1. Mahsulotga umumiy ko’rib chiqish
1.1 Funksional ta’rif
LQZJ-0.66 — bu 50 Hz yoki 60 Hz chastotali 0,66 kV sinfli past kuchlanishli o’zgaruvchan tok taqsimlash tarmoqlari uchun mo’ljallangan bitta nisbatli, bir fazali, ichki turdagi joriy transformator (CT). Qurilma asosiy tokni — markaziy Ø103 mm teshik orqali shina yoki izolyatsiyalangan kabel orqali o’tayotgan tokni — nomli nisbatga mos keladigan galvanik ajratilgan 5 A ikkilamchi tokka aylantiradi. Ikkilamchi signal energiya hisoblagichlari, ampermetrlar, transduserlar yoki ortiqcha tok / issiqlik himoya relelariga uzatiladi va yuqori tokli asosiy zanjir bilan o’lchash zanjiri o’rtasida elektr ajratishni ta’minlaydi.
1.2 Asosiy reytinglarning qisqacha ko’rinishi
| Parametr | Texnik xususiyat |
|---|---|
| Tizim kuchlanish sinfi (Um) | 0,72 kV (0,66 kV / 660 V tizimlari uchun mo’ljallangan) |
| Nominal chastota (fr) | 50 Hz yoki 60 Hz |
| Nominal asosiy tok (I₁n) | 5, 10, 15, 20, 30, 40, 50, 75, 100, 150, 200, 300, 400, 600, 800, 1000 A |
| Nominal ikkilamchi tok (I₂n) | 5 A standart (so’rov bo’yicha 1 A mavjud) |
| Aniqlik sinfi | 0,2, 0,5, 1 (hisoblash); 10P (himoya) |
| Nominal quvvat (Sn) | 0,2/0,5 sinfi uchun 10 VA; 1/10P sinfi uchun 15 VA (nomli plakaga ko’ra) |
| Nominal qisqa muddatli issiqlik toki (Ith) | I₁n ning 50 barobarini 1 soniya davomida |
| Nominal dinamik tok (Idyn) | I₁n ning 100 barobarli cho’qqisi |
| Yuklama quvvat koeffitsienti | cos φ = 0,8 orqaga siljish (IEC 61869-2 ga ko’ra standart) |
| Izolyatsiya tizimi | Epoxy smola vakuum quyilgan, to’liq yopiq; issiqlik sinfi B (130 °C) yoki undan yuqori |
| Asosiy teshik | Ø103 mm |
| Umumiy o’lchamlar | 140 mm (K) × 127,5 mm (B) × 103 mm (Ch) |
| Standartlar | IEC 61869-1, IEC 61869-2, GB/T 20840.1, GB/T 20840.2, GB 1208 |
| Oldingi model | Eski LQG-0,5 seriyasining to’g’ridan-to’g’ri almashtiruvchisi |

1.3 Ish prinsipi
LQZJ-0.66 Faradeyning elektromagnit induksiya qonuni va Amperning doiraviy qonuni asosida ishlaydigan bitta burilishli asosiy, ko’p burilishli ikkilamchi, halqasimon yadroli joriy transformator sifatida ishlaydi. Asosiy o’tkazgich toroidal yadro orqali bir marta o’tadi; ikkilamchi o’ram N₂ burilishlardan iborat bo’lib, yadro atrofida teng taqsimlangan. Barqaror sinusoidal ta’sir ostida ideal tok munosabati quyidagicha bo’ladi:
Ulangan yuklama Zb orqali haydalanayotgan ikkilamchi tok yadroda ikkilamchi EMF hosil qiladi. Haqiqiy CTlar ideal nisbatdan tok xatosi εi va faza siljishi δ bilan farq qiladi, ular ishchi oqimni saqlash uchun kerak bo’ladigan magnitlashtiruvchi tok Iμ dan kelib chiqadi. Nominal aniqlik chegarasi koeffitsienti (ALF) da murakkab xato ε himoya sinfi aniqligini belgilaydi va quyidagicha ifodalanadi:
bu yerda Kn — nominal transformatsiya nisbati. Hisoblash sinflari (0,2, 0,5, 1) uchun εi va δ IEC 61869-2 jadvali 201 ga muvofiq 100% I₁n da chegaralanadi; 10P himoya sinfi uchun murakkab xato ε aniqlik chegarasi toki (ALF × I₁n) da ≤ 10% gacha chegaralanadi.
