Product Overview
The JDZX16-35W voltage transformer is an outdoor epoxy cast-resin single-phase measurement device engineered for 35kV high-voltage power systems. This advanced voltage transformer features compact design (677mm total height, 53.2kg weight) with outdoor epoxy cast-resin insulation system that eliminates the need for oil maintenance while delivering superior UV resistance, moisture protection, and pollution tolerance for reliable operation in harsh environmental conditions. The JDZX16-35W represents the next generation of maintenance-free voltage measurement solutions for outdoor substations and transmission networks.
The JDZX16-35W delivers flexible voltage measurement solutions with multiple winding configurations: three-winding (Y/△ connection) for basic metering and protection, or four-winding (Y/Y/△ connection) for dual secondary outputs with enhanced redundancy. Multiple accuracy classes (0.2, 0.5, 1.0) accommodate precision metering to general measurement requirements, with thermal limit output up to 600VA ensuring reliable performance under heavy burden conditions. The compact design facilitates installation in space-constrained outdoor substations while the epoxy cast-resin construction provides maintenance-free operation throughout the equipment’s service life. Wide operating temperature range (-5°C to +50°C) and compliance with GB20840.3-2013 and IEC60044-2:2003 standards ensure reliable performance across diverse applications.
Product Display



Application Position
The JDZX16-35W is installed in outdoor substations, high-voltage switching stations, and transmission networks where reliable voltage measurement is required under harsh environmental conditions. The outdoor epoxy cast-resin insulation system provides excellent UV resistance, moisture protection, and pollution tolerance for long-term outdoor operation without maintenance. The compact design (677mm height, 53.2kg weight) allows installation in space-constrained locations where larger transformers cannot fit. Typical installation includes concrete foundation mounting with proper grounding and clearance for maintenance access. The epoxy construction withstands UV radiation, moisture, and industrial pollution without degradation, making it ideal for coastal areas, industrial zones, and regions with extreme weather conditions.
Main Applications
- 35kV outdoor substations and switching stations
- High-voltage transmission line voltage monitoring
- Industrial power distribution systems with outdoor switchgear
- Renewable energy substations (wind farms, solar plants)
- Rural electrification projects with outdoor distribution
- Utility networks requiring maintenance-free voltage measurement
- Harsh environment applications (coastal areas, industrial pollution)
- Space-constrained installations requiring compact design
Application Case Studies
Application Scenario 1: Compact Outdoor Substation Voltage Measurement
Utilities deploy JDZX16-35W epoxy cast-resin voltage transformers in 35kV outdoor substations where space constraints and maintenance-free operation are critical. The compact design (677mm height, 53.2kg weight) allows installation on existing foundations without structural modifications, reducing installation costs by 40% compared to larger transformers. The epoxy cast-resin insulation system eliminates oil testing and seal inspection requirements, reducing annual maintenance costs by 80% compared to oil-immersed transformers. The four-winding configuration (Y/Y/△) provides separate outputs for metering (accuracy class 0.2), protection (6P), and open-delta ground fault detection, ensuring reliable operation under all system conditions while the epoxy construction withstands UV radiation, moisture, and industrial pollution without degradation.
Application Scenario 2: Coastal Substation with High Pollution and Humidity
Coastal substations require voltage transformers that can withstand salt spray, high humidity, and industrial pollution without performance degradation. The JDZX16-35W offers superior environmental protection with epoxy cast-resin insulation that provides complete moisture barrier and pollution resistance. Unlike oil-immersed transformers that require periodic seal inspection and oil testing, the epoxy construction maintains consistent insulation performance throughout the service life without maintenance. The compact design (53.2kg weight) allows installation on lightweight foundations, while the wide operating temperature range (-5°C to +50°C) ensures reliable performance in coastal climates with temperature extremes. The high insulation level (40.5/95/200kV) provides excellent dielectric strength for reliable operation in high-humidity environments.
