-circuit withstand Ith: 100 × I₁n (1 s), Idyn: 2.5 × Ith (peak)
VT insulation level (JLSZW3-6) 7.2/32/60 kV
VT insulation level (JLSZW3-10) 12/42/75 kV
CT insulation level 12/42/75 kV
Connection configuration Three-phase four-wire Y/Yo
Applicable standards GB 20840.4-2015 (Combined); GB 20840.2-2014, GB 20840.1-2010 (CT); GB 20840.3-2013, GB 20840.1-2010 (VT)

Product Shows

JLSZW3 10 ثلاثي الطور Epoxy Resin CT PTs

مبدأ العمل

The combined transformer integrates independent voltage and current measurement functions using electromagnetic induction principles. The voltage transformer section employs a wound-core configuration with primary windings connected to the power system and secondary windings delivering standardized 100 V output. The current transformer section utilizes toroidal cores with primary conductors passing through apertures and secondary windings providing 5 A output current proportional to primary current. Both VT and CT sections operate simultaneously to supply complete three-phase voltage and current signals for metering instruments, protective relays, and monitoring systems.

System التطبيق Position

  • للخارج Distribution Networks: 6-10 kV overhead lines and pole-mounted switchgear
  • طاقة قياس Stations: Revenue-grade three-phase electricity measurement and billing
  • حماية Systems: Overcurrent, overvoltage, and directional protection schemes
  • Substation Monitoring: Remote terminal units (RTU) and SCADA data acquisition
  • Industrial طاقة Systems: Factory distribution panels and outdoor transformer stations

Structural Overview

The combined transformer features fully-enclosed metal housing with integrated epoxy resin cast VT and CT components. The voltage transformer sections use exposed iron cores with high-quality cold-rolled grain-oriented silicon steel, with primary and secondary windings wound on core limbs. التيار transformer sections employ closed iron cores with premium silicon steel, ensuring measurement accuracy and stability. Three voltage transformers and three current transformers are assembled in a sealed metal enclosure, providing compact installation footprint, environmental protection, and reliable long-term operation in outdoor conditions.

تعيين الموديل

JLSZW3 10 للخارج Dry Type Combined محول Epoxy Resin عزل model

Code Explanation

  • J — جهد transformer (VT/PT)
  • L — التيار transformer (CT)
  • S — Three-phase configuration
  • Z — Cast-resin (epoxy) insulated structure
  • W — للخارج installation type
  • 3 — Design series code
  • 6 / 10 — جهد class (kV)

الوصف

JLSZW3-6 and JLSZW3-10 designate the system voltage class (6 kV or 10 kV). The combined transformer integrates three single-phase voltage transformers and three single-phase current transformers in Y/Yo three-phase four-wire connection. The specific voltage ratio, current ratio, accuracy classes, and rated burdens are defined by project specification and confirmed on the nameplate.

ظروف الخدمة

The JLSZW3 series combined transformers are designed for outdoor operation under normal service conditions in medium-voltage distribution systems.

  • تركيب environment: للخارج installation in sheltered or exposed locations
  • Altitude: Not exceeding 1000 m above sea level (higher altitude applications require engineering confirmation)
  • Ambient temperature: −25 °C to +40 °C
  • Relative humidity: Daily average ≤ 95%, monthly average ≤ 90% (at +20 °C reference)
  • Environmental conditions: Free from severe salt fog, industrial contamination, or explosive atmospheres; no abnormal vibration or mechanical shock
  • Lightning protection: Zinc oxide surge arrester required within 1 meter of installation point
Engineering ملاحظة: تركيب shall comply with outdoor electrical safety regulations. Surge protection is mandatory per GB standards. Equipment location shall provide adequate clearance for operation and maintenance access.

البناء

البناء Design

محول الجهد Section:

  • Core type: Wound core with exposed structure
  • Core material: High-quality cold-rolled grain-oriented silicon steel sheets
  • عزل: Epoxy resin cast construction
  • اللفات: ابتدائي and secondary coils wound on core limbs

محول التيار Section:

  • Core type: Closed ring-type iron core
  • Core material: Premium quality silicon steel laminations
  • عزل: Epoxy resin monolithic casting
  • Configuration: Pass-through primary with secondary windings on toroidal core

Enclosure Assembly:

  • Housing: Sealed metal cabinet with environmental protection
  • المكونs: Three VT units + three CT units in integrated assembly
  • Terminals: ابتدائي and secondary terminal blocks accessible via compartment doors
  • حماية rating: Weather-resistant construction for outdoor service

The epoxy resin casting provides stable insulation properties, moisture resistance, pollution resistance, and aging resistance for reliable outdoor operation. The fully-enclosed metal housing protects components from environmental exposure while maintaining electrical clearances and creepage distances.

