Substation Metering & Protection with ZW-10 11kV Cast-Resin Current Transformer per IEC 61869-2
Thomas Insights

Substation Metering & Protection with ZW-10 11kV Cast-Resin Current Transformer per IEC 61869-2

May 22, 2026 Documents

Introduction to the ZW-10 Current Transformer The ZW-10 is a high-reliability, indoor-type cast-resin insulated current ...

Article Content




Introduction to the ZW-10 Current Transformer

The ZW-10 is a high-reliability, indoor-type cast-resin insulated current transformer (CT) engineered for critical metering and protection functions in 11 kV medium-voltage (MV) power distribution systems. Designed in strict compliance with IEC 61869-2 and GB/T 20840.2, this device exemplifies modern advancements in solid dielectric insulation technology for instrument transformers.

Cast-Resin Insulation Technology Principles

Cast-resin insulation in the ZW-10 employs a thermosetting epoxy resin system—typically a cycloaliphatic or bisphenol-A-based formulation—vacuum-cast under controlled conditions around the primary conductor and secondary windings. This process eliminates air voids and moisture ingress pathways, resulting in a monolithic, void-free dielectric structure with high mechanical strength and excellent tracking resistance. The resin matrix encapsulates grain-oriented electrical steel (GOES) cores and copper windings, providing both electrical insulation and mechanical support.

Key material properties include:

  • Relative permittivity (εr): 3.5–4.2 at 50 Hz
  • Volume resistivity: >1014 Ω·cm
  • Dielectric strength: ≥20 kV/mm
  • Comparative Tracking Index (CTI): ≥600 V (IEC 60112)

Key Advantages Over Oil-Immersed Designs

Compared to traditional oil-filled CTs, the ZW-10’s cast-resin construction offers significant operational and safety benefits:

  • Fire safety: Non-flammable, eliminating fire hazards in confined indoor switchgear rooms per IEC 61641.
  • Maintenance-free operation: No oil sampling, degassing, or leakage monitoring required.
  • Environmental resilience: Immune to oil oxidation, moisture absorption, and thermal cycling-induced seal degradation.
  • Compact footprint: Higher dielectric strength allows reduced creepage and clearance distances, optimizing space in metal-enclosed switchgear.
  • Vibration resistance: Rigid encapsulation minimizes core movement under short-circuit forces, preserving accuracy.

ZW-10 Specific Innovations

The ZW-10 incorporates several design enhancements tailored for MV substation reliability:

  • Dual-core configuration (optional): One core optimized for 0.2S/0.5S metering accuracy, another for 5P10/5P20 protection class.
  • Integrated electrostatic shields between primary and secondary windings to suppress capacitive coupling and improve transient response.
  • Precision-wound secondary coils with low inter-turn capacitance to minimize phase angle error under burden variations.
  • UV-stabilized outdoor-rated resin variants available for pole-mounted applications.

Technical Specifications and Design Parameters

The ZW-10 is engineered to meet stringent performance criteria across electrical, thermal, and mechanical domains.

Rated Voltage, Current, and Frequency

Parameter Value Standard Reference
System Voltage (Um) 12 kV (rated for 11 kV systems) IEC 60038
Primary Rated Current (Ip) 50 A to 3150 A (standard steps) IEC 61869-2 Table 1
Secondary Rated Current (Is) 1 A or 5 A IEC 61869-2
Rated Frequency 50 Hz or 60 Hz IEC 60044-1

Insulation Levels

The ZW-10 complies with IEC 60071-1 insulation coordination requirements for 12 kV systems:

  • Power Frequency Withstand Voltage: 28 kV rms, 1 min (phase-to-earth)
  • Lightning Impulse Withstand Voltage (BIL): 75 kV peak (1.2/50 μs waveform)
  • Partial Discharge Inception Voltage (PDIV): ≥1.2 × Um/√3 = 8.3 kV
  • Maximum Partial Discharge Magnitude: ≤10 pC at 1.2 × Um/√3

Accuracy Classes

Dual-core models support independent accuracy specifications:

Application Accuracy Class Max Composite Error Burden (VA)
Metering 0.2S / 0.5S ±0.2% / ±0.5% 5–15 VA
Protection 5P10 / 5P20 ≤5% at 10×/20× Ipn 15–30 VA

Note: The “S” suffix denotes special accuracy requirements for wide-range metering (e.g., smart grid revenue metering per IEC 62053-22).