Application Fit
Suitable For
- Outdoor 35kV voltage measurement applications
- Maintenance-free operation requirements (no oil testing)
- Harsh environment installations (coastal, industrial pollution)
- Space-constrained installations (compact design)
- Applications requiring lightweight transformers (53.2kg)
- UV exposure environments (epoxy resin UV resistance)
- High humidity or moisture-prone locations
- Rural electrification projects with limited maintenance resources
Not Recommended For
- Indoor installation applications (use indoor-rated models like JDZ9-35Q)
- Current measurement applications (use CT instead)
- High-voltage systems above 40.5kV (use higher voltage class models)
- Applications requiring very high thermal capacity (>600VA)
- Extreme cold environments below -5°C (use special low-temperature models)
- Three-phase measurement in single unit (use three separate single-phase units)
Installation Conditions
- Installation position: Outdoor substations, switching stations, or transmission networks
- Ambient temperature: -5°C to +50°C
- Altitude: ≤ 1000m (standard), higher altitude available on request
- Insulation: Epoxy cast-resin (maintenance-free)
- Frequency: 50Hz or 60Hz
- Phase configuration: Single-phase (use three units for three-phase systems)
- Pollution grade: Grade II-IV (suitable for coastal and industrial areas)
- UV resistance: Excellent (epoxy resin provides UV protection)
- Moisture protection: Complete moisture barrier (epoxy construction)
- Maintenance: Minimal (no oil testing or seal inspection required)
Technical Parameters
The JDZX16-35W series includes outdoor epoxy cast-resin single-phase voltage transformers for 35kV systems. Operating temperature -5°C to +50°C, compliant with GB20840.3-2013 and IEC60044-2:2003 standards.
| Model | Rated Voltage (kV) |
Accuracy Class & Rated Output (VA) |
Thermal Limit Output (VA) |
Insulation Level (kV) |
|---|---|---|---|---|
| JDZX16-35W (Three-winding) |
33/√3 / 0.11/√3 or 35/√3 / 0.1/√3 / 0.1/√3 |
0.2/6P(3P): 45/100 0.5/6P(3P): 100/100 1.0/6P(3P): 200/100 |
600 | 40.5/95/200 |
| JDZX16-35W (Four-winding) |
35/√3 / 0.1/√3 / 0.1/√3 / 0.1/3 | 0.2/0.2/6P(3P): 20/20/100 0.2/0.5/6P(3P): 20/30/100 0.5/0.5/6P(3P): 40/40/100 |
600 | 40.5/95/200 |
Note 1: Three-winding configuration (35/√3 / 0.1/√3 / 0.1/√3) – Standard Y/△ connection for metering, protection, and ground fault detection.
Note 2: Four-winding configuration (35/√3 / 0.1/√3 / 0.1/√3 / 0.1/3) – Enhanced configuration with dual secondary outputs for separate metering and protection circuits.
Note 3: Rated output and its relative accuracy class only one alternative per transformer.
Note 4: If user’s data go beyond the above-mentioned scopes, they may be subject to an agreement between manufacturer and purchaser.
Installation
Dimension Reference

Overall dimensions: Height 677mm, base width 350mm, base depth 310mm. Weight: approximately 53.2kg. Mounting: 4×M10 mounting holes on base plate. Clearance: Minimum 500mm around transformer for maintenance access. Top terminal: M10 bolt. Secondary outlet: Bottom outlet hole for cable connection.
Wiring Diagram

Three-winding: Primary terminals A, B, C connect to star configuration with neutral N. Secondary outputs a, b, c for metering (star connection), da/dn for open-delta ground fault detection. Four-winding: Additional secondary outputs 2a, 2b, 2c with neutral 2n for separate protection circuit.
Installation Guidelines
- Foundation: Install on a level concrete foundation capable of supporting 53.2kg weight. Foundation should be 100mm above ground level to prevent water accumulation. Use anchor bolts (M10) secured into foundation with minimum 150mm embedment depth.
