FDGE8 Indoor Semi-Enclosed Epoxy Resin Cast Discharge Coil

FDGE8 Indoor Semi-Enclosed Epoxy Resin Cast Discharge Coil

• Rated voltage 6.6-12kV with discharge capacity from 1.7 to 3.4 Mvar

  • Accuracy class 0.2, 0.5, or 1 with rated secondary output up to 100VA
  • Discharges capacitor residual voltage to safe value within 5 seconds
  • Iron-core semi-casting structure built with silicon steel sheets
  • Rated insulation level up to 12/42/75kV with >300mm creepage distance
  • Secondary winding provides voltage indication and optional relay output

Product Overview

The FDGE8 semi-enclosed dry type discharge coil is an single-phase epoxy resin vacuum-cast, single-phase indoor product for AC power systems at 50Hz with a rated voltage of 10kV and below. Connected in parallel with the high-voltage shunt capacitor bank, it reduces the residual voltage of the capacitor bank to a safe value within five seconds when the capacitor group is disconnected from the system. During normal operation the secondary winding functions as a voltage indicator; where users require it, a residual voltage winding can be provided to deliver relay protection.

The coil adopts an iron-core semi-casting structure in which the core is built from high-grade silicon-steel sheets. The result is a compact, light-weight unit with low no-load loss, strong resistance to over-voltage, and convenient installation that requires no maintenance. It is designed as a maintenance-free replacement for conventional oil-immersed discharge coils in capacitor bank compensation installations.

Key Features:

  • Rated voltage 6.6-12kV with discharge capacity from 1.7 to 3.4 Mvar
  • Accuracy class 0.2, 0.5, or 1 with rated secondary output up to 100VA
  • Discharges capacitor residual voltage to safe value within 5 seconds
  • Iron-core semi-casting structure built with silicon steel sheets
  • Rated insulation level up to 12/42/75kV with >300mm creepage distance
  • Secondary winding provides voltage indication and optional relay output

Product Display

 Product Display

Model Designation

 Product Type

The FDGE8 model designation follows a standardized coding system:

Example: FDGE8/11/√3-2.5-1 denotes a dry-type discharge coil with secondary winding, design No.8, rated primary voltage 11/√3 kV, matched capacitor capacity 2.5 Mvar, single phase.

Service Conditions

  • Installation: Indoor type
  • Ambient Temperature: -5°C to +40°C
  • Altitude: Not more than 1000m
  • System Frequency: 50Hz
  • Atmosphere: No corrosive gas or smoke; no conducting or explosive dust
  • Vibration: No severe mechanical vibration at the installation site
  • Relative Humidity: Monthly average ≤ 90%; daily average ≤ 95%

Construction

The FDGE8 uses an iron-core semi-casting (semi-enclosed) structure. The magnetic core is stacked from high-grade silicon-steel sheets to keep no-load loss low and to provide strong over-voltage withstand capability. Windings are encapsulated by epoxy resin vacuum casting, giving a moisture-proof, maintenance-free insulation system suited to indoor switchgear and capacitor compartments.

Construction Advantages: Semi-enclosed frame keeps the unit compact and light while allowing convenient mounting; base fixing holes and terminal arrangement suit standard capacitor bank layouts, maintenance-free design.

Technical Data

Type Rated

Voltage

(kV)

Accuracy Class

& Rated Output

(VA)

Discharge

Capacity

(Mvar)

Rated

Insulation

Level (kV)

FDGE8/6.6/√3-1.7-1 6.6/√3/0.1 0.2→20; 0.5→50; 1→100 1.7 7.2/32/60
FDGE8/7.2/√3-1.7-1 7.2/√3/0.1 0.2→20; 0.5→50; 1→100 1.7 7.2/32/60
FDGE8/11/√3-1.7-1 11/√3/0.1 0.2→20; 0.5→50; 1→100 1.7 12/42/75
FDGE8/11/√3-2.5-1 11/√3/0.1 0.2→20; 0.5→50; 1→100 2.5 12/42/75
FDGE8/11/√3-3.4-1 11/√3/0.1 0.2→20; 0.5→50; 1→100 3.4 12/42/75
FDGE8/12/√3-1.7-1 12/√3/0.1 0.2→20; 0.5→50; 1→100 1.7 12/42/75
FDGE8/12/√3-2.5-1 12/√3/0.1 0.2→20; 0.5→50; 1→100 2.5 12/42/75
FDGE8/12/√3-3.4-1 12/√3/0.1 0.2→20; 0.5→50; 1→100 3.4 12/42/75
Technical Note: Rated voltage ratio and secondary voltage (e.g. 100 V) can be customized upon technical agreement. Final parameters are subject to nameplate data and approved specifications.

Standards

The FDGE8 series conforms to the DL/T 653-1998 standard (Specification of discharge coils for high voltage parallel connection capacitor for order). Load power factor: cosφ 0.8 (lagging), surface creepage distance: more than 300mm.

Note: Final standard and test requirements shall be confirmed according to the project specification.

Installation & Dimensions

The FDGE8 discharge coil is designed for indoor installation. Overall dimensions: top width 180 mm; height 530±5 mm; base mounting 90/200±1 mm (front), 170/230±1 mm (side). Refer to the approved outline drawing before foundation and busbar work.

Installation Diagram

 Installation and Dimensions

FDGE8 Semi-Enclosed Discharge Coil Installation and Dimensions Diagram

Wiring Diagram

 Wiring Diagram

FDGE8 Semi-Enclosed Discharge Coil Wiring Diagram

The primary winding is connected in parallel across the high-voltage capacitor bank terminals (phase to neutral/earth point of the bank). The secondary winding supplies voltage indication; where fitted, the residual voltage winding connects to the protection relay. Confirm terminal markings, polarity and earthing against the approved wiring drawing before energization.

FAQs

It provides a controlled discharge path so the capacitor bank residual voltage falls to a safe level within five seconds, protecting personnel and equipment.
Yes. During normal operation the secondary winding outputs a proportional low voltage suitable for voltage indication.
On request a residual voltage winding can be provided to supply a relay for residual-voltage / unbalance protection of the capacitor bank.
Rated primary 6.6/√3, 7.2/√3, 11/√3 and 12/√3 kV with matched discharge capacities of 1.7, 2.5 and 3.4 Mvar; insulation level 7.2/32/60 or 12/42/75 kV.
No. The epoxy resin vacuum-cast, iron-core semi-casting design is maintenance-free, unlike oil-immersed discharge coils that require oil handling and testing.
It is manufactured in accordance with DL/T 653-1998, with load power factor cosφ 0.8 (lagging) and surface creepage distance greater than 300mm.

Inquiry for FDGE8 Indoor Semi-Enclosed Epoxy Resin Cast Discharge Coil:

Send your project requirements. Our team will reply with technical details and quotation.

Fast response Technical support OEM / ODM