PT for Synchronism Check & Auto-Reclosing: Voltage Transformer Accuracy, Phase Shift & Relay Coordination Guide (IEC 61869-3, IEEE C57.13)
Thomas Insights

PT for Synchronism Check & Auto-Reclosing: Voltage Transformer Accuracy, Phase Shift & Relay Coordination Guide (IEC 61869-3, IEEE C57.13)

May 10, 2026 Documents

PT for Synchronism Check & Auto-Reclosing: Voltage Transformer Accuracy, Phase Shift & Relay Coordination Guide ...

Article Content

PT for Synchronism Check & Auto-Reclosing: Voltage Transformer Accuracy, Phase Shift & Relay Coordination Guide (IEC 61869-3, IEEE C57.13)

Meta Description: Comprehensive guide on voltage transformer (PT) requirements for synchronism check and auto-reclosing applications. Covers accuracy class, phase angle error, transient response, relay coordination, and compliance with IEC 61869-3 and IEEE C57.13. Includes selection methodology, testing procedures, and troubleshooting for synchrocheck and auto-reclose schemes.


1. Introduction

Synchronism check and auto-reclosing are critical functions in power system protection and control, ensuring safe reconnection of power sources or network sections after fault clearance or maintenance. Voltage Transformers (PTs) provide the essential voltage signals for these functions, and their accuracy directly impacts system stability and equipment safety.

Key Requirements for PTs in Synchronism Check & Auto-Reclosing:
High ratio accuracy: Ensure voltage magnitude matches actual system voltage
Low phase angle error: Critical for synchronism check (phase angle comparison)
Fast transient response: Ensure relay operates correctly after fault clearance
Reliability: Continuous operation under normal and fault conditions

Improper PT selection or installation can cause:
Failed synchronism check: False blocking of breaker closure
Out-of-phase closing: Severe mechanical and electrical stress on generators/transformers
Auto-reclose failure: Delayed restoration or repeated fault interruption
System instability: Incorrect synchronization causes power oscillations

This guide systematically covers PT requirements for synchronism check and auto-reclosing, accuracy specifications, phase angle error limits, relay coordination, and testing per IEC 61869-3:2011 and IEEE C57.13 standards.


2. Synchronism Check Fundamentals

2.1 Synchronism Check Function (25)

The synchronism check relay (ANSI 25) verifies that two voltage sources are synchronized before allowing breaker closure:

Synchronization Conditions:

1. Voltage Magnitude Difference: |V₁ - V₂| ≤ ΔV_max (typically 5-10%)
2. Frequency Difference: |f₁ - f₂| ≤ Δf_max (typically 0.1-0.5 Hz)
3. Phase Angle Difference: |δ₁ - δ₂| ≤ δ_max (typically 10-20°)

Applications:
Generator synchronization: Connect generator to grid
Bus tie synchronization: Connect two bus sections
Auto-reclosing: Reconnect line after fault clearance
Island restoration: Reconnect isolated network sections

2.2 Auto-Reclosing Function (79)

Auto-reclosing automatically reopens and recloses a circuit breaker after fault clearance:

Auto-Reclose Sequence:

Fault → Breaker Trip → Dead Time (0.5-2s) → Reclose → Success/Failure

Types:
Single-shot: One reclose attempt
Multi-shot: Multiple reclose attempts (typically 2-3)
Fast reclose: Short dead time (0.5-1s) for transient faults
Delayed reclose: Long dead time (2-5s) for permanent fault clearance

2.3 PT Role in Synchronism Check & Auto-Reclosing

Function PT Input Relay Function Critical Parameter
Synchronism Check (25) Bus VT, Line VT Compare V_bus, V_line Phase angle error, ratio accuracy
Auto-Reclose (79) Line VT Verify dead line, synchrocheck Transient response, reliability
Synchrocheck Relay 2× PT inputs 25 function Phase angle error < 2°
Undervoltage Relay Line VT Verify dead line before reclose Ratio accuracy, response time

3. PT Accuracy Requirements

3.1 Accuracy Classes per IEC 61869-3

Class Ratio Error (%) Phase Angle Error (minutes) Application
0.1 ±0.1 ±5 High-accuracy metering
0.2 ±0.2 ±10 Revenue metering, synchrocheck
0.5 ±0.5 ±30 General metering, synchrocheck
1.0 ±1.0 ±60 Protection, indication
3P ±3.0 ±120 Protection only
6P ±6.0 ±240 Protection only

Synchronism Check Requirements:
Ratio accuracy: 0.5 or better (±0.5%)
Phase angle error: < 20 minutes (±0.33°) for 0.5 class, < 10 minutes (±0.17°) for 0.2 class
Recommendation: 0.2 class for critical synchronism check, 0.5 class for standard applications