1.4 Tizimda qo’llash o’rni
- Past kuchlanishli kommutatsion jihozlar
- 380 V / 400 V / 415 V / 690 V kommutatsion panellari, taqsimlash panellari, dvigatel boshqaruv markazlari (MCC) va sanoat hamda tijorat yuklamalarini ta’minlaydigan ATS panellari.
- Energiya hisoblash
- Daromad darajasidagi kWh/kvarh hisoblagich (0,2 / 0,5 sinfi), ijara hisoblagich va kommunal xizmatlar ulanish nuqtalari uchun tekshirish hisoblagichi.
- Jarayon o’lchash
- HMI/SCADA uchun ampermetr kirishi, transduser kirishi (4–20 mA / Modbus) va quvvat sifati tahlili uchun yuk profilini olish.
- Rele himoyasi
- Ortiqcha tok (51), darhol ortiqcha tok (50), issiqlik ortiqchaligi (49), dvigatel himoyasi va yer xatosi himoyasi (51N), bu yerda LQZJ fazaviy tokni olish uchun ajratilgan (yer xatosi uchun alohida qoldiq CT).
- Bino va energiya boshqaruvi
- Ajratilgan tokni olish talab qilinadigan BMS, EMS va ISO 50001 energiya kuzatish tizimlari uchun kirish qurilmasi.
1.5 Tuzilish shakliga umumiy ko’rib chiqish
Yonib ketishga qarshi materialdan yasalgan korpus ichida epoksi smolaga o’ralgan yadro va o’ramli yig’ilgan kompakt ustun turidagi konstruksiya. 140 × 127,5 mm poydevor va Ø103 mm teshik odatdagi past kuchlanishli kommutatsion jihozlarning shinlarini (odatda 50 × 5 mm dan 100 × 10 mm gacha) yoki diametri ~95 mm gacha bo’lgan 3-yadroli yoki bitta yadroli kabelni joylashtirishga mo’ljallangan. Pastki panel yoki yon panel — har biri ixtiyoriy 2 teshikli yoki 4 teshikli mahkamlash sxemasi bilan jihozlangan — kubik sxemalar bo’yicha o’rnatishda moslashuvchanlikni ta’minlaydi. To’liq yopiq quyilgan smola korpusi IP20 kirishdan himoya beradi (qo’shimcha qopqoqlar bilan yuqori darajada), ochiq tirik qismlarni yo’q qiladi va to’liq issiqlik sinfi B (yoki so’rov bo’yicha F) muddati davomida dielektrik va qisman razryad ishlashini barqaror saqlaydi.
2. Model belgilash va variantlar

2.1 Model kodi izohi
LQZJ-0.66 belgilash GB/JB xitoylik o’lchov transformatorlari nomlanish an’anasiga amal qiladi. Har bir belgi ma’lum bir qurilish yoki reyting xususiyatini kodlaydi:
| Belgi | O’rin | Ma’nosi |
|---|---|---|
| L | 1 | Joriy transformator (电流互感器) |
| Q | 2 | Halqasimon / halqa o’ralgan konstruksiya (浇圈式) |
| Z | 3 | Quyilgan smola (epoksi) izolyatsiyali, to’liq yopiq (浇注绝缘) |
| J | 4 | Oshirilgan quvvat / kengaytirilgan chiqish (加大容量) |
| □ | 5 | Loyihalash tartib raqami (ishlab chiqaruvchi takrorlash kodi) |
| 0.66 | qo’shimcha | kV da nominal kuchlanish sinfi (0,66 kV / 660 V) |
2.2 Standart variantlar matritsasi
LQZJ-0.66 bir nechta elektr konfiguratsiyalarida taklif etiladi, ularning har biri asosiy tok, aniqlik sinfi va nominal quvvat bilan belgilanadi. Barcha variantlar bir xil mexanik hajm va Ø103 mm teshikka ega bo’lib, bitta kommutatsion jihoz kesimidagi istalgan elektr texnik xususiyatni qabul qilish imkonini beradi.