Thermal and Dynamic Performance

  • Short-Time Thermal Current (Ith): 20–40 kA for 1 s (depends on primary rating)
  • Dynamic Withstand Current (Idyn): 2.5 × Ith (peak)
  • Temperature Rise Limit: ≤60 K for windings (measured by resistance method per IEC 61869-2)
  • Ambient Operating Range: –25°C to +40°C (indoor); –40°C to +45°C (outdoor variant)

IEC 61869 Compliance and Standards

IEC 61869-2 Specific Requirements

IEC 61869-2:2012 (“Instrument transformers – Part 2: Additional requirements for current transformers”) defines essential performance, testing, and marking criteria. The ZW-10 satisfies all mandatory clauses, including:

  • Clause 5.3: Insulation coordination per IEC 60071
  • Clause 5.5: Accuracy verification under defined burden and frequency
  • Clause 5.7: Temperature rise limits under rated continuous current
  • Clause 5.9: Short-circuit withstand capability
  • Clause 6.4: Partial discharge measurement methodology

Testing and Verification Procedures

Compliance is demonstrated through a comprehensive test matrix:

  • Type Tests: Performed once per design (e.g., temperature rise, short-circuit, PD)
  • Routine Tests: Conducted on every unit (e.g., power frequency withstand, accuracy check, polarity verification)
  • Special Tests: On request (e.g., seismic withstand, chopped impulse)

Comparison with GB/T 20840 Standards

GB/T 20840.2—China’s national adoption of IEC 61869-2—is technically harmonized but includes localized requirements:

  • Stricter partial discharge limits in some utility specifications (e.g., ≤5 pC at 1.2 Um/√3)
  • Mandatory seismic qualification for regions in Zone 8+ per GB 50260
  • Additional creepage distance requirements for coastal/polluted environments (≥20 mm/kV)

The ZW-10 is dual-certified, bearing both IEC 61869-2 and GB/T 20840.2 marks, facilitating global deployment.

International Certification Requirements

Beyond base standards, the ZW-10 often undergoes third-party certification:

  • KEMA-KEUR (Netherlands)
  • UL 61869 (USA/Canada)
  • SASO (Saudi Arabia)
  • BIS (India)

Installation Guidelines and Best Practices

Site Preparation and Environmental Requirements

Install only in clean, dry environments with relative humidity ≤80% (non-condensing). Avoid locations with:

  • Chemical vapors (e.g., chlorine, sulfur compounds)
  • Excessive dust or conductive particulates
  • Mechanical vibration sources (>0.5 g)

Mounting Procedures (Indoor/Outdoor)

The ZW-10 features standardized M12 or M16 threaded studs for secure panel or busbar mounting. Key steps:

  1. Verify mechanical alignment to prevent stress on primary conductor.
  2. Torque mounting bolts to 45–60 N·m (per manufacturer spec).
  3. Ensure minimum clearance to grounded parts: ≥125 mm (11 kV system).
  4. For outdoor use, orient secondary terminal box downward to prevent water ingress.

Electrical Connections and Grounding

  • Primary conductor must fully penetrate the central aperture without contact.
  • Secondary terminals: Use ring lugs with anti-oxidant compound; torque to 2.5 N·m.
  • Critical: Secondary winding must NEVER be left open-circuited during operation—use shorting links during maintenance.
  • Ground the transformer frame and electrostatic shield via dedicated 6 mm² Cu conductor to substation earth grid.

Safety Precautions During Installation

Adhere to IEC 61936-1 and local arc-flash protocols:

  • De-energize upstream circuit and apply lockout/tagout (LOTO).
  • Perform dielectric tests only with calibrated, current-limited HV sources.
  • Wear arc-rated PPE (Category 2 minimum for 11 kV).

Operation and Performance Characteristics

Load Behavior and Burden Considerations

The ZW-10’s accuracy is burden-dependent. Total connected burden (Zb) must not exceed rated VA:

  • Metering circuits: Typically 2–10 VA (watt-hour meters, AMR devices)
  • Protection circuits: 5–25 VA (relays, fault recorders)

Exceeding burden causes increased ratio and phase errors, potentially compromising relay coordination.

Transient Response Characteristics

Under fault conditions, the ZW-10 exhibits:

  • Remanence factor (kr) ≤ 0.7 due to GOES core with controlled hysteresis
  • Time to saturation > 30 ms at 20× Ipn (for 5P20 class)
  • DC offset immunity up to 100% (X/R = 15)

Temperature Rise and Thermal Management

Continuous operation at 1.2× Ipn results in ≤60 K rise above ambient. Heat dissipates radially through the resin body—no forced cooling required. Avoid installing near heat sources (e.g., power cables, reactors).

Partial Discharge Performance

Factory-tested per IEC 60270, the ZW-10 maintains PD levels <10 pC at 1.2 Um/√3 throughout its 30-year service life, provided operating voltage does not exceed Um.

