Product Overview
JLSZV(Y)9-6/10W is an outdoor stainless steel floor-mounted combined transformer with observation windows for 6kV and 10kV medium-voltage distribution systems. It integrates current transformer (CT) and voltage transformer (PT/VT) functions in a robust stainless steel enclosure with double-door design, providing reliable current and voltage signals for high-voltage energy metering with enhanced visibility and accessibility.
This product is suitable for 6kV and 10kV three-phase AC distribution networks. It is commonly used in substations, industrial facilities, and distribution points requiring floor-mounted installation with internal monitoring capability. The stainless steel enclosure with observation windows provides superior protection while allowing visual inspection of internal components without opening doors.
Product Display



[Product images to be added]
Application Position
JLSZV(Y)9-6/10W is installed at ground level in substations, industrial yards, or distribution points. The stainless steel floor-mounted design with observation windows provides enhanced durability and allows visual monitoring of internal meters and components. The primary terminals connect to the three-phase medium-voltage circuit, while the secondary terminal box supplies voltage and current signals to active energy meters, reactive energy meters, and monitoring instruments.
Main Applications
- 6kV and 10kV outdoor distribution networks requiring floor-mounted metering with visual monitoring
- Substations and industrial facilities requiring stainless steel enclosure with observation capability
- Applications requiring dual wiring configurations (3-phase and 3-phase 4-wire)
- Coastal areas and harsh environments requiring enhanced corrosion protection
- Active and reactive energy measurement for utility revenue billing
- Applications requiring wide current range from 7.5A to 600A
- Projects requiring State Grid standard compliance (GB17201-2006)
Application Case Studies
Application Scenario 1: Substation Yard Metering with Visual Monitoring
Utilities deploy floor-mounted combined transformers in substation yards for revenue billing and load monitoring. The observation windows allow operators to visually inspect internal meters and components without opening doors, reducing maintenance time and improving safety. The stainless steel enclosure provides superior corrosion resistance in outdoor environments.
Application Scenario 2: Industrial Facility with Flexible Wiring
Industrial facilities with 6kV or 10kV incoming supply require accurate energy measurement with flexible wiring options. The JLSZV(Y)9-6/10W supports both 3-phase and 3-phase 4-wire configurations, accommodating different metering requirements. The observation windows enable quick visual verification of meter readings during routine inspections.
Application Fit
Suitable For
- Outdoor 6kV and 10kV metering points requiring floor-mounted installation with visual monitoring
- Substations and industrial facilities requiring stainless steel enclosure with observation windows
- Applications requiring dual wiring configurations (3-phase and 3-phase 4-wire)
- Coastal areas and harsh environments requiring enhanced corrosion protection
- Projects requiring wide current range from 7.5A to 600A
- Applications requiring State Grid standard compliance (GB17201-2006)
- Distribution points requiring integrated CT and PT functions with internal monitoring capability
Not Recommended For
- Pole-mounted or elevated installation applications
- Indoor-only compact switchgear applications
- Applications requiring separate CT and PT bodies instead of integrated design
- Protection-only CT applications where metering accuracy is not required
- Applications with space constraints requiring smaller footprint equipment
Installation Conditions
- Installation position: Ground-level installation in substations, industrial yards, or distribution points
- Ambient temperature: -15°C to +55°C
- Maximum altitude: ≤ 4500m (no derating required)
- Enclosure material: Stainless steel with observation windows for visual monitoring
- Grounding: Connect grounding terminal per local electrical codes and metering standards
- Maintenance: Observation windows allow visual inspection without opening doors
Technical Parameters
The JLSZV(Y)9-6/10W is an outdoor stainless steel floor-mounted combined transformer with observation windows for 6kV and 10kV systems. Operating temperature -15°C to +55°C, altitude up to 4500m, compliant with GB17201-2006. Features stainless steel enclosure with observation windows, dual wiring configurations, and wide current range from 7.5A to 600A.
Voltage Transformer Data
| Model | Rated Voltage Ratio |
Accuracy Class / Rated Output |
Limit Output |
Rated Insulation Level (kV) |
|---|---|---|---|---|
| JLSZV(F)-6W | 6000/100 | 0.2 (2×20VA), 0.5 (2×50VA) | 2×400 VA | 7.2/32/60 |
| JLSZV(F)-10W | 10000/100 | 1.0 (2×80VA), 3.0 (2×200VA) | 2×400 VA | 12/42/75 |
Current Transformer Data
| Rated Primary Current (A) |
Accuracy Class / Rated Output |
1s Thermal Current (kA) |
Rated Dynamic Current (kA) |
|---|---|---|---|
| 7.5 – 15 | 0.2S (10VA), 0.5S (10VA), 0.5 (15VA) | 1.0 | 2.5 |
| 20 – 50 | 0.2S (10VA), 0.5S (10VA), 0.5 (15VA) | 2.5 | 6.3 |
| 75 – 100 | 0.2S (10VA), 0.5S (10VA), 0.5 (15VA) | 6.3 | 16 |
| 150 – 200 | 0.2S (10VA), 0.5S (10VA), 0.5 (15VA) | 16 | 40 |
| 300 – 400 | 0.2S (10VA), 0.5S (10VA), 0.5 (15VA) | 40 | 100 |
| 500 – 600 | 0.2S (10VA), 0.5S (10VA), 0.5 (15VA) | 60 | 150 |
Installation & Dimensions
Dimension Reference

| View | Key Dimensions |
Application Note |
|---|---|---|
| Front View | Width 1160mm (base 1020mm); Height 1380mm | Double-door design with observation windows |
| Side View | Width 1360mm | Stainless steel enclosure with ventilation |
| Bottom View | Footprint 1160mm × 1160mm | Mounting holes for floor installation |
Wiring Diagram

[Wiring diagram to be added]
Installation Guidelines
- Confirm AP1/AP2, BP1/BP2 and CP1/CP2 terminal sequence before commissioning
- CT secondary circuits must not be open-circuited during operation
- PT secondary terminals provide voltage input to meters and monitoring devices
- CT secondary terminals provide current input to active and reactive energy meters
- Grounding and meter box wiring should follow the approved project wiring diagram
- Stainless steel enclosure must be properly grounded for safety
- Supports both 3-phase and 3-phase 4-wire wiring configurations
Standards Compliance
Compliant with GB17201-2006 for combined transformer metering boxes. For international projects, compliance should be aligned with applicable IEC instrument transformer standards and local utility metering rules.
Selection Guide
Select by system voltage: Use JLSZV(Y)9-6W for 6kV systems (7.2kV class) and JLSZV(Y)9-10W for 10kV systems (12kV class).
Select by current ratio: Determine CT primary current according to actual load current. Supports 7.5A to 600A primary current range in multiple segments.
Select by metering accuracy: Use 0.2S CT accuracy for higher-accuracy energy metering. Use 0.5S or 0.5 according to metering specification.
Select by wiring configuration: Choose 3-phase or 3-phase 4-wire configuration according to network requirements.
Select by voltage ratio: Choose 6000/100 or 10000/100 according to network voltage and meter input requirement.
Ordering Information
When ordering, please specify:
- Model: JLSZV(Y)9-6W or JLSZV(Y)9-10W
- System voltage: 6kV or 10kV
- PT ratio: 6000/100 or 10000/100
- CT primary current: 7.5A to 600A (specify exact value)
- CT secondary current: 5A
- CT accuracy class: 0.2S, 0.5S, or 0.5
- PT accuracy class: 0.2, 0.5, 1.0, or 3.0
- Wiring configuration: 3-phase or 3-phase 4-wire
- Quantity