| Konfiguratsiya
ID |
Asosiy
tok I₁n (A) |
Aniqlik
sinfi |
Nominal quvvat
Sn (VA) |
Odatiy
foydalanish |
|---|---|---|---|---|
| M1 | 5–100 | 0.5 | 10 | Sub-hisoblagich, ampermetr |
| M2 | 50–600 | 0.5 | 10 | Taqsimlash hisoblagichi |
| M3 | 100–1000 | 0.2 | 10 | Daromad hisoblagichi |
| M4 | 50–1000 | 1 | 15 | Umumiy tok o’lchash |
| P1 | 50–1000 | 10P | 15 | Ortiqcha tok / issiqlik himoyasi |
2.3 Seriya rivojlanishi
LQZJ-0.66 avvalgi GB loyihalash avlodlarida ishlab chiqilgan eski LQG-0.5 seriyasini almashtiradi. Mexanik hajm, mahkamlash interfeysi va asosiy teshik (Ø103 mm) to’liq orqaga mos keladi. Oldingi modelga nisbatan konstruktiv yaxshilanishlar quyidagilarni o’z ichiga oladi: yaxshiroq issiqlik chidamliligi va kamroq qisman razryad boshlanish kuchlanishi o’zgaruvchanligiga ega yangilangan epoksi smola formulasi; past asosiy ta’sir ostida magnitlashtiruvchi tokni kamaytirish uchun yaxshilangan yadro donasiy yo’nalishi; va 25–120% I₁n hisoblash diapazonida aniqlikning torroq chegaralanishi.
3. Xizmat ko’rsatish sharoiti
LQZJ-0.66 IEC 61869-1, 4-banddagi oddiy xizmat ko’rsatish sharoitlariga muvofiq faqat ichki foydalanish uchun sertifikatlangan. Quyidagi chegaralardan tashqari ishlash muhandislik ko’rigini talab qiladi va quvvatni pasaytirish, alternativ izolyatsiya sinfi yoki maxsus konfiguratsiya talab qilinishi mumkin.
| Parametr | Standart | Kengaytirilgan
(so’rov bo’yicha) |
|---|---|---|
| O’rnatish | Faqat ichki | Ichki + IP darajasi oshirilgan korpus |
| Dengiz sathidan balandlik | ≤ 2000 m | ≤ 4000 m (IEC 61869-1, 4.2-bandga muvofiq izolyatsiya qayta baholanadi) |
| Atrof-muhit harorati | −5 °C dan +40 °C gacha | −25 °C dan +55 °C gacha |
| Nisbiy namlik | Kunlik o’rtacha ≤ 95% / Oylik o’rtacha ≤ 90% (kondensatsiyasiz) | Tropik (kondensatsiyali) — maxsus qoplam talab qilinadi |
| Atmosfera | Korroziya qiluvchi gazlar, o’tkazuvchi chang, portlovchi muhitlardan xoli | Dengiz / kimyoviy — maxsus korpus |
| Vibratsiya | ≤ 0,5 g, kuchli zarba yo’q | Seysmik sinf S2/S3, IEC 60068-3-3 ga muvofiq |
| Ifloslanish darajasi | PD 2, IEC 60664-1 ga muvofiq | PD 3 — kengaytirilgan tiniq masofa talab qilinadi |
4. Qurilish
4.1 Qurilish dizayni
- Magnit yadro
- Donali yo’naltirilgan kremniyli po’latdan (CRGO, odatda 0,30 mm yoki 0,27 mm qalinlikda) yasalgan halqasimon (halqa turidagi) o’ralgan yadro. Yadroning mexanik kuchlanishni yo’qotish va magnit o’tkazuvchanlikni tiklash uchun o’ramdan keyin jarrohlik qilinadi. Past tok diapazonlari (I₁n ≤ 50 A) uchun past darajadagi aniqlikni yaxshilash uchun nikel-temir qotishmasi yadrolari belgilanishi mumkin.
- Asosiy zanjir
- Bitta burilishli o’tish konfiguratsiyasi. Ø103 mm teshik asosiy «o’ram» sifatida shina yoki kabelni qabul qiladi. Maxsus asosiy terminal yo’q; foydalanuvchi ta’minlagan o’tkazgich korpusda P1 → P2 deb belgilangan yo’nalishda derazadan o’tadi.