Testing Procedures and Quality Assurance

Factory Acceptance Testing (FAT)

Each unit undergoes:

  • Winding resistance measurement
  • Ratio and polarity verification
  • Accuracy test at 5%, 20%, 100%, and 120% Ipn
  • Power frequency withstand (28 kV, 1 min)
  • Partial discharge scan (10–15 kV range)

Site Commissioning Tests

Post-installation verification includes:

  • Insulation resistance (>1000 MΩ @ 2500 V DC)
  • Secondary circuit continuity and burden check
  • Polarity confirmation via DC kick test
  • Ratio verification using portable CT analyzer

Routine and Type Tests per IEC 61869-2

Type tests (design validation):

  • Temperature rise
  • Short-time current
  • Dynamic current
  • Capacitance and tan δ (if applicable)

Diagnostic Testing Methods

For in-service assessment:

  • Excitation (knee-point) test to detect core degradation
  • Insulation resistance trend analysis
  • Online PD monitoring (for critical feeders)

Maintenance and Troubleshooting

Preventive Maintenance Schedules

Cast-resin CTs require minimal maintenance:

  • Visual inspection annually (cracks, discoloration, terminal corrosion)
  • Insulation resistance test every 3–5 years
  • Burden verification during relay calibration cycles

Common Fault Diagnosis

Symptom Possible Cause Diagnostic Action
High ratio error Open secondary, core saturation, burden overload Check connections, measure burden, perform excitation test
Elevated temperature Loose primary connection, excessive harmonic current Thermal imaging, harmonic analysis
Cracking/resin discoloration UV exposure (outdoor), thermal cycling fatigue Replace if surface tracking observed

Insulation Resistance Testing

Use a 2500 V megohmmeter:

  • Primary-to-secondary/frame: >1000 MΩ
  • Secondary-to-frame: >100 MΩ

A drop >50% from baseline indicates moisture ingress or resin degradation.

When to Replace vs Repair

Cast-resin CTs are not field-repairable. Replace if:

  • Insulation resistance <100 MΩ
  • Visible cracks or carbon tracking
  • Accuracy fails after verifying external burden

Application Scenarios and System Integration

Substation Metering Applications

The ZW-10’s 0.2S class enables precise energy billing in:

  • Utility revenue metering points
  • Industrial plant sub-metering
  • Demand-side management systems

Protection Relay Coordination

5P-class cores ensure reliable operation of:

  • Overcurrent relays (IEC 60255-151)
  • Differential protection schemes
  • Earth-fault detection (residual CT configuration)

Coordination studies must account for CT saturation during high-magnitude faults.

Integration with SCADA Systems

Secondary outputs interface with:

  • Numeric relays (e.g., SEL-751, Siemens 7SJ)
  • RTUs and IEDs via analog inputs
  • Power quality analyzers for harmonic monitoring

Case Studies and Field Experience

In a 2023 urban substation retrofit (Shanghai), 24 ZW-10 units replaced oil-filled CTs. Results after 18 months:

  • Zero maintenance interventions
  • Metering accuracy maintained within ±0.3%
  • Successful tripping during 18 kA fault (5P20 verified)

FAQ1: Can the ZW-10 be used in 12 kV systems?

Yes. The ZW-10 is rated for Um = 12 kV, making it suitable for nominal 11 kV systems per IEC 60038. Continuous operation at 12 kV is permissible within thermal and dielectric limits.

FAQ2: What is the maximum allowable burden for a 5P20 class?

The rated burden for 5P20 is typically 15–30 VA. However, the actual maximum depends on the specific model’s knee-point voltage (Ek). Verify using: Zb(max) = Ek / (20 × Isn) – Rct, where Rct is secondary winding resistance.

FAQ3: Is outdoor installation possible?

Yes, with the outdoor-rated variant featuring UV-stabilized resin, hydrophobic surface treatment, and IP54 terminal box. Standard indoor models are not rated for direct weather exposure.

FAQ4: How does remanence affect protection performance?

Remanence (residual flux) can reduce the effective knee-point voltage, causing premature saturation during subsequent faults. The ZW-10’s GOES core and controlled air gaps (if present) limit kr ≤ 0.7, ensuring 5P20 performance even with DC offset.

FAQ5: Can multiple secondaries share one core?

No. Each accuracy class (metering, protection) requires a dedicated magnetic core to prevent cross-coupling and ensure independent performance. The ZW-10 uses physically separated cores within one housing.

FAQ6: What is the expected service life?

Under normal operating conditions (≤40°C ambient, no overvoltage), the ZW-10 has a design life of ≥30 years. Accelerated aging occurs above 50°C ambient or with sustained overcurrent (>1.2 Ipn).