CT/PT Selection for Electric Arc Furnace (EAF) & Traction Systems: Harmonics, Fluctuation & Protection Guide (IEC 61869-2/3, IEEE C57.13)
Thomas Insights

CT/PT Selection for Electric Arc Furnace (EAF) & Traction Systems: Harmonics, Fluctuation & Protection Guide (IEC 61869-2/3, IEEE C57.13)

June 3, 2026 Documents

CT/PT Selection for Electric Arc Furnace (EAF) & Traction Systems: Harmonics, Fluctuation & Protection Guide (IE...

Article Content

CT/PT Selection for Electric Arc Furnace (EAF) & Traction Systems: Harmonics, Fluctuation & Protection Guide (IEC 61869-2/3, IEEE C57.13)

Meta Description: Comprehensive guide on current transformer (CT) and potential transformer (PT) selection for Electric Arc Furnace (EAF) and railway traction systems. Covers harmonic distortion, voltage fluctuation, fast transient response, and compliance with IEC 61869-2/3 and IEEE C57.13, including practical engineering examples for industrial and traction power systems.


1. Introduction

Electric Arc Furnace (EAF) steelmaking and railway traction systems present extreme challenges for instrument transformers (CTs and PTs) due to:
Rapid load fluctuation: EAF electrode movement, traction train acceleration/deceleration cause rapid current/voltage changes
Harmonic distortion: EAF and traction converters generate high-order harmonics (3rd, 5th, 7th, 11th, 13th)
Voltage fluctuation & flicker: Rapid load changes cause voltage dips/swells, flicker
Unbalanced load: EAF phases are unbalanced, traction systems cause negative-sequence current
Transient performance: EAF short circuits, traction faults require fast protection response

Consequences of Inadequate CT/PT Selection:
Metering errors: Inaccurate energy measurement, billing disputes, power quality penalties
Protection misoperation: False tripping, failure to trip, equipment damage
Harmonic saturation: CT/PT core saturation, relay misoperation
System instability: Voltage collapse, flicker, grid non-compliance

This guide systematically covers CT/PT selection for EAF and traction systems, harmonics, fluctuation, transient performance, and practical engineering per IEC 61869-2:2016, IEC 61869-3:2016, and IEEE C57.13 standards.


2. EAF System Characteristics

2.1 EAF Configuration

    Grid ── HV Busbar ── EAF Transformer ── Electrodes (Arc)
    Voltage: 33-132 kV (HV) → 200-1000V (LV, electrode)
    Current: 20,000-100,000 A (electode current)

CT/PT Applications:
HV busbar: Metering, protection (overcurrent, earth fault, over/under voltage)
EAF transformer primary: Metering, protection (differential, overcurrent, earth fault)
EAF transformer secondary: Metering, protection (overcurrent, short circuit)
Reactive power compensation (SVC/STATCOM): Metering, protection (overcurrent, harmonic filter)

2.2 EAF Load Profile

    Time
      │
      │    Melting Period (High fluctuation, high harmonics)
      │   /\/\/\/\/\/\/\/\/\/\
      │  /
      │ / Refining Period (Moderate fluctuation)
      │/
      │______________________ Tap Period (Low load)

Harmonic Content (EAF):
| Harmonic Order | Magnitude (% of Fundamental) |
|—————|—————————-|
| 3rd | 10-20% |
| 5th | 8-15% |
| 7th | 5-10% |
| 11th | 3-6% |
| 13th | 2-5% |


3. Traction System Characteristics

3.1 Traction Configuration

    Grid ── Traction Substation ── Overhead Catenary System (OCS) ── Train
    Voltage: 25 kV AC (50 Hz) or 1.5/3 kV DC
    Current: 500-2000 A per train

CT/PT Applications:
Traction substation primary: Metering, protection (overcurrent, earth fault)
Traction transformer: Metering, protection (differential, overcurrent)
OCS feeder: Metering, protection (overcurrent, earth fault, impedance relay)
Reactive power compensation (SVC, filter bank): Metering, protection

3.2 Traction Load Profile

    Time
      │
      │    Acceleration (High current, rapid change)
      │   /
      │  /
      │ / Cruising (Moderate current)
      │/
      │______________________ Braking (Regenerative, negative current)

Harmonic Content (Traction):
| Harmonic Order | Magnitude (% of Fundamental) |
|—————|—————————-|
| 3rd | 5-10% |
| 5th | 8-12% |
| 7th | 5-8% |
| 11th | 3-5% |
| 13th | 2-4% |


4. CT Selection for EAF & Traction

4.1 Harmonic Performance

Harmonic Impact on CT:

    EAF and traction systems generate high harmonics (up to 50th).
    Standard CTs (5P, 10P) saturate at high frequencies, causing measurement errors.
    Selection: Rogowski coil, Optical CT (OCT), Hall effect CT (wide frequency range, no saturation).

