Digital Substation & IEC 61850 Instrument Transformers: Merging Units, Process Bus & Digital Output Guide (IEC 61850-9-2, IEC 61869-9)
Thomas Insights

Digital Substation & IEC 61850 Instrument Transformers: Merging Units, Process Bus & Digital Output Guide (IEC 61850-9-2, IEC 61869-9)

May 19, 2026 Documents

Digital Substation & IEC 61850 Instrument Transformers: Merging Units, Process Bus & Digital Output Guide (IEC 6...

Article Content

Digital Substation & IEC 61850 Instrument Transformers: Merging Units, Process Bus & Digital Output Guide (IEC 61850-9-2, IEC 61869-9)

Meta Description: Comprehensive guide on digital substation instrument transformers and IEC 61850 integration. Covers merging units (MU), process bus, digital output (IEC 61850-9-2, IEC 60044-8), and compliance with IEC 61869-9. Includes architecture, selection methodology, testing procedures, and troubleshooting for digital CTs/PTs in smart grid applications.


1. Introduction

Digital substations represent a paradigm shift from traditional analog instrument transformers to digital output devices integrated with IEC 61850 process bus communication. This transition offers:
Reduced copper cabling: Fiber optic replaces heavy CT/PT secondary cables
Improved accuracy: Digital signal, no burden-induced error
Enhanced functionality: Multi-function merging units, synchronized sampling
Compact design: Low-power output sensors, digital relays
Smart grid integration: IEC 61850-9-2 process bus, GOOSE messaging, IEEE C37.118 synchrophasor

Key components in digital substation instrument transformer systems:
Digital CT/PT: Low-power output (0-4V, ±4V) or native digital output
Merging Unit (MU): Samples analog/digital signals, formats per IEC 61850-9-2 or IEC 60044-8
Process Bus: Fiber optic network connecting MU to relays, meters, control system
Digital Relays/IEDs: Accept digital samples, perform protection/control functions

This guide systematically covers digital substation instrument transformer architecture, IEC 61850-9-2 communication, merging unit functionality, selection methodology, and testing per IEC 61869-9:2016 and IEC 61850-9-2:2017 standards.


2. Digital Substation Architecture

2.1 IEC 61850 Substation Automation System (SAS) Layers

    ┌─────────────────────────────────────────────────────┐
    │              Station Level (Control Center)          │
    │  SCADA, HMI, Engineering Workstation, Gateway        │
    │              │ (GOOSE, MMS over Ethernet)            │
    └──────────────┼───────────────────────────────────────┘
                   │
    ┌──────────────┼───────────────────────────────────────┐
    │              Bay Level (Protection & Control)         │
    │  Digital Relays, IEDs, Metering, Control Units       │
    │              │ (GOOSE, Sampled Values)               │
    └──────────────┼───────────────────────────────────────┘
                   │
    ┌──────────────┼───────────────────────────────────────┐
    │            Process Level (Sensors & Actuators)        │
    │  Digital CTs/PTs, Merging Units (MU), Control Units  │
    │              │ (IEC 61850-9-2, Fiber Optic)           │
    └──────────────┼───────────────────────────────────────┘
                   │
    ┌──────────────┼───────────────────────────────────────┐
    │            Primary Equipment (HV System)              │
    │  Busbars, Circuit Breakers, CTs/PTs, Disconnectors   │
    └─────────────────────────────────────────────────────┘

2.2 Process Bus Communication

Standard Protocol Data Type Application
IEC 61850-9-2 Sampled Values (SV) Analog samples (current, voltage) Protection, metering
IEC 61850-9-2 LE Sampled Values (SV) Lightweight, simplified Retrofit, distribution
IEC 60044-8 Process Bus (FT3) Analog samples (legacy) Legacy digital systems
GOOSE Generic Object Oriented Substation Event Trip, control, status Fast control, interlocking

2.3 IEC 61850-9-2 Frame Structure

    Ethernet Header (MAC Address)
         │
         ├── APPID (Application Identifier)
         │
         ├── SmpCnt (Sample Counter)
         │
         ├── ConfRev (Configuration Revision)
         │
         ├── Data Set
         │     ├── Ia (Phase A Current)
         │     ├── Ib (Phase B Current)
         │     ├── Ic (Phase C Current)
         │     ├── In (Residual Current)
         │     ├── Va (Phase A Voltage)
         │     ├── Vb (Phase B Voltage)
         │     ├── Vc (Phase C Voltage)
         │     └── ... (Additional channels)
         │
         └── Status / Quality Flags

Key Parameters:
Sampling Rate: 4 kHz (80 samples/cycle at 50 Hz), 4.8 kHz (96 samples/cycle at 60 Hz)
Transmission Interval: 250 μs (50 Hz), 208.33 μs (60 Hz)
Synchronization: IEEE 1588 PTP or IRIG-B
Jitter: < 4 μs (protection applications)