3.2 Phase Angle Error Impact

Phase Angle Error Sources:
| Source | Typical Error | Mitigation |
|——–|————–|———–|
| PT internal | 5-30 minutes | Select 0.2/0.5 class |
| Cable burden | 2-10 minutes | Reduce burden, use 1A secondary |
| Relay input | 1-5 minutes | Calibrate relay |
| Total system | 10-40 minutes | Verify during commissioning |

Impact on Synchronism Check:

If PT phase angle error = 30 minutes (0.5°)
And relay δ_max setting = 20°
Then actual closing angle = 20° ± 0.5° (acceptable)

If PT phase angle error = 60 minutes (1.0°)
And relay δ_max setting = 10°
Then actual closing angle = 10° ± 1.0° (marginal, may cause out-of-phase closing)

3.3 PT Type Selection

PT Type Accuracy Class Phase Angle Error Application
Cast Resin 0.2, 0.5, 1.0 10-30 minutes Standard MV switchgear
Oil-Immersed 0.2, 0.5, 1.0 10-30 minutes HV/EHV substations
CVT 0.5, 1.0, 3P 30-60 minutes HV/EHV (transient response limits accuracy)
Electronic VT (EVT) 0.2, 0.5 < 5 minutes Digital substations, high accuracy

Selection Guidelines:
Generator synchronization: Cast resin 0.2 class (critical accuracy)
Bus tie synchronization: Cast resin 0.5 class (standard)
Auto-reclose: Cast resin 0.5 class or CVT (if HV)
Digital substation: EVT (native digital output, low phase error)


4. Synchronism Check Relay Coordination

4.1 Relay Input Requirements

Parameter Typical Value Notes
Rated Voltage 100V or 110V (secondary) Matches PT secondary
Frequency 50/60 Hz System frequency
Accuracy ±0.5% ratio, ±1° phase Per IEC 60255
Inputs 2× voltage (V_bus, V_line) For comparison

4.2 Relay Settings

Setting Typical Value Notes
ΔV_max 5-10% Voltage difference limit
Δf_max 0.1-0.5 Hz Frequency difference limit
δ_max 10-20° Phase angle difference limit
Dead time 0.5-2s Auto-reclose dead time
Check type Synchrocheck, Dead line, Live line Per application

4.3 Wiring Diagram

    Bus VT (PT1) ───┐
                    ├── Synchrocheck Relay (25) ── Permit to Close
    Line VT (PT2) ──┘
                    │
    Auto-Reclose Relay (79) ── Reclose Command
                    │
    Circuit Breaker ── Close/Reclose

4.4 Common Relay Functions

Function ANSI Description
Synchronism Check 25 Verifies synchronization conditions
Auto-Reclose 79 Automatically recloses breaker after fault
Undervoltage 27 Verifies dead line before reclose
Overvoltage 59 Detects abnormal voltage conditions
Frequency Relay 81 Monitors system frequency

5. Auto-Reclosing Scheme Design

5.1 Auto-Reclose Logic

Fault Detected → Breaker Trip → Timer Start (Dead Time)
    │
    ├── If Dead Line (V_line < threshold) → Reclose (No Synchrocheck)
    │
    └── If Live Line (V_line > threshold) → Synchrocheck → Reclose (if synchronized)

5.2 Dead Time Selection

Application Dead Time Rationale
Fast Reclose (Transient Fault) 0.5-1.0s Arc extinction, quick restoration
Standard Reclose 1.0-2.0s General transmission/distribution
Delayed Reclose (Permanent Fault) 2.0-5.0s Ensure fault clearance, equipment cooling
Generator Reclose 5.0-10.0s Generator stabilization, synchronization

5.3 PT Requirements for Auto-Reclosing

Requirement Specification Notes
Accuracy 0.5 class (ratio), < 30 min (phase) Ensures correct voltage/phase measurement
Transient Response T2 or better (CVT), fast (cast resin) Ensures relay operates correctly after fault
Reliability MTBF > 20 years Continuous operation required
Burden < 50% of rated burden Ensures accuracy under all conditions

6. Testing & Commissioning

6.1 PT Accuracy Testing

Test Method Acceptance Criteria
Ratio Test Apply rated voltage, measure secondary Within accuracy class (0.2/0.5)
Phase Angle Test Measure phase shift between primary/secondary < 20 min (0.2), < 30 min (0.5)
Burden Test Apply rated burden, verify accuracy Within accuracy class
Frequency Response Test at 50/60 Hz, verify accuracy Within accuracy class

6.2 Synchronism Check Relay Testing

Test Method Acceptance Criteria
Voltage Accuracy Inject known voltage, verify measurement Within ±0.5%
Phase Angle Accuracy Inject phase-shifted voltage, verify measurement Within ±1°
ΔV_max Test Vary voltage difference, verify blocking/trip Operates at setting ±5%
Δf_max Test Vary frequency difference, verify blocking/trip Operates at setting ±0.05 Hz
δ_max Test Vary phase angle, verify blocking/trip Operates at setting ±1°
Dead Line Test Apply low voltage, verify dead line detection Operates at threshold ±5%

