CT Ratio & Polarity Testing Guide: Methods, Equipment & Acceptance Criteria (IEC 61869-2, IEEE C57.13)
Thomas Insights

CT Ratio & Polarity Testing Guide: Methods, Equipment & Acceptance Criteria (IEC 61869-2, IEEE C57.13)

May 22, 2026 Documents

CT Ratio & Polarity Testing Guide: Methods, Equipment & Acceptance Criteria (IEC 61869-2, IEEE C57.13) Meta Desc...

Article Content

CT Ratio & Polarity Testing Guide: Methods, Equipment & Acceptance Criteria (IEC 61869-2, IEEE C57.13)

Meta Description: Comprehensive guide on current transformer (CT) ratio and polarity testing. Covers test methods, equipment, acceptance criteria, and compliance with IEC 61869-2 and IEEE C57.13. Includes step-by-step procedures, troubleshooting, and safety precautions for factory, site, and maintenance testing of MV/HV CTs.


1. Introduction

Current transformer (CT) ratio and polarity testing are fundamental diagnostic tests performed during factory acceptance, site commissioning, and periodic maintenance. These tests verify:
Ratio accuracy: Ensures CT secondary current accurately reflects primary current for metering and protection
Polarity correctness: Ensures CT secondary current direction matches relay/meter requirements for differential, directional, and distance protection

Incorrect ratio or polarity can cause:
Metering errors: Inaccurate energy measurement, revenue loss
Protection misoperation: False differential tripping, incorrect directional operation
System instability: Relay miscoordination, extended fault duration
Equipment damage: Unchecked faults, generator/transformer damage

This guide systematically covers CT ratio and polarity testing methods, equipment, acceptance criteria, procedures, and troubleshooting per IEC 61869-2:2016 and IEEE C57.13 standards.


2. CT Ratio Testing

2.1 Test Principle

Ratio Test: Apply known primary current, measure secondary current, verify ratio matches nameplate.

    Primary Current (I_p) ── CT Primary
                                │
                            CT Core
                                │
    Secondary Current (I_s) ── CT Secondary ── Ammeter/Tester
                                │
    Ratio = I_p / I_s

Expected Ratio:

Nameplate Ratio: e.g., 1000/5A = 200:1
Measured Ratio: I_p / I_s should be ≈ 200:1
Error = (Measured Ratio - Nameplate Ratio) / Nameplate Ratio × 100%

2.2 Test Equipment

Equipment Description Accuracy Application
CT Tester Integrated ratio/polarity/excitation tester ±0.1% Factory, site, maintenance
Primary Injection Kit Step-down transformer, ammeter ±0.5% Site, maintenance
Clamp Ammeter Primary current measurement ±1% Quick verification
Digital Multimeter Secondary current measurement ±0.5% Backup measurement

2.3 Test Procedure

Step 1: Safety Preparation

☐ De-energize CT primary circuit
☐ Isolate CT from relay/meter secondary circuit
☐ Short CT secondary terminals (except test terminal)
☐ Verify grounding
☐ Wear PPE (insulating gloves, safety glasses)

Step 2: Connect Test Equipment

    CT Primary: Connect primary injection leads (P1, P2)
    CT Secondary: Connect secondary leads (S1, S2) to tester
    Ground: Connect tester ground to substation ground grid

Step 3: Perform Test

1. Select CT ratio on tester (e.g., 1000/5A)
2. Inject primary current (typically 10-50% of rated primary)
3. Measure secondary current
4. Record ratio and error
5. Repeat at multiple current levels (25%, 50%, 100% rated primary)

Step 4: Calculate Error

Error (%) = (I_s_measured - I_s_expected) / I_s_expected × 100%
Where:
  I_s_expected = I_p_injected / Nameplate Ratio

2.4 Acceptance Criteria

Application Ratio Error Limit Standard Reference
Metering (0.2S, 0.5S) < ±0.2% (0.2S), < ±0.5% (0.5S) IEC 61869-2
Protection (5P, 10P) < ±1.0% IEC 61869-2
Site Acceptance < ±1.0% (all classes) IEEE C57.13
Maintenance < ±1.0% of baseline IEEE C57.13

2.5 Common Errors & Troubleshooting

Error Cause Solution
Ratio > 1% error Shorted turns, connection issue, wrong tap Verify connections, check tap, replace CT
Unstable reading Loose connection, interference Tighten connections, shield cables
Zero secondary current Open circuit, wrong terminal Verify secondary circuit, check S1/S2
Low secondary current Wrong ratio selected, burden too high Verify ratio setting, reduce burden

3. CT Polarity Testing

3.1 Test Principle

Polarity Test: Verify CT secondary current direction matches primary current direction (additive or subtractive polarity).