3. Merging Unit (MU) Architecture

3.1 MU Functions

Function Description Standard Reference
Analog Input Accept analog signals from CT/PT (0-4V, ±4V, 4-20 mA) IEC 61869-9
Digital Input Accept digital signals from electronic CT/PT IEC 61869-9
Sampling Synchronized sampling at 4/4.8 kHz IEC 61850-9-2
Formatting Format samples per IEC 61850-9-2 or IEC 60044-8 IEC 61850-9-2
Time Stamping Apply IEEE 1588 PTP or IRIG-B timestamp IEC 61850-9-2
Transmission Transmit SV frames over fiber optic Ethernet IEC 61850-9-2
Status/Monitoring Monitor MU health, link status, sample quality IEC 61850-9-2

3.2 MU Input/Output Configuration

Typical MU Configuration:
| Input Type | Channels | Output Protocol |
|———–|———|—————-|
| Analog Voltage | 12-16 channels (Ia, Ib, Ic, In, Va, Vb, Vc, …) | IEC 61850-9-2 |
| Digital (Serial) | 4-8 channels (native digital CT/PT) | IEC 61850-9-2 |
| PTP/IRIG-B | 1 input (synchronization) | Synchronized SV |
| GOOSE | 4-8 inputs/outputs (trip, control, status) | GOOSE |

3.3 MU Synchronization

Method Accuracy Application Notes
IEEE 1588 PTP ±1 μs Digital substation Requires PTP-capable switches
IRIG-B ±1 ms Retrofit, distribution Simple, widely used
SNTP ±10 ms Station level Not suitable for protection
Internal Clock ±100 μs (holdover) Backup Fallback if PTP/IRIG-B lost

4. Digital CT/PT Types

4.1 Low-Power Output CT/PT

Type Output Accuracy Application
LPCT (Current) 0-4V (metering), ±4V (protection) 0.5, 5P Digital substation, MV/HV
LPVT (Voltage) 0-4V (metering), ±4V (protection) 0.5, 3P Digital substation, MV/HV
Rogowski Coil mV/A or digital 0.5, 5P Digital substation, wideband
Optical CT (OCT) Digital (fiber) 0.2, 5P EHV, smart grid
EVT (Electronic VT) Digital (fiber) 0.2, 3P EHV, smart grid

4.2 Analog vs. Digital Output Comparison

Parameter Analog Output (0-4V) Digital Output (IEC 61850-9-2)
Signal Continuous voltage Discrete samples (16-bit)
Burden Low (< 0.1 VA) None (MU burden)
Cable Copper (shielded) Fiber optic (single-mode)
Distance < 100 m (voltage drop) < 20 km (fiber)
EMI Susceptible (shielding required) Immune (fiber)
Accuracy ±0.5% (burden-dependent) ±0.1% (digital)
Synchronization Not inherent IEEE 1588 PTP / IRIG-B
Multi-function Single relay per cable Multiple IEDs (multicast)

5. Selection Methodology

5.1 MU Selection Parameters

Parameter Description Standard Reference
Input Channels Number of analog/digital inputs Per bay configuration
Input Type Voltage (0-4V, ±4V), Digital, Rogowski IEC 61869-9
Sampling Rate 4 kHz (50 Hz), 4.8 kHz (60 Hz) IEC 61850-9-2
Synchronization IEEE 1588 PTP, IRIG-B IEC 61850-9-2
Output Protocol IEC 61850-9-2, IEC 60044-8, LE Per IED compatibility
Network Fiber optic (single-mode), Ethernet switch IEC 61850-9-2
Environmental Temperature, humidity, IP rating IEC 61850-3

5.2 Digital CT/PT Selection Parameters

Parameter Description Standard Reference
Rated Primary Current/Voltage System current/voltage IEC 61869-2/3
Output Type Analog (0-4V, ±4V), Digital IEC 61869-9
Accuracy Class 0.2S, 0.5, 5P, TPY IEC 61869-2/3
Frequency Range 45-65 Hz (standard), DC-10 kHz (wideband) IEC 61869-9
Linearity Error < 0.1% (metering), < 1% (protection) IEC 61869-9
Transient Response TQR class (digital) IEC 61869-9

5.3 Selection Decision Tree

Determine substation type:
    │
    ├── New Digital Substation
    │     ├── MV (≤ 36 kV) → LPCT/LPVT + MU (IEC 61850-9-2)
    │     ├── HV (72.5-170 kV) → LPCT/LPVT or OCT/EVT + MU
    │     └── EHV (≥ 245 kV) → OCT/EVT + MU (native digital)
    │
    ├── Retrofit Digital Substation
    │     ├── Existing CT/PT → Analog output + MU
    │     └── Replace CT/PT → LPCT/LPVT + MU
    │
    └── Standard Analog Substation
          └── Standard CT/PT (5A/1A, 100V) → Analog relays

6. Testing & Commissioning

6.1 MU Testing

Test Method Acceptance Criteria
Input Accuracy Inject known voltage, verify digital output Within ±0.1%
Sampling Rate Test Verify sampling frequency 4 kHz (50 Hz) or 4.8 kHz (60 Hz)
Synchronization Test Verify PTP/IRIG-B lock ±1 μs (PTP), ±1 ms (IRIG-B)
Jitter Test Measure transmission jitter < 4 μs
Protocol Test Verify IEC 61850-9-2 frame structure Per IEC 61850-9-2
Link Test Verify fiber optic link No errors, adequate power
Redundancy Test Verify dual-link switching < 10 ms switchover

