Mahsulotga umumiy ko’rib chiqish
Funksional ta’rif
BH-0.66R (RCT) seriyali tok transformatorlari past kuchlanishli o’zgaruvchan tok elektr tizimlarida aniq tok o’lchash, elektr energiyasini hisoblash va releli himoya qilish dasturlari uchun mo’ljallangan elektromagnit o’lchov asboblari hisoblanadi. Ushbu transformatorlar birlamchi tokka proporsional galvanik ajratilgan ikkilamchi tok signallarini ta’minlash uchun elektromagnit induksiya prinsipidan foydalanadi.
Asosiy reytinglar haqida qisqacha ma’lumot
| Band | Texnik xususiyatlar (buyurtma/yoki nom plakasi bo’yicha) |
|---|---|
| Tizim kuchlanish sinfi | 0,66 kV yoki undan past (ichki past kuchlanishli taqsimlash dasturlari) |
| Nominal chastota | 50 Gs yoki 60 Gs |
| Nominal ikkilamchi tok | 5 A |
| Aniqlik sinflari | 0,5; 1,0 (hisob-kitob va himoya yadrolari) |
| Nominal yuklama | 5 VA, 10 VA, 15 VA, 25 VA (ko’rsatilgani kabi har bir yadro/o’ram bo’yicha) |
| Yuklama quvvat koeffitsienti | cosφ = 0,8 (ortga siljish), agar aks holda ko’rsatilmagan bo’lsa |
| Izolyatsiya darajasi | 0,5 kV / 3 kV (nominal izolyatsiya kuchlanishi / chidamlilik sinov kuchlanishi) |
| Qo’llaniladigan standartlar | GB/T 20840.8-2007 (O’lchov transformatorlari – 8-qism: Elektron tok transformatorlari); JB/T 5356-2002 (Past kuchlanishli tok transformatorlari uchun umumiy texnik talablari) |
| Yadro teshigi variantlari | φ35, φ58, φ90, φ110 (turli birlamchi o’tkazgich kesimlari uchun) |
Mahsulot namoyishi

Ish prinsipi
Faradey elektromagnit induksiya qonuniga asoslangan ishlashda transformator birlamchi o’tkazgich (shinalar yoki kabel) teshigidan o’tadigan halqasimon (uzuk) magnit yadrosiga ega. Ikkilamchi o’ram yadro atrofida tekis o’ralgan. Birlamchi tok tomonidan hosil qilingan magnit oqimi ikkilamchi o’ramda proporsional kuchlanishni induksiyalaydi va ulangan yuklama orqali standartlashtirilgan chiqish tokini (5 A) yetkazib beradi.
Tizimda qo’llash sohasi
- Past kuchlanishli taqsimlash: 0,66 kV va undan past kuchlanishli taqsimlash paneli hamda kommutatsion jihozlar
- Energiya hisobi: Elektr energiyasini o’lchash va tushum hisob-kitob tizimlari
- Himoya zanjirlari: Past kuchlanishli tizimlarda ortiqcha tok va releli himoya sxemalari
- Tok monitoringi: Sanoat va tijorat elektr jihozlarida real vaqt rejimida tok monitoringi
Konstruksiya shakliga umumiy ko’rib chiqish
Plastmassa izolyatsiyali konstruksiya va halqasimon temir yadro dizayni. Pastdan o’rnatish konfiguratsiyasi past kuchlanishli taqsimlash uskunalari bilan ixcham integratsiyani ta’minlaydi. Dizayn shinalarni o’tkazish uchun maxsus teshik va mustahkam o’rnatish uchun montaj plastinkasini o’z ichiga oladi.
Model belgilash

Model kodining izohi
- BH — Ishlab chiqaruvchi belgilashi (Duoma Electric)
- 0.66 — Nominal kuchlanish sinfi (0,66 kV yoki undan past)
- R — Halqasimon (halqa turidagi) yadro konfiguratsiyasi
- (RCT) — Mahsulot seriyasi belgilashi: Past kuchlanishli dasturlar uchun smola izolyatsiyali tok transformatori
Xizmat ko’rsatish sharoitlari
RCT seriyali tok transformatorlari past kuchlanishli elektr tizimlarida oddiy xizmat ko’rsatish sharoitlarida faqat ichkarida ishlash uchun mo’ljallangan.
