FZW28Z-12 Outdoor Vacuum Sectionalizing Load Break Switch - featured

FZW28Z-12 Outdoor Vacuum Sectionalizing Load Break Switch

FZW28Z-12: 12kV Vacuum Sectionalizing Switch

  • 12 kV 50 Hz pole-mounted vacuum sectionalizing switch
  • 630 A rating with 20 kA short-circuit breaking capacity
  • Toshiba VSP5-12 unit, SF6 insulated, zero gas leakage
  • Auto detection and isolation of ground and phase faults
  • Aviation plugs for controller and remote operation
  • 40 to +40 degC service, altitude up to 3000 m

Product Overview

The FZW28Z-12 (FFK) is a 12kV, 50Hz outdoor pole-mounted vacuum sectionalizing load break switch with both manual and electric operation. Its switch body adopts the imported Toshiba (Japan) VSP5-12 maintenance-free load-switch unit, using vacuum arc extinguishing with SF6 gas insulation. Combining fault detection, protection, control and communication, it is installed on 10kV distribution lines to automatically cancel single-phase-to-ground faults and to isolate phase-to-phase short-circuit faults. It is applied at the T-connection or at the user end of 10kV overhead feeders; a compact spring mechanism and aviation-plug secondary connections allow straightforward combination with an intelligent controller for automated distribution and remote operation.

Product Display

FZW28Z-12 Outdoor Vacuum Sectionalizing Load Break Switch - display

FZW28Z-12 Outdoor Vacuum Sectionalizing Load Break Switch - display

FZW28Z-12 Outdoor Vacuum Sectionalizing Load Break Switch - poster_display

Model Designation

FZW28Z-12 Outdoor Vacuum Sectionalizing Load Break Switch - model

Model format: FZW28Z-12/630-20

  • FZW: Outdoor Vacuum Load Switch
  • 28: Design Sequence Number
  • Z: Spring Operating Mechanism
  • 12: Rated Voltage (kV)
  • 630: Rated Current (A)
  • 20: Rated Short-Circuit Breaking Current (kA)

Service Conditions

  • Ambient Temperature: -40 degC to +40 degC
  • Altitude:
  • Relative Humidity: Daily average
  • Wind Pressure:
  • Neutral Earthing: Solidly earthed, earthed via arc-suppression coil, or earthed via low resistance
  • Installation Environment: Outdoor, no explosive or severely corrosive gas, no frequent severe vibration

Construction

The FZW28Z-12 integrates a vacuum-interrupter load-switch unit (imported Toshiba VSP5-12) inside a sealed, SF6-insulated enclosure, giving maintenance-free operation with no gas leakage and full isolation from the outdoor environment.

A miniaturized spring operating mechanism with manual and electric options provides reliable 10,000-operation life, while aviation plugs bring the secondary control, sensing and communication circuits to an external intelligent controller; the unit is designed for quick pole mounting with standard brackets for repeated sectionalizing and fault-isolation duty.

Technical Data

Item Unit Value
Rated voltage kV 12
Rated frequency Hz 50
Rated current A 630
Rated short-circuit breaking current kA 20
Rated short-time withstand current (4 s) kA 12.5 / 16 / 20
Rated short-circuit making current (peak) kA 31.5 / 40 / 50
1 min power-frequency withstand voltage (ph-ph / ph-earth / open contacts) kV Dry 42 / 48; Wet 34
Lightning impulse withstand voltage (peak, ph-ph / ph-earth / open contacts) kV 75 / 85
Mechanical life times 10000
Net weight kg 210
Selection note: The FZW28Z-12 is a sectionalizing load break switch; confirm its short-circuit ratings against the prospective fault level at the installation point and coordinate it with the upstream breaker or recloser.

Standards

The FZW28Z-12 is designed and type-tested to IEC 62271-103 and GB/T 16926 for high-voltage alternating-current load break switches, covering making and breaking capacity, insulation level and mechanical endurance.

Technical note: The sealed SF6-insulated enclosure is maintenance-free for life with no gas handling required; type-test and routine-test certificates are supplied with each unit.

Installation & Dimensions

Installation Diagram

FZW28Z-12 Outdoor Vacuum Sectionalizing Load Break Switch - installation

The FZW28Z-12 is designed for standard pole-mounted installation using brackets, with the controller mounted separately on the pole. Adequate clearance must be maintained around the unit for safe operation and maintenance, and all primary and secondary connections must comply with local utility standards. The certified outline and mounting dimension drawing is supplied with each unit.

Dimension Value (mm)
Overall height 808
Overall width (across cable outlets) 795
Switch body width 400
Switch body height 658
Control device height 340
Control device diameter 300
Safety notice: De-energize and earth the circuit before any physical interaction with the switch. Ensure the neutral-point earthing arrangement matches the selected CT and controller settings.

FAQs

a

a

a

a

a

a

Inquiry for FZW28Z-12 Outdoor Vacuum Sectionalizing Load Break Switch:

Send your project requirements. Our team will reply with technical details and quotation.

Fast response Technical support OEM / ODM