- Ikkilamchi o’ram
- Yadro atrofida bir tekis o’ralgan ko’p burilishli mis magnit simi (B yoki F sinfli emal izolyatsiyasi). Ikkilamchi burilishlar soni N₂ nominal transformatsiya nisbatiga teng (masalan, 200/5 → N₂ = 40). Burilishlar orasidagi izolyatsiya va mexanik mustahkamlash quyishdan oldin o’ram yig’ilmaga integratsiyalangan.
- Izolyatsiya tizimi
- Vakuum quyilgan epoksi smola yadro va o’ram yig’ilmasini to’liq qoplaydi. Quyilgan korpus asosiydan ikkilamchigacha, ikkilamchidan yergacha izolyatsiya, mexanik qo’llab-quvvatlash va atrof-muhitni himoya qilishni bitta monolit tuzilishda birlashtiradi. Standart issiqlik sinfi B (130 °C); F sinfi (155 °C) so’rov bo’yicha mavjud.
- Korpus
- Quyilgan smola korpus ustiga yonib ketishga qarshi termoplastik tashqi qobiq (UL94 V-0), qo’l bilan ishlash paytida mexanik himoya va xizmat ko’rsatishda IP20 kirishdan himoya beradi.
- Mahkamlash poydevori
- Integratsiyalangan polimer poydevor ikkita interfeys variantiga ega: pastki mahkamlash (panel-polga mos keladigan poydevor) yoki yon mahkamlash (vertikal shina o’rnatishlari uchun mos). Har bir poydevor 2 teshikli yoki 4 teshikli mahkamlash sxemasini taklif qiladi; M6 elementlari standartdir.
- Terminallar
- Ikkilamchi terminallar S1 va S2 boltli turdagi (M5 yoki M6 mis) bo’lib, qulfli g’ildirak va arra bilan birga old tomonda joylashgan. Polarity IEC 61869-2, 6.13-bandga muvofiq korpusda doimiy belgilangan (asosiy P1/P2 ikkilamchi S1/S2 ga ayirish an’anasiga muvofiq).
4.2 O’ramlar va terminal belgilash
| Terminal | Belgilash | Funksiya |
|---|---|---|
| P1 | Asosiy, polarity belgilangan uch | An’anaviy tok kirishi; nisbat testi uchun referens yo’nalish |
| P2 | Asosiy, polarity belgilanmagan uch | An’anaviy tok chiqishi |
| S1 | Ikkilamchi, polarity belgilangan uch | Ampermetr / hisoblagich / rele musbat kirishiga chiqish |
| S2 | Ikkilamchi, polarity belgilanmagan uch | O’lchash jihozlarining neytraliga chiqish; xizmat ko’rsatishda bitta nuqtadan yerga ulanadi |
Referens tok yo’nalishi: asosiy tok i₁ P1 ga kirib, P2 dan chiqsa, ikkilamchi tok i₂ S1 dan tashqari yuklama orqali o’tib, S2 ga qaytadi. Bu ayirish polarity kWh hisoblagich, vattmetrik yer xatosi himoyasi va istalgan yo’nalishli rele funktsiyasi uchun majburiydir.
5. Texnik ma’lumotlar
Ushbu bo’lim LQZJ-0.66 seriyasi uchun tanlash darajasidagi elektr ma’lumotlarini taqdim etadi. Barcha qiymatlar nomli plakada ko’rsatilgan nominal yuklama va nominal chastotada amal qiladi. Standart diapazondan tashqari konfiguratsiyalar uchun texnik kelishuv va loyiha uchun maxsus ma’lumot varaqasi asos bo’ladi.
