JDX-10 Indoor Oil-Immersed Single-Phase Voltage Transformer

JDX-10 Indoor Oil-Immersed Single-Phase Voltage Transformer

JDX-10 indoor oil-immersed single-phase voltage transformer for 10kV systems.

  • Oil-immersed insulation provides excellent dielectric strength and thermal dissipation for indoor use
  • Three-winding configuration with 0.2 class for metering, 0.5 class for control, and residual winding for protection
  • High precision 0.2/0.5/3P accuracy classes with 500VA limit output for diverse needs
  • Large capacity design meets demanding industrial measurement requirements
  • Compact single-phase structure simplifies installation requirements
  • Customizable for different countries, regions, and project requirements

Product Overview

The JDX-10 voltage transformer is an indoor oil-immersed single-phase measurement device designed for 10kV medium-voltage distribution systems. This advanced voltage transformer features three separate windings with different accuracy classes, providing comprehensive voltage measurement for metering, control, and protection applications.

The JDX-10 delivers precise voltage measurement with 0.2 class winding for energy metering, 0.5 class winding for control systems, and residual voltage winding for zero-sequence protection. The oil-immersed construction ensures excellent dielectric strength and thermal performance, while the single-phase design with large capacity and high precision meets demanding industrial requirements.

Product Display

JDX-10 Product Display
JDX-10 Product Display - Engineered for Accurate Indoor Voltage Transformation
JDX-10 Product Display - Precise Measurement Reliable Protection

Application Position

The JDX-10 is installed in indoor switchgear, substations, and distribution networks where reliable single-phase voltage measurement is required. The oil-immersed insulation provides excellent dielectric strength and thermal dissipation for continuous indoor operation. Three-winding configuration accommodates metering, control, and protection system requirements simultaneously.

Main Applications

  • 10kV indoor distribution networks
  • Substations requiring voltage measurement
  • Industrial facilities with medium-voltage supply
  • Energy metering applications (0.2 class)
  • Control system voltage monitoring (0.5 class)
  • Zero-sequence protection (residual winding)

Application Case Studies

Application Scenario 1: Substation Comprehensive Measurement
Utilities deploy the JDX-10 oil-immersed voltage transformer in 10kV indoor substations for comprehensive voltage measurement. The three-winding configuration provides 0.2 class output for energy metering, 0.5 class output for control systems, and residual voltage output for zero-sequence protection, ensuring complete system monitoring while the oil-immersed design delivers reliable performance in indoor environments.

Application Scenario 2: Industrial Medium-Voltage Metering and Protection
Industrial facilities with 10kV incoming supply require accurate voltage measurement for energy management and protection coordination. The JDX-10 offers multiple accuracy classes to meet different measurement requirements, with large capacity (500VA limit output) for various burden conditions and three-winding configuration for enhanced system flexibility.

Application Fit

Suitable For

  • Indoor 10kV voltage measurement
  • Substations with comprehensive measurement requirements
  • Industrial facilities with medium-voltage supply
  • Energy metering applications
  • Control system voltage monitoring
  • Zero-sequence protection systems
  • Outdoor installation applications
  • Current measurement applications (use CT instead)
  • High-voltage systems above 12kV (use higher voltage class models)
  • Applications requiring single winding only

Installation Conditions

  • Installation position: Indoor switchgear, substations, or distribution points
  • Ambient temperature: -5°C to +40°C
  • Altitude: ≤ 1000m (standard), higher altitude available on request
  • Insulation: Oil-immersed
  • Frequency: 50Hz or 60Hz
  • Connection: Single-phase with three windings
  • Maintenance: Periodic oil level and quality inspection recommended

Technical Parameters

The JDX-10 is an indoor oil-immersed single-phase voltage transformer for 10kV systems. Operating temperature -5°C to +40°C, compliant with IEC and GB standards.