6.3 Auto-Reclose Sequence Testing

Test Method Acceptance Criteria
Dead Time Test Simulate fault, measure dead time Within setting ±0.1s
Reclose Success Simulate synchronized reclose Breaker closes successfully
Reclose Failure Simulate out-of-phase condition Breaker remains open, alarm
Multi-Shot Test Simulate multiple faults, verify reclose sequence Correct number of reclose attempts
Lockout Test Simulate permanent fault, verify lockout Breaker locks out after final attempt

6.4 Commissioning Checklist

☐ PT ratio and phase angle verified
☐ PT burden within rated limits
☐ Synchrocheck relay settings verified
☐ Auto-reclose dead time verified
☐ Dead line/live line logic verified
☐ Synchronization conditions verified (ΔV, Δf, δ)
☐ Out-of-phase blocking verified
☐ Multi-shot sequence verified
☐ Lockout logic verified
☐ Documentation updated (single-line diagram, relay settings)

7. Standards & References

7.1 IEC Standards

Standard Title Relevant Sections
IEC 61869-3 Voltage Transformers §5.2 (Accuracy), §6.2 (Tests)
IEC 60255 Measuring Relays §5 (Synchronism Check)
IEC 62271-1 Switchgear §5.3 (Control)

7.2 IEEE Standards

Standard Title Relevant Sections
IEEE C57.13 Instrument Transformers §3 (Accuracy)
IEEE C37.122 Switching Practices §4 (Auto-Reclose)
IEEE C37.118 Synchrophasor §3 (Accuracy)

8. Engineering FAQ

Q1: Why do I need 0.2 class PT for generator synchronization?

A: Generator synchronization requires precise voltage and phase angle matching to prevent out-of-phase closing, which can cause severe mechanical stress on the generator shaft and electrical stress on the windings. 0.2 class PTs ensure ratio error < ±0.2% and phase angle error < ±10 minutes, providing the accuracy needed for reliable synchronization.

Q2: Can I use CVTs for synchronism check?

A: CVTs can be used, but their transient voltage response (TVR) and higher phase angle error (30-60 minutes) may affect synchronism check accuracy. For HV/EHV applications where CVTs are required, ensure:
– TVR class T1 or T2
– Phase angle error < 30 minutes
– Relay has TVR compensation (if available)
– Verify accuracy during commissioning

Q3: How do I verify PT phase angle error in the field?

A:
– Use a precision phase angle meter or power quality analyzer
– Measure phase shift between primary (system) and secondary (PT output) voltages
– Compare with relay measurement
– Verify within accuracy class limits (0.2: < 10 min, 0.5: < 30 min)

Q4: What happens if the synchrocheck relay allows out-of-phase closing?

A: Out-of-phase closing causes:
High mechanical stress: Torque spike on generator/transformer shaft
High electrical stress: Current surge (5-10× rated), winding deformation
System instability: Power oscillations, voltage dip
Equipment damage: Potential failure of generator, transformer, or breaker
Prevention: Verify relay settings, PT accuracy, and out-of-phase blocking during commissioning.

Q5: How do I select the auto-reclose dead time?

A:
Transmission lines: 0.5-1.0s (fast reclose for transient faults)
Distribution lines: 1.0-2.0s (standard reclose)
Cable networks: 2.0-5.0s (delayed reclose, cable faults often permanent)
Generator circuits: 5.0-10.0s (generator stabilization, synchronization)
Consider fault type, arc extinction time, and system stability requirements.


9. Conclusion

Voltage transformers for synchronism check and auto-reclosing require high accuracy, low phase angle error, and reliable operation to ensure safe and efficient power system restoration. Proper PT selection, relay coordination, and commissioning testing are critical to prevent out-of-phase closing and ensure successful auto-reclosing.

Key selection principles:
Accuracy: 0.2 class for critical synchronization, 0.5 class for standard applications
Phase angle error: < 20 minutes (0.2), < 30 minutes (0.5)
Relay coordination: Verify ΔV, Δf, δ settings with PT accuracy
Testing: Perform comprehensive accuracy and sequence testing during commissioning
Reliability: Ensure continuous operation under normal and fault conditions

Design checklist:

☐ PT accuracy class selected (0.2 or 0.5)
☐ Phase angle error verified (< 20/30 minutes)
☐ Relay settings coordinated (ΔV, Δf, δ)
☐ Auto-reclose dead time selected
☐ Dead line/live line logic specified
☐ Commissioning test procedures defined
☐ Out-of-phase blocking verified
☐ Documentation updated (single-line diagram, relay settings)

Technical Reference: IEC 61869-3:2011, IEC 60255, IEEE C57.13-2016, IEEE C37.122-2012
Product Reference: Duomatech JDZ/JDZX series (cast-resin PTs, 0.2/0.5 class) — optimized for synchronism check and auto-reclosing applications