5.1 Asosiy va ikkilamchi reytinglar
| Nominal asosiy
tok I₁n (A) |
Nominal ikkilamchi
tok I₂n (A) |
Mavjud
aniqlik sinfi |
Nominal
quvvat Sn (VA) |
Ith / 1 s
(kA) |
Idyn cho’qqi
(kA) |
|---|---|---|---|---|---|
| 5 | 5 | 0.5 / 1 | 10 / 15 | 0.25 | 0.5 |
| 10 | 5 | 0.5 / 1 | 10 / 15 | 0.5 | 1.0 |
| 15 | 5 | 0.5 / 1 | 10 / 15 | 0.75 | 1.5 |
| 20 | 5 | 0.5 / 1 | 10 / 15 | 1.0 | 2.0 |
| 30 | 5 | 0.5 / 1 | 10 / 15 | 1.5 | 3.0 |
| 40 | 5 | 0.5 / 1 | 10 / 15 | 2.0 | 4.0 |
| 50 | 5 | 0.2 / 0.5 / 1 / 10P | 10 / 15 | 2.5 | 5.0 |
| 75 | 5 | 0.2 / 0.5 / 1 / 10P | 10 / 15 | 3.75 | 7.5 |
| 100 | 5 | 0.2 / 0.5 / 1 / 10P | 10 / 15 | 5.0 | 10 |
| 150 | 5 | 0.2 / 0.5 / 1 / 10P | 10 / 15 | 7.5 | 15 |
| 200 | 5 | 0.2 / 0.5 / 1 / 10P | 10 / 15 | 10 | 20 |
| 300 | 5 | 0.2 / 0.5 / 1 / 10P | 10 / 15 | 15 | 30 |
| 400 | 5 | 0.2 / 0.5 / 1 / 10P | 10 / 15 | 20 | 40 |
| 600 | 5 | 0.2 / 0.5 / 1 / 10P | 10 / 15 | 30 | 60 |
| 800 | 5 | 0.2 / 0.5 / 1 / 10P | 10 / 15 | 40 | 80 |
| 1000 | 5 | 0.2 / 0.5 / 1 / 10P | 10 / 15 | 50 | 100 |
Eslatma: 1 A ikkilamchi konfiguratsiyalar so’rov bo’yicha mavjud; standart bo’lmagan nisbatlar uchun zavod bilan maslahatlashing.
5.2 Aniqlik sinfi chegaralari (IEC 61869-2 ga muvofiq)
| Sinfi | Aniqlik qo’llanadigan
tok |
Tok xatosi
εi (±%) |
Faza siljishi
δ (±min) |
ALF da murakkab xato
ε |
|---|---|---|---|---|
| 0.2 | 5%, 20%, 100%, 120% I₁n | 0.75 / 0.35 / 0.20 / 0.20 | 30 / 15 / 10 / 10 | — |
| 0.5 | 5%, 20%, 100%, 120% I₁n | 1.5 / 0.75 / 0.50 / 0.50 | 90 / 45 / 30 / 30 | — |
| 1 | 5%, 20%, 100%, 120% I₁n | 3.0 / 1.5 / 1.0 / 1.0 | 180 / 90 / 60 / 60 | — |
| 10P | I₁n da | ±3.0 (tok xatosi) | belgilanmagan | ALF × I₁n da ≤ 10% |
0,2 va 0,5 sinflari uchun aniqlik nominal yuklamaning 25%–100% va nominal tokning 5%–120% oralig’ida tekshiriladi. 10P himoya sinfi uchun aniqlik chegarasi koeffitsienti (ALF) odatda 5, 10, 15, 20 yoki 30 — nomli plakada, masalan, «10P10» (10 × I₁n da murakkab xato ≤ 10%) deb ko’rsatilgan.
5.3 Issiqlik va dinamik bardosh
Qisqa muddatli issiqlik toki Ith (1 s) va dinamik cho’qqi toki Idyn quyidagi munosabatlar bilan belgilanadi:
LQZJ-0.66 uchun standart reytinglar Ith = 50 × I₁n / 1 s va Idyn = 100 × I₁n cho’qqi. Ikkalasi ham o’rnatish nuqtasidagi tizimning potentsial qisqa tutashuv toki Ipsc va cho’qqi nosozlik toki Ipk dan kam bo’lmasligi kerak. Tasdiqlash zavodning qisqa tutashuv turli test hisoboti orqali amalga oshiriladi, bu hisobot rutin test sertifikatida ko’rsatilgan.
