JLSZV-35 Indoor Epoxy Resin Combined Transformer 35kV CT PT

JLSZV-35 Indoor Epoxy Resin Combined Transformer 35kV CT PT

JLSZV-35 indoor epoxy resin combined transformer for 35kV distribution networks, integrating CT and PT functions in one three-phase two-component unit.

  • Indoor three-phase two-component CT PT metering unit
  • Suitable for 35kV distribution systems (40.5kV class)
  • Wide CT primary current range: 5A to 1200A
  • Epoxy cast-resin insulation for indoor environments
  • Operating temperature: -25°C to +55°C
  • Compliant with GB20840.4-2015 and IEC 61869.4:2013

Product Overview

The JLSZV-35 combined transformer is an indoor epoxy resin cast three-phase two-component measurement device designed for 35kV medium-voltage distribution systems. This CT PT combined transformer integrates voltage transformer (PT) and current transformer (CT) functions in a single epoxy cast-resin assembly, providing accurate current and voltage signals for energy metering and protection applications.

As a 35kV combined transformer with 40.5kV class insulation, the JLSZV-35 is suitable for indoor switchgear, compact substations, and industrial distribution systems requiring high-accuracy metering. The epoxy cast-resin metering transformer design ensures excellent insulation performance, moisture resistance, and long-term reliability in demanding indoor environments.

Product Display

JLSZV-35 Product Display - Technical Specifications
JLSZV-35 Product Display - Key Functions

JLSZV-35 Product Display

[Product images to be added]

Application Position

The JLSZV-35 is installed indoors in switchgear compartments, metering cabinets, or compact substations. The primary terminals connect to the three-phase 35kV circuit, while the secondary terminal box supplies voltage and current signals to energy meters, protection relays, and monitoring instruments. The indoor epoxy resin transformer design provides superior insulation performance without requiring additional environmental protection.

Main Applications

  • 35kV indoor switchgear metering applications using JLSZV-35 combined transformer
  • Compact substations requiring integrated CT PT measurement
  • Industrial distribution systems with 35kV incoming supply
  • High-accuracy revenue metering for utility billing with 0.2S accuracy class
  • Protection relay applications requiring precise current signals
  • Indoor metering cabinets with space constraints
  • Projects requiring GB20840.4-2015 and IEC 61869.4 compliance

Application Case Studies

Application Scenario 1: Indoor Switchgear Metering
Utilities deploy the JLSZV-35 combined transformer in 35kV indoor switchgear for revenue billing and load monitoring. The compact three-phase two-component design integrates CT and PT functions in one unit, reducing installation space and wiring complexity. The epoxy cast-resin insulation ensures reliable performance in indoor environments with controlled temperature and humidity. This indoor metering transformer 35kV solution provides accurate measurement for utility billing applications.

Application Scenario 2: Industrial High-Voltage Metering
Industrial facilities with 35kV incoming supply require accurate energy measurement for cost allocation and load monitoring. The JLSZV-35 combined transformer supports wide current range from 5A to 1200A, accommodating various load conditions. The 0.2S accuracy class provides high-precision metering for billing applications, while the epoxy resin construction ensures long-term stability without maintenance. This CT PT combined transformer 35kV delivers reliable performance for industrial metering needs.

Application Fit

Suitable For

  • Indoor 35kV metering points requiring integrated CT and PT signals
  • Switchgear compartments with space constraints
  • Compact substations requiring high-accuracy metering
  • Industrial facilities with 35kV incoming supply
  • Applications requiring wide current range from 5A to 1200A
  • Projects requiring GB20840.4-2015 and IEC 61869.4 compliance
  • Indoor environments with controlled temperature and humidity
  • Outdoor installation applications requiring weather protection
  • Pole-mounted or elevated installation applications
  • Applications requiring separate CT and PT bodies
  • Protection-only applications where metering accuracy is not required
  • Environments with extreme temperature variations beyond -25°C to +55°C

Installation Conditions

  • Installation position: Indoor switchgear, metering cabinets, or compact substations
  • Ambient temperature: -25°C to +55°C
  • Maximum altitude: ≤ 4500m (no derating required)
  • Environment: Indoor with controlled temperature and humidity
  • Grounding: Connect grounding terminal per local electrical codes and metering standards
  • Maintenance: Epoxy resin construction requires minimal maintenance in indoor environments

Technical Parameters

The JLSZV-35 is an indoor epoxy cast-resin combined transformer for 35kV systems with three-phase two-component design. Operating temperature -25°C to +55°C, altitude up to 4500m, compliant with GB20840.4-2015 and IEC 61869.4:2013. Features 40.5kV class insulation and wide current range from 5A to 1200A.

