Product Overview
The FZN21-40.5 indoor high-voltage AC vacuum load break switch and the FZRN21-40.5D switch-fuse combination unit are built for 35 kV box-type substations in networks of 40.5 kV at 50 Hz, and either unit can also be used as a standalone switching unit. The load break switch makes and breaks load and overload current at 1250 A and needs no maintenance between services; in the combination unit the series striker-type fuse clears short-circuit current at 20 kA. The vacuum chamber carries current only at the instant of closing and opening, which is what allows the switch to be offered as a maintenance-free unit with a mechanical life of 10000 operations.
Product Display


Model Designation

Model format: FZRN21-40.5D/50-20 (combination unit) and FZN21-40.5 (load break switch, 1250 A)
- F: load break switch; Z: vacuum; R: with fuse; N: indoor
- 21: design sequence number
- 40.5: rated voltage, kV
- D: with earthing switch
- 50: rated current of the combination unit and of its fuse, A
- 20: rated short-circuit breaking current, kA
- Without the R, FZN21-40.5 describes the load break switch on its own, rated 1250 A
Service Conditions
- Ambient temperature: +40 °C upper, -25 °C lower
- Altitude: not more than 1000 m
- Relative humidity: daily average not more than 95%, monthly average not more than 90%
- Seismic intensity: not more than 8 degrees
- Site condition: no fire, explosion hazard, chemical corrosion or violent vibration
- Pollution level: II
Construction
The three poles stand on a common steel frame: the spring operating mechanism drives the disconnect blade and the earthing blade through the insulating pull rod, the vacuum arc extinction chamber interrupts the circuit, and the operating panel at the front shows the position of each. The disconnect blade gives a visible isolation gap and the earthing blade bonds the de-energised side before maintenance.
The vacuum chamber carries current only at the instant of closing and opening, which is what allows the switch to be offered as a maintenance-free unit with a mechanical life of 10000 operations. The striker of the series fuse acts on the release device, so a blown fuse is reported at the switch instead of being left to protection alone, and the fuse compartment is reached only after the circuit is isolated and earthed.
Technical Data
| No. | Item | Unit | Combined unit FZRN21-40.5D | Load break switch FZN21-40.5 |
|---|---|---|---|---|
| 1 | Rated voltage | kV | 40.5 | 40.5 |
| 2 | Rated frequency | Hz | 50 | 50 |
| 3 | Rated short-time withstand current (4 s) | kA | 16 | 16 |
| 4 | Rated current | A | 50 | 1250 |
| 5 | Rated breaking current of active load | A | / | 1250 |
| 6 | Rated closed-loop breaking current | A | / | 1250 |
| 7 | Rated peak withstand current | kA | / | 40 |
| 8 | Rated short-circuit breaking current | kA | 20 | / |
| 9 | Rated cable charging current | A | / | 21 |
| 10 | 1 min power-frequency withstand voltage (vacuum gap, phase-to-phase and phase-to-earth / across the isolation gap) | kV | 95/110 | 95/110 |
| 11 | Lightning impulse withstand voltage (same arrangement) | kV | 185/215 | 185/215 |
| 12 | 1 min power-frequency withstand voltage of control and auxiliary circuits | kV | 2 | 2 |
| 13 | Mechanical life | operations | 10000 | 10000 |
| 14 | Permissible wear of the vacuum chamber contacts | mm | 3 | 3 |
| 15 | Manual operating torque | N·m | Not more than 250 | Not more than 250 |
| 16 | Contact gap | mm | 17±1 | 17±1 |
| 17 | Contact over-travel | mm | 5±1 | 5±1 |
| 18 | Average closing speed | m/s | 0.6±0.2 | 0.6±0.2 |
| 19 | Average opening speed | m/s | 1.5±0.2 | 1.5±0.2 |
| 20 | Opening and closing inconsistency of the three poles | ms | ≤2 | ≤2 |
| 21 | Closing bounce time of the contacts | ms | ≤3 | ≤3 |
| 22 | Clearance between live parts and to earth | mm | ≥300 | ≥300 |
| 23 | Main circuit resistance (excluding the fuse) | μΩ | Not more than 150 | Not more than 150 |
Standards
The source page does not quote a standard number for this switch. The usual references for indoor high-voltage load break switches are IEC 62271-102 / IEC 60265-1 and GB/T 3804; confirm the applicable edition with the factory when ordering.
Installation & Dimensions
Installation Diagram

The unit is bolted to the cubicle frame through six 17 by 22 mm slots. Before energisation, check the closed, open and earthed positions and the interlocks on all three poles, fit the specified striker-type fuse with its striker engaging the release device, and measure the main circuit resistance and the clearances.
| View / dimension | Value (mm) |
|---|---|
| Front view overall width | 1060 (1015 between outer frames) |
| Pole spacing | 410 ± 2, marked twice |
| Front view vertical steps | 99 / 285 / 400 / 450 |
| Mounting slots | 6 × 17 × 22 |
| Side view over top | 1065 |
| Side view overall height | 1610 (680 at base) |
| Terminals | lower 4 × 12.5 holes, upper 2 × 12.5 holes |