JDZX12-35R 35kV Voltage Transformer Detail View

JDZX12-35R 35kV Indoor Epoxy Cast-Resin Voltage Transformer

JDZX12-35R indoor epoxy cast-resin single-phase voltage transformer for 35kV systems with integrated safety protection features.

  • Integrated protection system provides enhanced safety for personnel and equipment during fault conditions
  • Epoxy cast-resin insulation offers superior arc resistance and fire retardant properties
  • Compact design with built-in safety features eliminates need for external protection devices
  • Solid insulation system prevents oil leakage and environmental contamination risks
  • Wide operating temperature range (-5°C to +50°C) ensures reliable performance in diverse indoor environments
  • Customizable for different countries, regions, and project requirements

Product Overview

The JDZX12-35R voltage transformer is an indoor epoxy cast-resin single-phase measurement device designed for 35kV medium-voltage distribution systems. This advanced voltage transformer features epoxy resin cast insulation technology, providing excellent dielectric strength and maintenance-free operation for reliable performance in indoor environments.

The JDZX12-35R delivers precise voltage measurement for energy metering, voltage monitoring, and relay protection applications with multiple accuracy classes (0.2, 0.5, 1.0, 6P) and flexible winding configurations. Available in two connection types: Y/△ connection (three-winding configuration) and Y/Y/△ connection (four-winding configuration). The epoxy resin cast construction ensures superior insulation performance while providing up to 600VA thermal limit output capacity. Compact design with 68kg weight simplifies installation and reduces structural support requirements.

Product Display

JDZX12-35R 35kV Voltage Transformer Detail View
JDZX12-35R 35kV Voltage Transformer Product Poster
JDZX12-35R 35kV Voltage Transformer Technical Features

Application Position

The JDZX12-35R is installed in indoor switchgear, substations, and distribution networks where reliable single-phase voltage measurement is required. The epoxy resin insulation provides excellent moisture resistance and long-term durability for indoor operation. Three units are typically connected in three-phase configuration with star-connected primary and secondary windings, plus open-delta connected residual voltage winding for ground fault detection.

Main Applications

  • 35kV indoor distribution networks
  • Substations requiring voltage measurement with ground fault detection
  • Industrial facilities with medium-voltage supply
  • Energy metering applications
  • Voltage monitoring and relay protection
  • Indoor power distribution systems

Application Case Studies

Application Scenario 1: Substation Voltage Measurement with Ground Fault Detection
Utilities deploy three JDZX12-35R epoxy cast-resin voltage transformers in 35kV indoor substations for energy metering and ground fault protection. The three-winding configuration with Y/△ connection provides accurate voltage signals for protection relays and metering devices, while the open-delta connected residual voltage winding enables reliable ground fault detection. The epoxy resin insulation ensures reliable performance in indoor environments with 40.5/95/200kV insulation level and maintenance-free operation.

Application Scenario 2: Industrial Medium-Voltage Metering with Enhanced Flexibility
Industrial facilities with 35kV incoming supply require accurate voltage measurement for energy management and protection coordination. The JDZX12-35R offers four-winding configuration (Y/Y/△) with dual secondary outputs, providing enhanced system flexibility and redundancy for critical applications. Multiple accuracy classes (0.2, 0.5, 1.0, 6P) meet different measurement requirements, with 600VA thermal limit output capacity for various burden conditions.

Application Fit

Suitable For

  • Indoor 35kV voltage measurement
  • Substations with ground fault detection requirements
  • Industrial facilities with medium-voltage supply
  • Voltage monitoring applications
  • Relay protection systems
  • Environments requiring maintenance-free operation
  • Outdoor installation applications (use outdoor-rated models)
  • Current measurement applications (use CT instead)
  • High-voltage systems above 40.5kV (use higher voltage class models)
  • Applications requiring three-phase measurement in single unit

Installation Conditions

  • Installation position: Indoor switchgear, substations, or distribution points
  • Ambient temperature: -5°C to +50°C
  • Altitude: ≤ 1000m (standard), higher altitude available on request
  • Insulation: Epoxy resin cast
  • Frequency: 50Hz or 60Hz
  • Connection: Single-phase (three units for three-phase system)
  • Maintenance: Minimal maintenance required (epoxy resin design)

Technical Parameters

The JDZX12-35R series includes indoor epoxy cast-resin single-phase voltage transformers for 35kV systems. Operating temperature -5°C to +50°C, compliant with GB20840.3-2013 and IEC60044-2:2003 standards.

Three-Winding VT Data

JDZX12-35R model with Y/△ connection configuration for basic metering and protection applications.

Rated Voltage
(kV)
Accuracy Class
& Rated Output (VA)
Thermal Limit
Output (VA)
Insulation Level
(kV)
33/√3 : 0.1/√3
35/√3 : 0.1/√3 : 0.1/√3
0.2/6P(3P): 45/100
0.5/6P(3P): 100/100
1.0/6P(3P): 200/100
600 40.5/95/200

Four-Winding VT Data

JDZXW12-35R model with Y/Y/△ connection configuration for dual secondary outputs and enhanced redundancy.