- Grounding: Connect the grounding terminal to the substation grounding grid using copper conductor with minimum 35mm² cross-section. Ensure grounding resistance is less than 4 ohms.
- Clearance: Maintain minimum 500mm clearance on all sides for maintenance access and ventilation. Ensure adequate clearance from live parts according to local electrical codes (typically 400mm for 35kV).
- Primary Connection: Connect primary terminals (A, B, C) to the 35kV power system using appropriate high-voltage conductors or busbars. Ensure proper phase sequence and torque specifications (typically 40 N·m for M10 bolts).
- Secondary Connection: Connect secondary terminals to metering devices, protection relays, or monitoring equipment according to the wiring diagram. Use shielded cables for secondary circuits to minimize electromagnetic interference. Ensure proper termination and labeling.
- Inspection: Before energizing, inspect the epoxy cast-resin body for any physical damage or contamination. Clean the surface if necessary to maintain insulation performance.
- Commissioning Tests: Perform insulation resistance test (minimum 1000 MΩ at 20°C), turns ratio test, and polarity test before energizing. Verify all connections are tight and properly torqued.
Epoxy Cast-Resin Insulation Features
- Maintenance-Free Operation: Epoxy cast-resin construction eliminates the need for oil testing, seal inspection, and oil replacement. The solid insulation system maintains consistent performance throughout the equipment’s service life without periodic maintenance.
- Superior Moisture Protection: Epoxy resin provides complete moisture barrier, preventing water ingress and insulation degradation. Unlike oil-immersed transformers that require seal inspection, the epoxy construction maintains moisture resistance without maintenance.
- Excellent UV Resistance: Epoxy cast-resin insulation provides superior UV resistance, preventing degradation from solar radiation. The material maintains mechanical strength and dielectric properties even after years of outdoor exposure.
- Pollution Tolerance: Epoxy resin surface provides excellent pollution resistance, preventing contamination buildup and flashover. The smooth surface facilitates self-cleaning during rain, maintaining insulation performance in industrial and coastal environments.
- Compact Design: Epoxy cast-resin construction allows more compact design compared to oil-immersed transformers. The JDZX16-35W achieves 677mm total height and 53.2kg weight, facilitating installation in space-constrained locations.
Standards
- GB20840.3-2013 (Instrument transformers – Part 3: Inductive voltage transformers)
- IEC60044-2:2003 (Instrument transformers – Part 2: Inductive voltage transformers)
- Customer-specific requirements available on request
Selection Guide
When selecting the JDZX16-35W voltage transformer, consider the following factors:
- Winding Configuration: Choose three-winding (Y/△) for basic metering and protection, or four-winding (Y/Y/△) for dual secondary outputs and enhanced redundancy
- Accuracy Class: Choose 0.2 for revenue metering, 0.5 for monitoring applications, 1.0 for general measurement, 6P(3P) for protection applications
- Burden Requirements: Ensure the rated output matches the connected load (metering devices, relays) to maintain accuracy. Thermal limit output is 600VA for both configurations
- Environmental Conditions: Verify ambient temperature (-5°C to +50°C), altitude (≤1000m standard), and pollution grade match your installation environment
- Maintenance Capability: Epoxy cast-resin transformers require minimal maintenance (no oil testing). Ensure this aligns with your maintenance strategy
- Space Constraints: Compact design (677mm height, 53.2kg weight) allows installation in space-constrained locations
- Weight Requirements: Lightweight design (53.2kg) allows installation on lightweight foundations without structural modifications
Ordering Information
When ordering the JDZX16-35W voltage transformer, please specify:
- Model: JDZX16-35W
- Winding configuration: Three-winding or Four-winding
- Rated voltage ratio (e.g., 35/√3 / 0.1/√3 / 0.1/√3 kV)
- Accuracy class and rated output (e.g., 0.2/6P(3P), 45/100VA)
- Rated frequency (50Hz or 60Hz)
- Quantity required
- Any special requirements or custom specifications