Standard Polarity:

    Primary Current: P1 → P2
    Secondary Current: S1 → S2 (subtractive polarity, standard)

    When primary current enters P1, secondary current leaves S1.

Polarity Markings:

    CT Nameplate:
        P1 ─── Primary (Line)
        P2 ─── Primary (Load)
        S1 ─── Secondary (Output)
        S2 ─── Secondary (Return)

3.2 Test Methods

Method 1: Battery & Analog Meter (DC Method)

Equipment:
– 1.5V or 9V battery
– Analog voltmeter/milliammeter (center-zero)

Procedure:

1. Connect battery to primary (P1 +, P2 -)
2. Connect analog meter to secondary (S1 +, S2 -)
3. Momentarily connect battery
4. Observe meter deflection:
   - Positive deflection → Additive polarity (S1 matches P1)
   - Negative deflection → Subtractive polarity (standard)

Method 2: CT Tester (Automatic Polarity Test)

Equipment:
– CT tester with polarity function

Procedure:

1. Connect CT tester to primary (P1, P2) and secondary (S1, S2)
2. Select polarity test mode
3. Perform test
4. Read result: "Correct" or "Reverse"

Method 3: Secondary Injection (Relay Verification)

Equipment:
– Relay tester

Procedure:

1. Inject current into relay current input
2. Verify relay measures correct direction
3. Compare with CT polarity marking

3.3 Acceptance Criteria

Parameter Limit Standard Reference
Polarity Correct (S1 matches P1, subtractive) IEC 61869-2
Differential Protection All CTs same polarity, matching IEEE C37.112
Directional Protection Correct polarity for direction IEEE C37.90

3.4 Common Errors & Troubleshooting

Error Cause Solution
Reverse polarity Wrong connection, CT installed backward Reverse secondary leads (S1/S2), reinstall CT
Unstable reading Loose connection, battery weak Tighten connections, replace battery
No deflection Open circuit, wrong terminal Verify secondary circuit, check S1/S2
Differential relay trips Mismatched polarity (neutral vs terminal) Verify all CT polarity, correct connections

4. Combined Ratio & Polarity Testing

4.1 Integrated CT Tester Procedure

Modern CT testers perform ratio, polarity, excitation, and burden tests in one setup:

1. Connect tester to CT secondary (S1, S2)
2. Enter CT nameplate data (ratio, class, burden)
3. Select test mode (ratio, polarity, excitation)
4. Perform test
5. Record results
6. Compare with acceptance criteria

4.2 Multi-Core CT Testing

CTs with multiple cores (metering, protection, standby) require testing each core:

Core Purpose Ratio Test Polarity Test
Core 1 Metering (0.5S) Yes Yes
Core 2 Protection (5P20) Yes Yes
Core 3 Standby/Reserve Yes (if used) Yes (if used)

Procedure:

1. Test Core 1 (metering)
2. Short Core 1 secondary
3. Test Core 2 (protection)
4. Short Core 2 secondary
5. Test Core 3 (if used)
6. Record all results

5. Testing During Commissioning & Maintenance

5.1 Factory Acceptance Tests (FAT)

Test Method Acceptance Criteria
Ratio Test Primary injection, multiple taps < ±0.2% (metering), < ±1% (protection)
Polarity Test DC method or tester Correct (subtractive)
Excitation Test Secondary voltage injection Knee-point ≥ nameplate
Insulation Test Megger, withstand voltage > 1000 MΩ, no flashover

5.2 Site Acceptance Tests (SAT)

Test Method Acceptance Criteria
Ratio Test CT tester or primary injection < ±1% of factory
Polarity Test CT tester or DC method Correct
Burden Test Measure secondary circuit resistance ≤ Rated burden
Secondary Injection Relay test kit Relay operates correctly

5.3 Periodic Maintenance Testing

Test Interval Acceptance Criteria
Ratio Test 3-6 years < ±1% of baseline
Polarity Test 3-6 years (after modification) Correct
Excitation Test 3-6 years Knee-point ≥ 90% baseline
Insulation Resistance Annual > 1000 MΩ

6. Safety Precautions

6.1 CT Secondary Open Circuit Hazard

WARNING: Never open CT secondary circuit while primary current is flowing!

