LZZBW-10/165/2S Outdoor Cast-Resin Pillar-Type Current Transformer

LZZBW-10/165/2S Outdoor Cast-Resin Pillar-Type Current Transformer

Outdoor fully enclosed pillar-type CT for 12kV, 13.8kV, 15kV systems

  • LZZBW-10/165/2S outdoor cast-resin current transformer
  • Fully enclosed pillar-type design for outdoor installations
  • Supports 12kV, 13.8kV, 15kV voltage classes
  • High accuracy and IEC compliant for metering and protection
  • Resistant to pollution, moisture, and harsh environments

Product Overview

The LZZBW-10/165/2S is an outdoor epoxy cast-resin current transformer designed for medium-voltage AC systems with rated voltage up to 12kV. It is used for current measurement, metering, and relay protection. This model supports 5A or 1A secondary current and complies with IEC61869-2:2012 and GB20840.2-2014 standards.

Product Type

Item Specification
Product name Outdoor Epoxy Cast-Resin Current Transformer
Model LZZBW-10/165/2S
Insulation Epoxy resin
Rated voltage 10/11/12kV class
Rated insulation level 12/42/75kV
Rated frequency 50Hz
Rated secondary current 5A or 1A
Ambient temperature -5°C to +55°C

Product Display

LZZBW 10 165 2S Current Transformer product display

Main Applications

  • Outdoor medium-voltage distribution systems
  • Current measurement and energy metering circuits
  • Relay protection and monitoring devices
  • Switchgear and distribution cabinets installation

Key Technical Features

  • Outdoor epoxy resin cast for weather and insulation stability
  • Supports 5A or 1A secondary current output
  • Rated insulation 12/42/75kV suitable for 10/11/12kV systems
  • High short-circuit withstand with accurate metering and protection
  • Complies with IEC61869-2:2012 and GB20840.2-2014

Working Principle

The transformer operates via electromagnetic induction. Primary current generates flux in the laminated core, inducing a proportional current in the secondary winding. Epoxy resin ensures insulation between primary and secondary circuits.

Rated Primary, Accuracy and Output

Rated

Primary

Current(A)

Accuracy

Combination

Rated

Output(VA)

Short-Time

Thermal

Current (kA/1s)

Rated

Dynamic

Current (kA)

5–400 0.2/10P, 0.25/10P, 0.5/10P 10 / 10 / 15 60 / 50 / 50 / 45 150 / 120 / 100 / 90
600 10 50 120
800 15 50 100
1000 15 45 90

Overall Dimensions

The following are reference dimensions (mm) for installation and layout planning:

LZZBW-10/165/2S Outdoor Cast-Resin Pillar-Type Current Transformer Installation and Dimensions

FAQs

Used for outdoor medium-voltage measurement, metering, and protection.

5A or 1A secondary current.

12/42/75kV insulation for 10/11/12kV systems.

IEC61869-2:2012 and GB20840.2-2014.

Yes, it supports rated short-time thermal and dynamic currents as specified.

-5°C to +55°C ambient temperature.

Installed on mounting base as per switchgear drawing, ensuring vertical or horizontal alignment.