4.2 Fluctuation & Fast Response

Load Fluctuation Impact on CT:

    Rapid load changes (EAF electrode movement, train acceleration) cause rapid current changes.
    CT must respond fast (< 1 ms) without saturation.
    Selection: Rogowski coil, OCT (linear response, fast response).

4.3 CT Ratio Selection

Formula:

CT Primary = 1.5 × Full Load Current (recommended, accounts for fluctuation)
CT Secondary = 1A (recommended, reduces burden, improves accuracy)

Example (EAF):

Given:
  Full Load Current = 5000 A (HV side)
  CT Primary = 1.5 × 5000 = 7500 A
  Select: 7500/1A (standard ratio)

Example (Traction):

Given:
  Full Load Current = 1000 A (feeder)
  CT Primary = 1.5 × 1000 = 1500 A
  Select: 1500/1A (standard ratio)

5. PT Selection for EAF & Traction

5.1 Voltage Fluctuation & Flicker

Fluctuation Impact on PT:

    EAF and traction systems cause voltage fluctuation (±10%) and flicker.
    PT must maintain accuracy during fluctuation, no ferroresonance.
    Selection: Cast-resin PT (3P), CVT (stable, no ferroresonance), OVT (digital, wide range).

5.2 Harmonic Performance

Harmonic Impact on PT:

    EAF and traction systems generate high harmonics (up to 50th).
    Standard PTs (0.3, 0.6) saturate at high frequencies.
    Selection: OVT (excellent harmonic performance), CVT (good harmonic performance).

5.3 PT Ratio Selection

Formula:

PT Primary = System Maximum Voltage (Um) / √3 (for grounded neutral)
PT Secondary = 100/√3 V (IEC), 115 V (ANSI)

Example (EAF):

Given:
  System Voltage: 110 kV (Um = 123 kV)
  Neutral: Grounded (solidly)

PT Primary = 123,000 / √3 = 71,000 V
Select: 71000/√3 / 100/√3 V (standard ratio)

Example (Traction):

Given:
  System Voltage: 25 kV (Um = 36 kV)
  Neutral: Grounded (via impedance)

PT Primary = 36,000 / √3 = 20,780 V
Select: 20780/√3 / 100/√3 V (standard ratio)

6. Protection Requirements

6.1 EAF Protection

Protection CT/PT Requirement Response Time
Differential TPY class, matching ratio < 20 ms
Overcurrent 5P class, high saturation resistance < 40 ms
Earth Fault 5P class, sensitive (ZSCT) < 40 ms
Short Circuit Rogowski coil, OCT (fast response) < 10 ms

6.2 Traction Protection

Protection CT/PT Requirement Response Time
Impedance Relay 5P class, accurate up to 50th harmonic < 40 ms
Overcurrent 5P class, high saturation resistance < 40 ms
Earth Fault 5P class, sensitive (ZSCT) < 40 ms
Auto-Reclosing PT for voltage check (synchronism) < 100 ms

7. Testing & Commissioning

7.1 Post-Installation Tests

Test Method Acceptance Criteria
Ratio Test CT/PT tester < Class limit (e.g., ±0.2% for 0.2S class)
Polarity Test CT/PT tester or DC method Correct
Burden Test Measure secondary circuit ≤ Rated burden
Harmonic Test Power quality analyzer Accuracy up to 50th harmonic
Fluctuation Test Simulate rapid load change < Class limit during fluctuation
Protection Test Relay test kit Response time < requirement

7.2 Commissioning Checklist

☐ CT/PT type and ratio verified (nameplate matches design)
☐ CT/PT accuracy class verified (0.2S, 0.5S, 5P, 10P, 3P)
☐ CT/PT burden verified (≤ rated burden)
☐ CT/PT polarity verified (correct)
☐ CT/PT secondary wiring verified (correct terminal, grounding)
☐ Primary connection verified (alignment, torque, clearance)
☐ Grounding verified (continuous, < 1 Ω)
☐ Post-installation tests performed (ratio, polarity, burden, harmonic, fluctuation, protection)
☐ Relay settings entered (ratios, compensation, trip time)
☐ Documentation updated (CT/PT records, test reports)