Consequences:
– High voltage (hundreds to thousands of volts) across secondary terminals
– Core saturation, overheating
– Insulation breakdown, fire hazard
– Electric shock hazard

Precautions:
– Always short CT secondary before disconnecting
– Use shorting test switches or terminal blocks
– Verify short circuit before working on secondary circuit
– Wear PPE (insulating gloves, safety glasses, arc flash suit if required)

6.2 Test Safety Checklist

☐ De-energize CT primary circuit (for FAT/SAT)
☐ Isolate CT from relay/meter secondary circuit
☐ Short CT secondary terminals (except test terminal)
☐ Verify grounding
☐ Wear PPE (insulating gloves, safety glasses)
☐ Use insulated test leads
☐ Verify test equipment calibration
☐ Follow lockout/tagout procedures
☐ Post warning signs

7. Standards & References

7.1 IEC Standards

Standard Title Relevant Sections
IEC 61869-2 Current Transformers §6.3 (Ratio Test), §6.4 (Polarity Test)
IEC 60044-1 CTs (Legacy) §5 (Tests)

7.2 IEEE Standards

Standard Title Relevant Sections
IEEE C57.13 Instrument Transformers §4.2 (Ratio Test), §4.3 (Polarity Test)
IEEE 80 Substation Grounding §5 (Safety)

8. Engineering FAQ

Q1: Can I perform ratio test on energized CT?

A: No. Ratio test requires primary injection with CT de-energized and isolated. For energized CTs, use clamp ammeter to measure primary and secondary current simultaneously and calculate ratio indirectly.

Q2: What is the difference between additive and subtractive polarity?

A:
Subtractive polarity (standard): Primary current enters P1, secondary current leaves S1. Most common.
Additive polarity: Primary current enters P1, secondary current enters S1. Rare, used in specific applications.
IEC and IEEE standards specify subtractive polarity as default.

Q3: How do I verify CT polarity in the field without a tester?

A: Use battery and analog meter (DC method):
1. Connect battery to primary (P1 +, P2 -)
2. Connect analog meter to secondary (S1 +, S2 -)
3. Momentarily connect battery
4. Positive deflection → Additive; Negative deflection → Subtractive (standard)

Q4: What causes CT ratio error?

A: Common causes:
Shorted turns: Internal winding fault
Wrong tap: Incorrect tap selection on multi-ratio CT
Burden too high: Exceeds rated burden, causes saturation
Core damage: Mechanical impact, overheating
Investigate and replace if error > ±1%.

Q5: How often should I test CT ratio and polarity?

A:
Factory: Every CT, every core
Site commissioning: Every CT, every core
Maintenance: Every 3-6 years, or after modification/relay replacement
After fault: If CT exposed to high fault current, verify ratio/excitation


9. Conclusion

CT ratio and polarity testing are essential diagnostic tests that verify CT accuracy and correct connection for metering and protection applications. Proper testing procedures, equipment, and safety precautions ensure reliable operation and prevent protection misoperation.

Key testing principles:
Ratio test: Verify < ±0.2% (metering), < ±1% (protection)
Polarity test: Verify correct (subtractive) polarity
Multi-core testing: Test each core independently
Safety: Never open CT secondary, short before disconnecting, wear PPE
Frequency: Factory (100%), site (100%), maintenance (3-6 years)

Design checklist:

☐ Test equipment selected (CT tester, primary injection kit)
☐ Test procedures defined (ratio, polarity, multi-core)
☐ Acceptance criteria established (per IEC 61869-2, IEEE C57.13)
☐ Safety precautions specified (shorting, PPE, lockout/tagout)
☐ Commissioning test schedule defined
☐ Maintenance test schedule defined (3-6 years)
☐ Documentation updated (test reports, CT records)

Technical Reference: IEC 61869-2:2016, IEEE C57.13-2016
Product Reference: Duomatech LZZBJ9 series (cast-resin CTs), LJWD series (oil-immersed CTs) — optimized for ratio and polarity testing