Model Designation

Code Meaning
J Voltage transformer
D Single phase
X With residual voltage winding
10 Voltage grade (kV)

VT Data

Rated Voltage
Ratio (V)
Accuracy Class
& Rated Output (VA)
Limit Output
(VA)
Insulation Level
(kV)
10000/√3 : 100/√3 : 100/√3 : 100/3 0.2: 20
0.5: 25
3P: 50
500 12/42/75

Installation

Dimension Reference

JDX-10 Installation Diagram

View Key
Dimensions
Application
Note
Front View Height 645±10mm Bleed valve, nameplate, oil drain hole
Side View Insulator height 285±5mm; Tank height 380±5mm Secondary protection cover, terminal board
Top View Diameter φ330±5mm Circular top flange with bolt holes
Bottom View Width 250mm / 290mm Circular base dimensions

Wiring Diagram

JDX-10 Wiring Diagram

Installation Guidelines

  • Install in indoor switchgear or substation with adequate ventilation
  • Connect primary terminal A to voltage system
  • Connect neutral terminal N to system ground
  • Connect secondary terminals to meters, control systems, and protection devices
  • Connect residual winding terminals (dn) to zero-sequence protection relay
  • Verify voltage ratio matches system requirements before commissioning
  • Check oil level and insulation resistance before energizing

Three-Winding Features

The JDX-10 incorporates three separate windings including:

  • 0.2 class winding for high-precision energy metering (20VA)
  • 0.5 class winding for control system voltage monitoring (25VA)
  • Residual voltage winding for zero-sequence protection (50VA)
  • Independent circuits for enhanced system reliability

Oil-Immersed Features

The JDX-10 incorporates advanced oil-immersed insulation technology including:

  • Excellent dielectric strength for high-voltage applications
  • Superior thermal dissipation for continuous operation
  • Large capacity for various burden requirements
  • Proven reliability in indoor environments

Standards

The JDX-10 oil-immersed voltage transformer complies with IEC and GB standards for voltage transformers, ensuring compatibility with international and Chinese standards for medium-voltage measurement applications.

Selection Guide

Select by system voltage: JDX-10 is designed for 10kV systems with 12/42/75kV insulation level.

Select by accuracy class: Use 0.2 for high-precision metering, 0.5 for control systems, or 3P for protection applications.

Select by rated output: Choose rated output (20-50VA) based on connected burden requirements.

Ordering Information

When ordering the JDX-10 oil-immersed voltage transformer, please specify:

  • Model: JDX-10
  • System voltage: 10kV
  • Accuracy class: 0.2, 0.5, or 3P
  • Rated output: 20, 25, or 50 VA
  • Frequency: 50Hz or 60Hz
  • Installation type: Indoor
  • Quantity

FAQs

Oil-immersed voltage transformer uses transformer oil as insulation medium instead of epoxy resin or silicone rubber. This provides excellent dielectric strength and thermal dissipation for reliable operation in medium-voltage applications.

Three-winding configuration provides separate outputs for different applications: 0.2 class for metering, 0.5 class for control, and residual winding for protection. This eliminates the need for multiple transformers and ensures comprehensive system coverage.

Three accuracy classes are available: 0.2 for high-precision metering (20VA), 0.5 for control systems (25VA), and 3P for protection applications (50VA). Each winding serves different system requirements.

Oil-immersed transformers require periodic oil level checks and oil quality inspection. The oil may need replacement after extended service. Regular maintenance ensures long-term reliability and accurate measurement performance.

The JDX-10 complies with IEC and GB standards for voltage transformers, ensuring compatibility with international and Chinese standards for medium-voltage measurement applications.

Confirm model (JDX-10), system voltage (10kV), accuracy class (0.2, 0.5, or 3P), rated output (20, 25, or 50VA), frequency (50Hz or 60Hz), installation type (indoor), and quantity.

Inquiry for JDX-10 Indoor Oil-Immersed Single-Phase Voltage Transformer:

Send your project requirements. Our team will reply with technical details and quotation.

Fast response Technical support OEM / ODM