6. Standartlar va havolalar
6.1 Qo’llaniladigan standartlar
| Standart | Sarlavha | Qo’llash |
|---|---|---|
| IEC 61869-1 | O’lchov transformatorlari — 1-qism: Umumiy talablarni | Umumiy elektr, mexanik, issiqlik talablari |
| IEC 61869-2 | O’lchov transformatorlari — 2-qism: Joriy transformatorlar uchun qo’shimcha talablar | CT-ga xos aniqlik, yuklama, qisqa tutashuv, turli testlar |
| GB/T 20840.1 | O’lchov transformatorlari — 1-qism: Umumiy talablar | Milliy standart, IEC 61869-1 bilan uyg’unlashtirilgan |
| GB/T 20840.2 | O’lchov transformatorlari — 2-qism: Joriy transformatorlar | Milliy standart, IEC 61869-2 bilan uyg’unlashtirilgan |
| GB 1208 | Joriy transformatorlar | Milliy CT standarti (ko’rsatilgan holda eski havola) |
| IEC 60664-1 | Past kuchlanishli tizimlardagi jihozlar uchun izolyatsiya koordinatsiyasi | 0,66 kV sinfi uchun tiniq va suzuv masofa |
| IEC 60529 | Himoya darajalari (IP kodi) | Kirishdan himoya reytingi |
| IEC 60085 | Elektr izolyatsiyasi — Issiqlik baholash va belgilash | Issiqlik sinfi B / F belgilash |
| IEEE C57.13 | O’lchov transformatorlari uchun standart talablar | Shimoliy Amerika loyihalari uchun ixtiyoriy havola |
6.2 Rutin testlar (Har bir qurilma)
IEC 61869-2, 7.3-band / GB/T 20840.2 ga muvofiq har bir ishlab chiqarilgan qurilma uchun amalga oshiriladi:
- Belgilashni tekshirish (P1/P2, S1/S2, nomli plaka ma’lumotlari)
- Asosiy o’ramda chastotali kuchlanishga bardosh testi (0,66 kV sinfi uchun 1 daqiqa davomida 3 kV effektiv)
- Ikkilamchi o’ramda chastotali kuchlanishga bardosh testi (1 daqiqa davomida 3 kV effektiv)
- Ikkilamchi o’ramda burilishlar orasidagi ortiqcha kuchlanish testi
- Nominal yuklamada xatolarni aniqlash (metering sinfi uchun 5%–120% I₁n oralig’ida tok xatosi εi va faza siljishi δ; himoya sinfi uchun ALF da murakkab xato)
- Polarityni tekshirish (P1–S1 ayirish an’anasiga muvofiq)
- 500 V DC da izolyatsiya qarshiligi ≥ 100 MΩ
6.3 Turli testlar (Loyiha tasdiqlash)
IEC 61869-2, 7.2-bandga muvofiq namunaviy namunalar ustida amalga oshiriladi:
- Nominal doimiy tokda harorat ko’tarilish testi (izolyatsiya sinfiga ko’ra chegaralar)
- Qisqa muddatli tok testi (1 s uchun Ith) va dinamik tok testi (Idyn cho’qqi)
- Yorug’lik impulsi kuchlanishiga bardosh testi (0,72 kV Um sinfi uchun 8 kV cho’qqi, 1,2/50 μs)
- Chegaraviy yuklama sharoitlarida xatolarni aniqlash
- Aniqlik sinfini to’liq ishlash diapazoni bo’yicha tekshirish
- Loyiha tomonidan ko’rsatilgan mexanik va atrof-muhit testlari
7. O’rnatish va o’lchamlar

7.1 Tashqi o’lchamlar
| O’lcham | Qiymat | Havola |
|---|---|---|
| Umumiy kenglik | 140 mm (maks.) | old tomondan ko’rinish |
| Umumiy balandlik | 127.5 mm | old tomondan ko’rinish |
| Umumiy chuqurligi | 103 mm (taxminan) | yon tomondan ko’rinish |
| Asosiy teshik | Ø103 mm | markaziy deraza |
| Mahkamlash poydevori uzunligi | 110 mm | mahkamlash interfeysi |
| Mahkamlash teshiklari orasidagi masofa | 56 mm × 89 mm (odatda, sertifikatlangan chizmaga murojaat qiling) | 2 teshikli / 4 teshikli sxema |
| Mahkamlash elementlari | 4 × Ø5 mahkamlash slotlari; M6 elementlari tavsiya etiladi | variantga qarab |
| Toza og’irlik | ~ 0.8–1.2 kg (konfiguratsiyaga qarab) | yuborish havolasi |
Loyiha uchun maxsus chidamlilik va mahkamlash teshiklari koordinatalari uchun sertifikatlangan o’lchov chizmasiga murojaat qiling.
