JSZV12-20R Three-Phase Résine époxy Combination Transformateur de tension (TT) with Built-in Fuse

JSZV12-20R Three-Phase Résine époxy Combination Transformateur de tension (TT) with Built-in Fuse

20kV three-phase VT with fuse protection for XGW-12 pour extérieur switchgear

  • Three-phase V-connection résine époxy VT with integrated primary fuse protection
  • Dual secondary outputs: 100V measurement and 220V auxiliary power supply
  • Fully-enclosed cast-resin isolation with 24/65/125 kV niveau d'isolement rating
  • GB 1207-1997 compliant design with 0.2 and 0.5 classes de précision

Aperçu du produit

Définition fonctionnelle

The JSZV12-20R three-phase résine époxy combination transformateur de tension (tt) with built-in fuse protection is specifically designed for XGW-12 pour extérieur AC fixed metal-enclosed switchgear applications. This transformateur de tension (tt) provides both 100V measurement voltage output and 220V operating power supply, delivering stable power to circuit breakers while ensuring reliable operation and système efficiency.

Caractéristiques principales

Article Spécification
Classe de tension système 12 kV class (pour extérieur switchgear applications, rated 20 kV)
Fréquence assignée 50 Hz
Rated primary voltage 20 kV / √3
Rated secondary voltage 100V, 220V (as specified)
Classes de précision 0.2, 0.5 (mesurage applications)
Primary connection V-connection (open-delta)
Fuse protection Built-in primary winding fuse protection
Niveau d’isolement 24/65/125 kV (Um/Ud/Up)
Normes applicables GB 1207-1997

Principe de fonctionnement

Operating on electromagnetic induction principles, the transformateur de tension (tt) features three-phase résine époxy cast noyaus with primary and secondary enroulements. The transformer steps down high voltage to standardized measurement and auxiliary supply voltages, providing galvanically isolated secondary outputs proportional to primary voltage. The V-connection configuration enables voltage measurement with two single-phase units while also detecting ground faults in the système.

Position d’application système

  • Distribution moyenne tension: 12-20kV pour extérieur metal-enclosed switchgear (XGW-12 series)
  • Voltage Mesurage: Revenue-grade electricity measurement and voltage monitoring systèmes
  • Auxiliary Power Supply: Providing operating power for circuit breaker control and circuits de protection
  • Protection Schemes: Overvoltage, undervoltage, and ground fault protection applications

Aperçu structurel

Epoxy resin cast construction with fully-enclosed design ensures superior isolation performance, moisture resistance, and mechanical strength. The built-in fuse protection located at the primary output terminals provides easy replacement and maintenance access. The compact structure integrates voltage measurement and auxiliary power supply functions in a single unit, optimizing installation space in metal-enclosed switchgear environments.

Désignation du modèle

JSZV12 20R pour intérieur Fully enclosed epoxy resin Combined VT TYPE

Model Explication du code

  • J — Voltage transformer (VT)
  • S — Three-phase configuration
  • Z — Cast-resin (epoxy) insulated structure
  • V — V-connection (open-delta) configuration
  • 12 — Voltage class (kV)
  • 20 — Rated voltage (kV)
  • R — Built-in fuse protection

Conditions de service

The JSZV12-20R transformateur de tension (tt) is designed for pour extérieur metal-enclosed switchgear installation under normal conditions de service in medium-voltage power systèmes.

  • Environnement d’installation: Pour extérieur metal-enclosed switchgear (XGW-12)
  • Altitude: ≤1000 m above sea level (pollution level II)
  • Température ambiante: −5°C to +40°C
  • Humidité relative: ≤80%
  • Conditions environnementales: Free from corrosive gases or vapor; free from carbon dust or conductive metallic dust; no severe vibration or mechanical shock
Note technique: The installation location shall comply with applicable electrical safety regulations and provide stable operating conditions throughout the transformer’s service life.

Construction

Conception de construction

  • Structure: Three-phase combination type for pour extérieur switchgear
  • Isolation: Fully enclosed résine époxy cast isolation
  • Connection: V-connection (open-delta) configuration
  • Protection: Built-in fuse at primary output terminals
  • Système: Integrated voltage measurement and auxiliary power supply

The résine époxy casting provides stable isolation properties with excellent resistance to moisture, contamination, and aging for long-term pour extérieur switchgear service. The built-in fuse protection système prevents primary winding short-circuit conditions, enhancing overall système safety and reliability.

Enroulements & Terminal Marking

  • Bornes primaires: A, B, C (phase connections)
  • Bornes secondaires (100V): a, b, c, n (measurement voltage output)
  • Bornes secondaires (220V): 110V and 220V auxiliary power terminals

Terminal markings follow standard VT polarity conventions. Correct terminal identification shall be observed to ensure mesurage accuracy and protection performance. The auxiliary power terminals provide stable operating voltage for circuit breaker control circuits and protection relays.