Terminal Arrangement & Marking

JLSZW3 10 ثلاثي الطور Epoxy Resin CT PTs output

محول الجهد Terminals:

  • ابتدائي terminals (per phase): A / B / C / N (neutral)
  • ثانوي terminals (per phase): a / b / c / n (neutral)
  • Connection: Y/Yo three-phase four-wire configuration

محول التيار Terminals:

  • ابتدائي terminals (per phase): P1 / P2
  • ثانوي terminals (Phase A): 1K1 / 1L1
  • ثانوي terminals (Phase B): 1K2 / 1L2
  • ثانوي terminals (Phase C): 1K3 / 1L3

Terminal markings follow standard polarity conventions per GB 20840 series. Correct terminal identification is essential for accurate metering and proper protection relay operation. Wiring diagrams and terminal assignment are provided with each unit.

البيانات الفنية

محول الجهد المواصفات

Model مصنّف
جهد
Ratio (V)
الدقة
الفئة
مصنّف
المخرج
(VA)
Limit
المخرج
(VA)
مصنّف
عزل
Level (kV)
JLSZW3-6 3000/100 0.2 / 0.5 15 / 30 300 3.6/25/40
6000/100 7.2/32/60
JLSZW3-10 3000/100 0.2 / 0.5 15 / 30 300 3.6/25/40
6000/100 7.2/32/60
10000/100 12/42/75

محول الجهد ملاحظةs:

  • فئة الدقة 0.2 for precision metering; 0.5 for general metering applications
  • مصنّف output (burden) available as 15 VA or 30 VA per secondary winding
  • Limit output capacity: 300 VA continuous
  • عزل level format: Um/ACSD/LI (system voltage / short-duration power-frequency / lightning impulse)
  • ثانوي voltage: 100 V line-to-neutral (57.7 V phase-to-neutral in Y connection)

محول التيار المواصفات

Model مصنّف
التيار
Ratio (A)
الدقة
الفئة
مصنّف
المخرج
(VA)
مصنّف
Short-Time
Thermal التيار
(kA)
مصنّف Dynamic
Stability التيار
(kA peak)
مصنّف
عزل
Level (kV)
JLSZW3-6 5~200/5 0.2S 10 100 × I₁n 2.5 × Ith 12/42/75
0.2
JLSZW3-10 5~200/5 0.2S 10 100 × I₁n 2.5 × Ith 12/42/75
0.2

محول التيار ملاحظةs:

  • فئة الدقة 0.2S for electronic energy meters (extended range); 0.2 for standard metering
  • مصنّف primary current (I₁n) selectable from 5 A to 200 A in standard steps
  • مصنّف secondary current: 5 A (1 A available as special order)
  • Short-time thermal current (Ith): 100 times rated primary current for 1 second
  • Dynamic stability current (Idyn): 2.5 times Ith (peak value)
  • حمل power factor: cosφ = 0.8 (inductive) unless otherwise specified

الدقة and حمل

محول الجهد الدقة Performance:

جهد transformers meet accuracy class 0.2 or 0.5 requirements per GB 20840.3-2013 at rated burden from 25% to 100% of rated voltage. Ratio error and phase displacement remain within specified limits across the operating range.

محول التيار الدقة Performance:

التيار transformers meet accuracy class 0.2S or 0.2 requirements per GB 20840.2-2014. الفئة 0.2S provides extended accuracy range from 1% to 120% of rated primary current, suitable for electronic energy meters. الدقة limits are maintained at rated burden and rated frequency.

حمل Selection:

VT rated burden (15 VA or 30 VA) shall accommodate total connected load including meters, relays, and wiring resistance. CT rated burden (10 VA) shall cover secondary circuit impedance at rated current (5 A). Actual burden should be verified during system design to ensure accuracy compliance.

المعايير Compliance

Applicable المعايير

  • GB 20840.4-2015: Instrument transformers – Part 4: Additional requirements for combined transformers
  • GB 20840.2-2014: Instrument transformers – Part 2: Additional requirements for current transformers
  • GB 20840.1-2010: Instrument transformers – Part 1: General requirements
  • GB 20840.3-2013: Instrument transformers – Part 3: Additional requirements for inductive voltage transformers
  • IEC 61869 series: Instrument transformers (reference standard)

Testing and Acceptance

Each combined transformer unit undergoes factory testing per applicable standards:

  • Routine tests: جهد ratio, current ratio, polarity, accuracy, burden, insulation resistance, dielectric withstand
  • عزل test: طاقة-frequency voltage withstand test on primary and secondary circuits
  • Lightning impulse test: Full-wave impulse voltage test per insulation level specification
  • Short-circuit withstand test: Verification of Ith and Idyn ratings (type test or calculation)
  • Visual and dimensional inspection: Nameplate data, terminal marking, workmanship verification
  • Special tests: Partial discharge measurement, temperature rise test (where specified)
Compliance ملاحظة: Test certificates accompany each manufactured unit with traceability to accredited laboratories. Type test reports available upon request for project approval and qualification.