7.2 O’rnatish ko’rsatmalari
- CT-ni toza, tekis, qattiq sirtga barcha belgilangan mahkamlash teshiklaridan foydalanib o’rnating. Mahkamlash elementlarini ishlab chiqaruvchining tavsiya etgan momentga (odatda M6 elementlar uchun 6–8 N·m) qadar siqib qo’ying.
- Asosiy o’tkazgichni (shina yoki kabelni) Ø103 mm teshik markazidan o’tkazing. Belgilangan P1 → P2 yo’nalishini saqlang — ushbu yo’nalishda oqayotgan tok S1 → S2 ikkilamchi chiqishini beradi.
- Tizim izolyatsiya koordinatsiyasiga muvofiq qo’shni tirik qismlarga yetarli tiniq masofani ta’minlang (IEC 60664-1, PD 2 ga muvofiq 0,66 kV sinfi uchun minimal 25 mm havo tiniq masofasi).
- Ikkilamchi arqonni nominal tokda yuklama Sn doirasida qolishini ta’minlash uchun umumiy ikkilamchi zanjir qarshiligini cheklang. 5 A ikkilamchi uchun 25 m gacha uzunlikdagi arqonlar uchun 2,5 mm² mis odatiydir; undan uzunroq arqonlar 4 mm² yoki 1 A ikkilamchiga o’tishni talab qilishi mumkin.
- S1 ni ampermetr / hisoblagich / rele tirik kirishiga ulang; S2 ni o’lchash jihozlarining neytraliga ulang. Ikkilamchi zanjirning bitta nuqtasini (odatda himoya paneli terminal blokida) yerga ulang — hech qachon bir nechta nuqtalarni ulamang.
- Asosiy zanjirni quvvatlaganidan oldin birlamchi inyeksiya yoki polarity testeri yordamida polarity va nisbatni ishga tushirishda tekshiring.
7.3 Xavfsizlik va texnik xizmat ko’rsatish eslatmalari
- Har doim pastki o’lchash jihozlarini uzishdan oldin S1–S2 ni qisqa tutash qiling.
- Ikkilamchi zanjirning bitta nuqtasi yerga ulanishi kerak (odatda marshalling kioskida S2).
- Asosiy o’tkazgich tashqi tarzda o’rnatilishi va qo’llab-quvvatlanishi kerak — LQZJ-0.66 korpusi asosiy o’tkazgich og’irligini yoki nosozlik natijasida vujudga keladigan mexanik kuchlarni qo’llab-quvvatlash uchun mo’ljallanmagan.
- Nosozliklar paytida nomli plakadagi Ith / Idyn reytinglaridan tashqari asosiy tokda CT-larni ishlatish magnit, mexanik yoki izolyatsiya doimiy shikastlanishiga sabab bo’ladi.
- Barcha ishlar IEC 60364, GB 26860, NFPA 70E yoki tegishli mahalliy elektr xavfsizlik qoidalariga, shu jumladan qulflash / yorliqlash protseduralariga rioya qilinishi kerak.
8. Tanlash bo’yicha qo’llanma (Ishlangan misol)
Quyidagi to’rt bosqichli jarayon 400 V kommutatsion panelda 250 A doimiy yuklama dvigatel tarmog’i uchun LQZJ-0.66 ni tanlashni namoyish etadi, bu yerda raqamli ko’p funksiyali hisoblagich va issiqlik ortiqchaligi rele ulangan bo’lib, kommutatsion paneldan hisoblagich kioskgacha ikkilamchi kabel uzunligi 20 m.
1-bosqich — Nominal asosiy tok I₁n ni aniqlash
Doimiy yuklama toki Ic = 250 A. I₁n ≥ 1,2 × Ic = 300 A ni tanlang. Standart ro’yxatdan: I₁n = 300 A. Bu ishlash nuqtasini I₁n ning 250/300 = 83% ga qo’yadi, bu 25%–100% optimal aniqlik diapazoni ichida yaxshi.