Voltage Transformer Data

Rated Voltage
Ratio (kV)
Rated Insulation
Level (kV)
Accuracy Class
/ Rated Output
Max
Output
35/0.1 40.5/95/200 0.2 (2×30VA), 0.5 (2×60VA) 600 VA
33/0.1 40.5/95/200 0.2 (2×30VA), 0.5 (2×60VA) 600 VA

Current Transformer Data

Rated Primary
Current (A)
Rated Insulation
Level (kV)
Accuracy Class
/ Rated Output
1s Thermal
Current
Dynamic
Current
5 – 600 40.5/95/185 0.2S (2×15VA) 80 × In 200 × In
750 – 800 40.5/95/185 0.2S (2×15VA) 80 kA 200 kA
1000 – 1200 40.5/95/185 0.2S (2×20VA) 100 kA 250 kA

Installation & Dimensions

Dimension Reference

JLSZV-35 Installation Diagram

View Key
Dimensions
Application
Note
Side View Length 1523±3mm; Width 636±5mm; Height 815±5mm Four bushings with terminals
End View Width 840mm Depth profile with mounting base
Top View Length 1400±2mm; Width 1060±2mm Terminal layout: AP1, AP2, CP1, CP2

Wiring Diagram

JLSZV-35 Wiring Diagram

[Wiring diagram to be added]

Installation Guidelines

  • Confirm AP1/AP2 and CP1/CP2 terminal sequence before commissioning
  • CT secondary circuits must not be open-circuited during operation
  • PT secondary terminals provide voltage input to meters and protection relays
  • CT secondary terminals provide current input to energy meters and protection devices
  • Grounding and wiring should follow the approved project wiring diagram
  • Ensure adequate ventilation in indoor installation environment

Standards Compliance

The JLSZV-35 combined transformer complies with GB20840.4-2015 and IEC 61869.4:2013 for combined instrument transformers. For international projects, compliance should be aligned with applicable IEC instrument transformer standards and local utility metering rules.

Selection Guide

Select by system voltage: Use JLSZV-35 for 35kV systems (40.5kV class insulation).

Select by current ratio: Determine CT primary current according to actual load current. Supports 5A to 1200A primary current range in three segments.

Select by metering accuracy: Use 0.2S CT accuracy for high-accuracy energy metering. PT accuracy classes include 0.2 and 0.5.

Select by voltage ratio: Choose 35/0.1kV or 33/0.1kV according to network voltage and meter input requirement.

Ordering Information

When ordering the JLSZV-35 combined transformer, please specify:

  • Model: JLSZV-35
  • System voltage: 35kV or 33kV
  • PT ratio: 35/0.1kV or 33/0.1kV
  • CT primary current: 5A to 1200A (specify exact value)
  • CT secondary current: 5A
  • CT accuracy class: 0.2S
  • PT accuracy class: 0.2 or 0.5
  • Installation type: Indoor
  • Quantity

FAQs

The JLSZV-35 combined transformer is an indoor epoxy resin combined transformer used for 35kV medium-voltage metering applications. It integrates CT and PT functions in one unit, providing accurate current and voltage signals for energy metering and protection in indoor switchgear and substations. This three-phase two-component transformer design reduces installation complexity while maintaining high accuracy.

JLSZV-35 is designed for indoor installation with epoxy cast-resin insulation, while JLSZW-35 is designed for outdoor installation with weatherproof enclosure. JLSZV-35 supports wider current range (5-1200A) and has broader temperature range (-25°C to +55°C).

The JLSZV-35 supports CT primary current from 5A to 1200A in three segments: 5-600A, 750-800A, and 1000-1200A. This wide range accommodates various load conditions without requiring multiple metering units.

Use 40.5kV class for the 35kV version. The insulation level is 40.5/95/200kV, meeting international standards for 35kV systems.

The JLSZV-35 combined transformer complies with GB20840.4-2015 and IEC 61869.4:2013 for combined instrument transformers, ensuring compatibility with international requirements and specifications. This GB20840.4-2015 transformer meets strict accuracy and performance standards for indoor metering applications.

CT accuracy class is 0.2S for high-precision metering. PT accuracy classes include 0.2 (2×30VA) and 0.5 (2×60VA). The maximum output is 600VA.

No, the JLSZV-35 is designed for indoor installation only. For outdoor applications, use the JLSZW-35 model which has weatherproof enclosure and UV-resistant construction.

Confirm system voltage (35kV or 33kV), PT ratio, CT primary current, CT secondary current, accuracy classes, rated burden, installation type (indoor), and quantity.