تركيب & Dimensions

تركيب Guidelines

  • Combined transformer shall be mounted on stable foundation or pole-mounted bracket with secure mechanical fixing
  • Mounting position shall provide adequate clearance for electrical safety, heat dissipation, and maintenance access
  • ابتدائي connections made via busbar or cable termination as specified by project design
  • ثانوي circuits routed through cable glands with proper sealing and strain relief
  • Surge arrester installation mandatory within 1 meter of primary terminals per GB requirements
  • Grounding connection required on designated terminal following local electrical codes

Outlines

JLSZW3-6kV / 10kV محول مجمع

JLSZW3 10 للخارج Dry Type Combined محول Epoxy Resin عزل outline

ملاحظة: Dimensional drawings show typical configuration. Actual dimensions confirmed on approved drawings prior to manufacture. Mounting hole patterns and terminal locations may vary by specification.

سلامة Notice: VT and CT secondary circuits must never be left open when primary is energized. Before maintenance, de-energize primary circuit and short-circuit secondary terminals in accordance with local electrical safety procedures. One point of each secondary circuit shall be reliably grounded.

سلامة ملاحظةs

  • VT secondary circuit should not be short-circuited during operation; miniature circuit breaker or fuse protection recommended
  • CT secondary circuit must never be open when primary carries current; dangerous high voltage will appear at secondary terminals
  • During inspection or maintenance, CT secondary shall be short-circuited before disconnecting any instruments or wiring
  • One point of VT secondary neutral and one point of CT secondary circuit shall be reliably grounded per applicable standards
  • All installation and maintenance operations shall comply with national and local electrical safety regulations
  • De-energize primary circuit and verify absence of voltage before accessing terminal compartments

معلومات الطلب

When placing an order, the required configuration shall be specified according to local utility requirements, applicable standards, and project technical specification. The following parameters shall be clearly stated for technical confirmation and production release:

محول الجهد Requirements:

  • مصنّف primary voltage / voltage ratio: 3000/100 V, 6000/100 V, or 10000/100 V
  • فئة الدقة: 0.2 or 0.5
  • مصنّف burden: 15 VA or 30 VA per secondary winding
  • عزل level: Per system voltage class and project specification

محول التيار Requirements:

  • مصنّف primary current / transformation ratio: 5/5 A through 200/5 A in standard steps
  • فئة الدقة: 0.2S or 0.2
  • مصنّف burden: 10 VA per secondary winding
  • Short-circuit withstand: Ith (1 s) and Idyn (peak) per system fault level

System and Configuration:

  • System voltage class: 6 kV or 10 kV
  • مصنّف frequency: 50 Hz (specify if 60 Hz required)
  • Connection type: Three-phase four-wire Y/Yo (standard)
  • تركيب type: للخارج pole-mounted or foundation-mounted

If special requirements apply (non-standard ratios, additional accuracy cores, special terminal arrangements, mounting configurations, documentation language, certificates, or factory testing beyond routine), specify them at ordering stage for technical review and confirmation. Custom configurations require engineering approval and final datasheet before production release.

الأسئلة الشائعة

Select VT ratio matching system nominal voltage (10000/100 V for 10 kV system). Select CT primary current from feeder continuous load and measurement range requirements, then verify against system design and protection coordination.

Revenue-grade metering requires VT class 0.2 and CT class 0.2S per GB standards. General monitoring and protection applications may use VT class 0.5 and CT class 0.2. Confirm requirements with local utility regulations.

VT burden shall cover total VA consumption of all connected meters, relays, and wiring losses. CT burden (10 VA at 5 A) shall accommodate secondary circuit impedance including meter coils and cable resistance. Calculate total burden during engineering design and select VT rated burden (15 VA or 30 VA) accordingly.

GB standards require surge arrester within 1 meter of combined transformer primary terminals to protect against lightning overvoltages and switching surges in outdoor installations. Arrester prevents insulation failure and equipment damage from transient overvoltages.

Calculate system prospective short-circuit current at installation point. Verify nameplate Ith (thermal) rating ≥ fault current RMS value for 1 second duration. Verify Idyn (dynamic) rating ≥ 2.5 × Ith ≥ peak fault current. Ratings confirmed by factory test report or type test certificate.

VT secondary neutral (n) terminal shall be grounded at one point. CT secondary circuits shall be grounded at one point per phase. Never open CT secondary under energized primary. Short and ground CT secondary before disconnecting instruments. Observe polarity markings (a/b/c/n for VT, K/L for CT) for correct metering and protection operation.

Nameplate data and factory routine test report govern acceptance. Test certificates verify ratio, accuracy, burden, insulation withstand, and short-circuit capability per GB 20840 series standards. Type test reports available for lightning impulse and special tests where specified by project.