2-bosqich — Aniqlik sinfini ko’rsatish
Loyiha sub-hisoblagich darajasidagi hisoblashni talab qiladi — IEC 61869-2 ga muvofiq 0,5 sinfi mos keladi. Issiqlik rele bu holda xuddi shu hisoblagich yadrosini ishlatishi mumkin (relening 1-sinf talabi 0,5-sinf tomonidan avtomatik ravishda qanoatlantiriladi). Qat’iyroq o’rnatish uchun alohida 10P yadro belgilanadi.
3-bosqich — Kerakli yuklamani hisoblash
Ikkilamchi zanjirdagi ulangan yuklamalar:
- Ko’p funksiyali hisoblagich kirishi: Sm = 0,05 VA (odatda elektron)
- Issiqlik ortiqchaligi rele: Sr = 0,5 VA
- Ikkilamchi kabel: 20 m × 2 (halqa) = 40 m umumiy yo’l; ρ = 0,0175 Ω·mm²/m bo’lgan 2,5 mm² mis → Rwire = 0,0175 × 40 / 2,5 = 0,28 Ω
- Arqon yuklamasi Sw = I₂n² × Rwire = 5² × 0,28 = 7,0 VA
Sn = 10 VA ni 0,5 sinfda tanlash 32% chegara beradi, bu yetarli. Agar kabel uzunligi 30 m dan ortiq bo’lsa, arqon yuklamasi Sb ni 10 VA ga yaqin qiladi — bunday holda 4 mm² kabelga o’tish yoki arqon yuklamasini 25 marta kamaytirish uchun 1 A ikkilamchini belgilash kerak.
4-bosqich — Qisqa tutashuvga bardoshni tekshirish
Kommutatsion paneldagi shinalarda tizimning potentsial nosozlik toki: Ipsc = 25 kA / 1 s. I₁n = 300 A uchun CT-ni nomli plakadagi Ith = 50 × 300 = 15 000 A = 15 kA / 1 s. Bu yetarli emas. Tanlangan CT kengaytirilgan Ith reytingi (zavod varianti) bilan belgilanishi yoki yuqori himoya tozalash vaqti CT-ni standart reyting doirasiga keltirish kerak. Qayta hisoblash: agar breyker tozalash vaqti tf = 0,3 s bo’lsa, Ith,equiv = 25 × √0,3 = 13,7 kA — standart reyting doirasida. Yuqori himoya qurilmasining haqiqiy o’tkazuvchan I²t ni CT nomli plakasi bilan solishtiring.
9. Buyurtma ma’lumotlari
Har bir buyurtma ishlab chiqarishni boshlash va qabul qilish imkonini berish uchun quyidagi parametrlarni ko’rsatishi kerak. Loyiha standart bo’lmagan konfiguratsiyani (kengaytirilgan harorat, alternativ issiqlik sinfi, tropiklashtirish, maxsus terminal sxemasi, tilga xos nomli plaka) talab qilsa, ularni so’rov bosqichida aniq ko’rsating; ular texnik kelishuv va loyiha uchun maxsus ma’lumot varaqasi bilan belgilanadi.
| Kerakli parametr | Format / variantlar |
|---|---|
| Model | LQZJ-0.66 |
| Nominal asosiy tok I₁n | 5, 10, 15, 20, 30, 40, 50, 75, 100, 150, 200, 300, 400, 600, 800, 1000 A |
| Nominal ikkilamchi tok I₂n | 5 A (standart) / 1 A (so’rov bo’yicha) |
| Aniqlik sinfi | 0.2 / 0.5 / 1 / 10P (10P uchun ALF ni ko’rsating, masalan, 10P10) |
| Nominal quvvat Sn | 10 VA / 15 VA |
| Ikkilamchi yadrolar soni | 1 (bitta yadro); 2 (alo-hida hisoblagich + himoya yadrolari) so’rov bo’yicha |
| Mahkamlash turi | Pastki mahkamlash / Yon mahkamlash |
| Mahkamlash teshiklari sxemasi | 2 teshikli / 4 teshikli |
| Chastota | 50 Hz / 60 Hz |
| Maxsus talablar | Izolyatsiya sinfi F, tropiklashtirish, nomli plaka tili, uchinchi tomon tomonidan guvohlantirish testi va boshqalar. |
10. Tez-tez beriladigan savollar