Rated Voltage
(kV)
Accuracy Class
& Rated Output (VA)
Thermal Limit
Output (VA)
Insulation Level
(kV)
35/√3 : 0.1/√3 : 0.1/√3 : 0.1/3 0.2/0.2/6P(3P): 20/20/100
0.2/0.5/6P(3P): 20/30/100
0.5/0.5/6P(3P): 40/40/100
600 (0.2 Class) 40.5/95/200

Installation

Dimension Reference

JDZX12-35R Voltage Transformer Dimension Drawing

Overall dimensions: 815±10mm (height) × 403mm (width) × 280mm (depth). Weight: approximately 68kg. Mounting holes: 4×M6 on base plate.

Wiring Diagram

JDZX12-35R Voltage Transformer Wiring Diagram

Figure 1: Y/△ Connection (Three-Winding) – Primary terminals A, B, C connect to star configuration, secondary outputs a, b, c for metering, da/dn for open-delta ground fault detection.

Figure 2: Y/Y/△ Connection (Four-Winding) – Enhanced configuration with dual secondary winding sets (1a/1b/1c and 2a/2b/2c) plus delta output (da/dn) for maximum flexibility.

Installation Guidelines

  1. Mounting: Secure the transformer to a flat, stable surface using the four mounting holes on the base flange. Ensure the mounting surface can support the 68kg weight.
  2. Clearance: Maintain adequate clearance around the transformer for ventilation and maintenance access. Follow local electrical codes for minimum clearance requirements.
  3. Primary Connection: Connect the primary terminals (A, N) to the 35kV power system using appropriate high-voltage cables and connectors. Ensure proper torque specifications are followed.
  4. Secondary Connection: Connect secondary terminals to metering devices, protection relays, or monitoring equipment according to the wiring diagram. Use shielded cables for secondary circuits to minimize electromagnetic interference.
  5. Grounding: Ensure proper grounding of the transformer base and secondary circuit neutral point for safety and accurate measurement.

Epoxy Resin Features

  • Superior Insulation: Epoxy resin provides excellent dielectric strength with rated insulation level up to 40.5/95/200kV
  • Moisture Resistance: Cast-resin construction prevents moisture ingress, ensuring stable performance in humid environments
  • Mechanical Strength: Epoxy resin housing offers high impact resistance and structural integrity
  • Maintenance-Free: Sealed epoxy design eliminates the need for regular insulation testing or oil maintenance
  • Long Service Life: Epoxy resin insulation resists aging and maintains performance over decades of operation

Standards

  • GB20840.3-2013 (Instrument transformers – Part 3: Inductive voltage transformers)
  • IEC60044-2:2003 (Instrument transformers – Part 2: Inductive voltage transformers)
  • Customer-specific requirements available on request

Selection Guide

When selecting the JDZX12-35R voltage transformer, consider the following factors:

  • Accuracy Class: Choose 0.2 for revenue metering, 0.5 for monitoring applications, 1.0 for general measurement, 6P/3P for protection applications
  • Winding Configuration: Select three-winding (Y/△) for basic metering and protection, or four-winding (Y/Y/△) for dual secondary outputs and enhanced redundancy
  • Burden Requirements: Ensure the rated output matches the connected load (metering devices, relays) to maintain accuracy
  • Environmental Conditions: Verify ambient temperature (-5°C to +50°C) and altitude (≤1000m standard) match your installation environment

Ordering Information

When ordering the JDZX12-35R voltage transformer, please specify:

  • Model: JDZX12-35R (three-winding) or JDZXW12-35R (four-winding)
  • Rated voltage ratio (e.g., 35/√3 / 0.1/√3 kV)
  • Accuracy class and rated output (e.g., 0.2/6P, 45/100VA)
  • Rated frequency (50Hz or 60Hz)
  • Quantity required
  • Any special requirements or custom specifications

FAQs

Epoxy cast-resin transformers use solid epoxy insulation, requiring minimal maintenance (no oil testing or seal inspection). They are suitable for indoor applications with excellent moisture resistance and compact design. Oil-immersed transformers use transformer oil for insulation and cooling, providing superior thermal dissipation but requiring periodic maintenance including oil testing and seal inspection.

Epoxy cast-resin transformers require minimal maintenance. Periodic visual inspection for physical damage or contamination is recommended. Unlike oil-immersed transformers, there is no need for oil testing, seal inspection, or oil replacement. The solid insulation system maintains consistent performance throughout the equipment’s service life.

For revenue metering applications, accuracy class 0.2 is recommended to ensure precise energy measurement. Class 0.5 is suitable for monitoring and general measurement applications. Class 6P(3P) is used for protection applications where accuracy is less critical than reliability.

The thermal limit output represents the maximum burden the transformer can supply without exceeding temperature rise limits. For JDZX12-35R, the thermal limit output is 600VA. This ensures reliable operation even under heavy load conditions in indoor environments.

Standard ratios include 35/√3 / 0.1/√3 / 0.1/√3. Custom ratios can be manufactured based on specific project requirements. Please contact our technical team for custom specifications and lead times.

With proper installation and normal operating conditions, epoxy cast-resin transformers have service life exceeding 30 years. The solid insulation system does not degrade over time like oil-immersed insulation. Key factors affecting service life include operating temperature, load conditions, and environmental factors.

The JDZX12-35R complies with GB20840.3-2013 (Chinese standard) and IEC61869-3:2011 (international standard) for voltage transformers, ensuring compatibility with both domestic and international high-voltage measurement applications.

Indoor installation provides protection from environmental factors such as UV radiation, extreme temperatures, pollution, and moisture. This extends equipment life and reduces maintenance requirements. Indoor transformers typically have more compact designs optimized for switchgear and control panel integration.