Product Overview
The ZW32-12G is a three-phase 12kV, 50Hz outdoor vacuum circuit breaker for urban and rural overhead distribution networks. It interrupts load, overload and short-circuit currents, and its integrated isolating switch (G) adds a visible break point for safe maintenance isolation and frequent operation. A spring operating mechanism (T) supports manual and electric operation, and pairing the unit with a controller forms an automatic recloser with remote control, measurement, signalling and fault isolation. The compact, maintenance-free, fire- and explosion-free construction suits harsh outdoor duty from -40 to +40 degC and altitudes up to 3000 m.
Product Display



Model Designation

Model format: ZW32-12G T 630-20 S/D
- ZW: Outdoor Vacuum Circuit Breaker
- 32: Design Sequence Number
- 12: Rated Voltage (kV)
- G: With Isolating (Disconnector) Switch
- T: Spring Operating Mechanism
- 630: Rated Current (A)
- 20: Rated Short-Circuit Breaking Current (kA)
- S / D: Manual / Electric Operation
Service Conditions
- Ambient Temperature: -40 degC to +40 degC
- Altitude:
- Wind Pressure:
- Air Pollution Degree:
- Ice Cover Thickness:
- Installation Site: No fire, explosion, chemical corrosion or severe vibration
Construction
Each phase uses a vacuum interrupter with outdoor-grade insulation mounted on a hot-dip galvanised common frame, driven by a spring mechanism that supports both automatic and manual operation.
The built-in isolating switch gives a clear visible break, while an overcurrent release (5 A, +/-10%) and control/auxiliary circuits rated DC220/AC220 with 2000 V power-frequency withstand enable intelligent protection and remote automation on 10kV overhead lines.
Technical Data
| Item | Unit | Value |
|---|---|---|
| Rated voltage | kV | 12 |
| Rated frequency | Hz | 50 |
| Rated current | A | 630 |
| Rated short-circuit breaking current | kA | 12.5 / 16 / 20 |
| Rated short-circuit making current (peak) | kA | 50 |
| Rated peak withstand current | kA | 50 |
| Rated short-time withstand current (4 s) | kA | 20 |
| 1 min power-frequency withstand voltage | kV | Dry 42 (phase-to-phase/earth), 48 (across open contacts); Wet 34 |
| Lightning impulse withstand voltage (peak) | kV | 75 (phase-to-phase/earth), 85 (across open contacts) |
| Rated operating sequence | – | O-0.3s-CO-180s-CO |
| Closing / opening time | ms | 25~50 / 15~50 |
| Number of rated short-circuit breaking operations | times | 30 |
| Mechanical life | times | 10000 |
| Control & auxiliary circuit 1 min power-frequency withstand | V | 2000 |
| Rated operating / auxiliary circuit voltage | V | DC220 / AC220 |
| Overcurrent release rated current / accuracy | A / % | 5 / +/-10 |
Standards
The ZW32-12G is designed and type-tested to IEC 62271-100 and GB 1984 for high-voltage alternating-current circuit-breakers, covering insulation level, temperature rise, short-circuit making and breaking capacity, and mechanical endurance.
Installation & Dimensions
Installation Diagram

The ZW32-12G is designed for standard pole-mounted outdoor installation on a hot-dip galvanised frame, with the isolating switch operating links and mechanism accessible for manual operation. Adequate clearance must be maintained around the unit for safe switching and maintenance, and all primary and secondary connections must comply with local utility standards. The certified outline and mounting dimension drawing is supplied with each unit.
| Dimension | Value (mm) |
|---|---|
| Total height | 760 |
| Total width (incl. bushings) | 990 |
| Base / frame width | 920 |
| Phase spacing (adjacent poles) | 340 |
| Overall depth (side view) | 790 |
| Mounting hole span (W x D) | 460 x 225 |
| Bushing flange width | 160 |
| Insulator mounting span | 360 |
| Pole-mounting bolt holes | 4 x 13 |