6.2 Digital CT/PT Testing

Test Method Acceptance Criteria
Ratio Test Inject primary current/voltage, verify output Within accuracy class
Linearity Test Inject 10-120% rated, verify output < 0.1% error
Frequency Response Inject 45-65 Hz, verify output Within accuracy class
Transient Test Inject fault current with DC offset, verify output Within TQR class
Insulation Test Verify withstand voltage Per IEC 61869-2/3

6.3 Commissioning Checklist

☐ MU input channels verified (match CT/PT output)
☐ Sampling rate verified (4/4.8 kHz)
☐ Synchronization verified (PTP/IRIG-B)
☐ IEC 61850-9-2 protocol verified (APPID, SmpCnt, data set)
☐ Fiber optic link verified (power, errors)
☐ Digital relay/IED configured (SV input, APPID, data set)
☐ Protection function test performed (secondary injection via MU)
☐ Metering accuracy test performed
☐ Redundancy test performed (if dual-link)
☐ Documentation updated (network diagram, ICD/CID files, test reports)

7. Standards & References

7.1 IEC Standards

Standard Title Relevant Sections
IEC 61850-9-2 Sampled Values Full document
IEC 61869-9 Digital Output Instrument Transformers §5 (Performance), §6 (Tests)
IEC 61850-3 Environmental Conditions §5 (Substation)
IEEE 1588 Precision Time Protocol Full document

7.2 IEEE Standards

Standard Title Relevant Sections
IEEE C57.13 Instrument Transformers §3 (Requirements)
IEEE C37.118 Synchrophasor §3 (Accuracy)
IEEE 802.3 Ethernet Full document

8. Engineering FAQ

Q1: What is the difference between IEC 61850-9-2 and IEC 60044-8?

A:
IEC 60044-8: Legacy process bus protocol (FT3 encoding), point-to-point, proprietary
IEC 61850-9-2: Modern protocol (Ethernet, multicast), standardized, multi-IED support, GOOSE integration
IEC 61850-9-2 is preferred for new digital substations.

Q2: How do I synchronize MUs in a digital substation?

A:
IEEE 1588 PTP: Best accuracy (±1 μs), requires PTP-capable switches, grandmaster clock
IRIG-B: Simple, widely used (±1 ms), B-code signal distribution
Internal clock: Backup (±100 μs holdover), fallback if primary source lost
Select method based on accuracy requirement and network infrastructure.

Q3: Can I retrofit digital MUs to existing analog CTs/PTs?

A: Yes, if CTs/PTs have low-power output (0-4V, ±4V) or can be replaced with LPCT/LPVT. Standard 5A/1A CTs require external shunt resistors to convert current to voltage, which introduces burden and reduces accuracy.

Q4: What is the maximum distance for IEC 61850-9-2 fiber optic cable?

A: Single-mode fiber optic cable supports up to 20 km (1310 nm) or 40 km (1550 nm) without repeaters. Multi-mode fiber supports up to 2 km. Verify optical power budget and link attenuation.

Q5: How do I verify IEC 61850-9-2 communication in the field?

A:
– Use IEC 61850 protocol analyzer or Wireshark with SV plugin
– Verify APPID, SmpCnt, ConfRev, data set structure
– Verify sampling rate (4/4.8 kHz), jitter (< 4 μs)
– Verify digital relay/IED receives and processes SV frames correctly


9. Conclusion

Digital substation instrument transformers and IEC 61850 process bus communication represent the future of power system automation, offering improved accuracy, reduced cabling, enhanced functionality, and smart grid integration. Proper MU selection, synchronization, protocol configuration, and testing are critical to ensure reliable protection, control, and metering.

Key selection principles:
MU: Match input channels, output protocol, synchronization method
Digital CT/PT: Match rated current/voltage, output type, accuracy class
Communication: IEC 61850-9-2 (modern), IEEE 1588 PTP (synchronization)
Testing: Verify accuracy, sampling rate, synchronization, protocol, link
Commissioning: Configure IEDs, verify protection/metering, document network

Design checklist:

☐ Substation type determined (new, retrofit, analog)
☐ Digital CT/PT selected (output type, accuracy, frequency range)
☐ MU selected (input channels, output protocol, synchronization)
☐ Network architecture specified (fiber optic, switches, PTP/IRIG-B)
☐ IEC 61850-9-2 configuration defined (APPID, data set, sampling rate)
☐ Testing procedures defined (accuracy, sampling, sync, protocol, link)
☐ Commissioning procedures defined (IED configuration, protection test)
☐ Documentation prepared (network diagram, ICD/CID files, test reports)

Technical Reference: IEC 61850-9-2:2017, IEC 61869-9:2016, IEEE 1588-2019
Product Reference: Duomatech LZZBJ9 series (cast-resin CTs), JDZ/JDZX series (cast-resin PTs) — digital output variants available for IEC 61850-9-2 integration