Données techniques

This section provides selection-oriented données techniques for the JSZV12-20R three-phase résine époxy combination transformateur de tension (tt) with built-in fuse used in 12-20 kV class AC systèmes (50 Hz). Data shown below is intended for preliminary selection of voltage ratio, classe de précision, and puissance assignée capacity.

Definitions: Accuracy class indicates mesurage performance level. Rated output (VA) is the maximum burden that can be connected while maintaining specified accuracy. Load power factor is assumed as cosφ = 0.8 (lagging).

Référence des données

Model Rated
Voltage
Ratio (V)
Class 0.2
Output
(VA)
Class 0.5
Output
(VA)
Rated
Isolation
Level (kV)
JSZV12-20R 20000/100 30 50 24/65/125
JSZV12-20R 20000/100/100 20 50 24/65/125
JSZV12-20R 20000/220 20 50 24/65/125
JSZV12-20R 20000/100/220 20 50 24/65/125
Support technique d’application: Application-specific recommendations may include burden calculation, accuracy assessment, voltage ratio selection, and switchgear integration guidance based on project spécification.

Normes & Normative References

Standard Titre Application
GB 1207-1997 Transformateurs de tension VT exigences générales and testing
IEC 61869-3 Transformateurs de mesure – Part 3: Transformateurs de tension Optionnel (international reference)

Conformité aux tests d’usine

  • Tests de routine per GB 1207-1997 requirements (including polarity verification, vérification du rapport, and vérification de la précision per specified class and burden)
  • Tests diélectriques per isolation coordination requirements and applicable standard
  • Inspection visuelle et dimensionnelle including marking and workmanship conformity
  • Tests de type et spéciaux as required by the project spécification
Note de conformité: All units maintain full compliance with listed normes. Test certificates available for each manufactured unit with traceability to accredited laboratories.

Installation & Dimensions

Outline

JSZV12 20R Pour intérieur Three Phase Epoxy Resin Voltage Transformer with Fuse outline installation

Principle diagram

JSZV12 20R Pour intérieur Three Phase Epoxy Resin Voltage Transformer with Fuse wiring

  • Outline dimensions and mounting details are provided in the switchgear documentation
  • Le transformateur doit être securely mounted using the designated fixing holes within the XGW-12 switchgear compartment
  • Primary connections are made via busbar terminals integrated with the switchgear design
  • Dégagement adéquat shall be maintained for isolation, heat dissipation, and maintenance access
  • Built-in fuse protection is accessible from the front panel for easy replacement
Avis de sécurité: Circuit secondaire must be properly grounded in accordance with normes applicables. Toute installation and maintenance work shall comply with local electrical safety regulations.

Notes de sécurité

  • Circuit secondaire must be properly grounded in accordance with normes applicables
  • Pendant l’inspection or maintenance, the primary circuit shall be de-energized and properly isolated
  • Fuse replacement shall only be performed by qualified personnel following proper safety procedures
  • Toute installation and maintenance work shall comply with local electrical safety regulations

Informations de commande

Lors de la commande, the required configuration shall be specified according to the local grid requirements, normes applicables, and project technical spécification. The following parameters shall be clearly stated for technical confirmation and production release:

  • Rated voltage ratio (primary/secondary voltage)
  • Rated secondary voltage (100V, 220V, or combined configuration)
  • Accuracy class (0.2 or 0.5 for mesurage applications)
  • Charge assignée (VA) for each secondary winding
  • Application requirements (voltage measurement and/or auxiliary power supply)

If local utility or project requirements apply (e.g., niveau d’isolement, terminal arrangement, mounting constraints, documentation language, or required certificates), specify them at the ordering stage. Special configurations shall be confirmed by technical agreement and final data sheet prior to production.

FAQ

A: JSZV12-20R is designed for XGW-12 pour extérieur metal-enclosed switchgear in 10-20kV systèmes, providing voltage measurement, comptage d’énergie, and auxiliary power supply for circuit breaker control circuits.

A: The built-in fuse protection prevents primary winding short-circuit conditions, enhancing overall système safety and reducing the risk of transformer failure or système faults.

A: Yes, provided the humidité relative does not exceed 80% and there are no corrosive gases or conductive dust present in the environnement d’installation.

A: Yes, customization options include extended temperature range, modified voltage ratio configurations, high altitude adaptation, and specific terminal arrangements per project requirements.

A: The résine époxy cast construction provides excellent isolation properties with superior moisture resistance, anti-aging caractéristiques, and long-term reliability in pour extérieur metal-enclosed switchgear environments.

A: Compact structure with integrated voltage measurement and auxiliary power supply, built-in fuse protection for easy maintenance, compliance with internorme nationales, and cost-effective solution for modern distribution systèmes.