8. Standards & References

8.1 IEC Standards

Standard Title Relevant Sections
IEC 61869-2 Current Transformers §5 (Accuracy Classes), §6 (Tests)
IEC 61869-3 Voltage Transformers §5 (Accuracy Classes), §6 (Tests)
IEC 61000-4-30 Power Quality Measurement Full document
IEC 61000-3-7 Flicker Assessment Full document

8.2 IEEE Standards

Standard Title Relevant Sections
IEEE C57.13 Instrument Transformers §4 (Accuracy Classes)
IEEE 1459 Power Definitions Full document

9. Engineering FAQ

Q1: Why do EAF and traction CTs need harmonic performance?

A: EAF and traction systems generate high harmonics (3rd, 5th, 7th, 11th, 13th, up to 50th). Standard CTs (5P, 10P) are designed for 50/60 Hz and saturate at higher frequencies, causing measurement errors and protection misoperation. EAF/traction CTs must maintain accuracy up to 2500 Hz (50th harmonic at 50 Hz).

Q2: What CT type is best for EAF/traction harmonic metering?

A:
Rogowski coil: Linear response, wide frequency range (0.1 Hz – 1 MHz), excellent harmonic performance
Optical CT (OCT): Linear response, wide frequency range (DC – 1 MHz), excellent harmonic performance, digital output (IEC 61850)
Hall effect CT: DC and AC measurement, good harmonic performance, requires external power

Q3: How do I verify CT/PT fluctuation performance?

A:
– Simulate rapid load change (step current/voltage)
– Verify CT/PT accuracy during fluctuation < class limit
– Compare with reference meter, verify error < class limit

Q4: What is the grid code requirement for EAF/traction metering?

A:
Metering accuracy: 0.2S, 0.5S class
Harmonic measurement: Up to 50th harmonic (2500 Hz)
Flicker assessment: IEC 61000-3-7 compliance
Protection response time: < 40 ms (overcurrent, earth fault), < 10 ms (short circuit)

Q5: How do I select CT/PT for EAF/traction systems?

A:
– Verify system voltage (Um, frequency)
– Select CT/PT type (Rogowski/OCT for harmonic metering, cast-resin for protection)
– Select CT/PT ratio (1.5 × full load current for CT, Um/√3 for PT)
– Select accuracy class (0.2S, 0.5S for metering, 5P, 3P for protection)
– Calculate burden, select rated burden (≥ total burden)
– Verify grid code compliance (accuracy, harmonics, flicker, response time)
– Specify testing requirements (ratio, polarity, burden, harmonic, fluctuation, protection)


10. Conclusion

CT/PT selection for EAF and traction systems requires careful consideration of harmonics, fluctuation, fast response, transient performance, and testing requirements. Proper CT/PT selection ensures accurate metering, reliable protection, and grid compliance for industrial and traction power systems.

Key selection principles:
Harmonics: Rogowski coil, OCT, Hall effect CT for harmonic metering
Fluctuation: Fast response (< 1 ms), linear response, no saturation
Grid code: 0.2S, 0.5S class, up to 50th harmonic, flicker compliance, < 40 ms response time
Testing: Ratio, polarity, burden, harmonic, fluctuation, protection
Documentation: Specification, datasheet, test reports, grid compliance certificate

Design checklist:

☐ System voltage determined (Um, frequency)
☐ CT/PT type selected (Rogowski, OCT, Hall effect, cast-resin)
☐ CT/PT ratio selected (1.5 × full load current for CT, Um/√3 for PT)
☐ Accuracy class selected (0.2S, 0.5S for metering, 5P, 3P for protection)
☐ Burden calculated (devices + leads)
☐ CT/PT rated burden selected (≥ total burden)
☐ Grid code compliance verified (accuracy, harmonics, flicker, response time)
☐ Testing requirements defined (ratio, polarity, burden, harmonic, fluctuation, protection)
☐ Documentation prepared (specification, datasheet, test reports, grid compliance)

Technical Reference: IEC 61869-2:2016, IEC 61869-3:2016, IEEE C57.13, IEC 61000-4-30, IEC 61000-3-7, IEEE 1459
Product Reference: Duomatech LZZBJ9 series (cast-resin CTs), JDZ/JDZX series (cast-resin PTs) — optimized for EAF and traction system applications