- O’rnatish muhiti: Faqat ichkarida o’rnatish
- Dengiz sathidan balandlik: 1000 m dan oshmasligi kerak
- Atrof-muhit harorati: −5 °C dan +40 °C gacha
- Nisbiy namlik: ≤ 80%
- Atrof-muhit sharoitlari: Jiddiy atmosfera ifloslanmagan; korroziyaga sababchi gazlar, portlovchi muhit yoki kuchli mexanik titrashlardan xoli
Konstruksiya
Konstruksiya dizayni
- Yadro turi: Halqasimon (uzuk) temir yadro
- Izolyatsiya: Plastmassa izolyatsiyali tuzilma
- O’ram: Ikkilamchi o’ram yadro atrofida tekis o’ralgan
- O’rnatish: Montaj plastinkasi va shina teshigi bilan pastdan o’rnatilgan
Asosiy xususiyatlar
- Halqasimon temir yadro: Uzoq muddatli xizmat ko’rsatish davrida samarali tok transformatsiyasi va aniq o’lchash uchun optimallashtirilgan magnit oqim yo’li
- Bir xil ikkilamchi o’ram: Aniq tok o’lchash uchun aniq va ishonchli chiqishni ta’minlaydigan doimiy o’ram taqsimoti
- Mustahkam o’rnatish uchun montaj plastinkasi: Montaj plastinkasi bilan pastdan o’rnatish konstruksiyasi taqsimlash tizimlarida barqaror ishlashni ta’minlaydi
- Shinalarga kirish teshigi: Birlamchi o’tkazgich (shinalar) o’tish uchun maxsus teshik elektr tizimiga sodda integratsiyani osonlashtiradi
O’ramlar va terminal belgilash
- Birlamchi o’tkazgich: Yadro teshigidan o’tuvchi shinalar yoki kabel (doimiy terminal yo’q)
- Ikkilamchi terminal: Ikkilamchi zanjirni ulash uchun chiqish terminali
Terminal belgilash standart CT polarlik an’analari asosida amalga oshiriladi. Hisob-kitob va himoya samaradorligini ta’minlash uchun to’g’ri terminal identifikatsiyasi kuzatilishi kerak.
Texnik ma’lumotlar
Ushbu bo’lim 0,66 kV sinfli o’zgaruvchan tok tizimlarida (50 Gs yoki 60 Gs) ishlatiladigan RCT seriyali ichki plastmassa izolyatsiyali tok transformatorlari uchun aniqlik sinfi, nominal yuklamalar va transformatsiya nisbatlarini dastlabki tanlashga yo’naltirilgan texnik ma’lumotlarni taqdim etadi.
Ta’riflar: Nominal transformatsiya nisbati birlamchi va ikkilamchi tok nisbatini ko’rsatadi (masalan, 100/5). Nominal chiqish (VA) ikkilamchi yadro bo’yicha ko’rsatilgan. To’g’ridan-to’g’ri o’tish burilish soni birlamchi o’tkazgichning teshikdan o’tish sonini ko’rsatadi (odatda shinalar uchun 1).
Ma’lumotlar havolasi
| Turi (Yadro teshigi) | Nominal transformatsiya nisbati (A) | Shina kesimi (mm) | Xarid qilish texnik xususiyatlari (mm) | To’g’ridan-to’g’ri o’tish burilish soni | Aniqlik sinfi va nominal chiqish (VA) cosφ = 0.8 |
Nominal izolyatsiya darajasi (kV) | |
|---|---|---|---|---|---|---|---|
| 0.5 | 1.0 | ||||||
| φ35 | 15/5 | — | — | 10 | 5 | 10 | 0.5/3 |
| 20/5 | — | — | 5 | 5 | 10 | ||
| 30/5 | — | — | 5 | 5 | 10 | ||
| 40/5 | — | — | 3 | 5 | 10 | ||
| 50/5 | — | — | 2 | 5 | 10 | ||
| 75/5 | — | — | 2 | 5 | 10 | ||
| 100/5 | 30 × 10 | 1 | 1 | 5 | 10 | ||
| φ58 | 150/5 | 30 × 10 | 1 | 1 | 10 | 15 | 0.5/3 |
| 200/5 | 30 × 10 | 1 | 1 | 10 | 15 | ||
| 300/5 | 50 × 10 | 1 | 1 | 10 | 15 | ||
| 400/5 | 50 × 10 | 1 | 1 | 10 | 15 | ||
| φ90 | 500/5 | 50 × 10 | 60 × 10 | 1 | 15 | 25 | 0.5/3 |
| 600/5 | 50 × 10 | 60 × 10 | 1 | 15 | 25 | ||
| 800/5 | 80 × 10 | 60 × 10 | 1-2 | 15 | 25 | ||
| 1000/5 | 80 × 10 | 60 × 10 | 1-2 | 15 | 25 | ||
| φ110 | 1200/5 | 80 × 10 | 80 × 10 | 1-2 | 15 | 25 | 0.5/3 |
| 1500/5 | 100 × 10 | 80 × 10 | 1-2 | 15 | 25 | ||
| 2000/5 | 100 × 10 | 80 × 10 | 1-2 | 15 | 25 | ||
| 2500/5 | 100 × 10 | 80 × 10 | 1-2 | 15 | 25 | ||
| 3000/5 | 100 × 10 | 80 × 10 | 1-2 | 15 | 25 | ||
| 4000/5 | 100 × 10 | 80 × 10 | 1-2 | 15 | 25 | ||
Standartlar va normativ havolalar
| Standart | Sarlavha | Qo’llash sohasi |
|---|---|---|
| GB/T 20840.8-2007 | O’lchov transformatorlari – 8-qism: Elektron tok transformatorlari | Past kuchlanishli tok transformatorlari uchun milliy standart |
| JB/T 5356-2002 | Past kuchlanishli tok transformatorlari uchun umumiy texnik talablari | Past kuchlanishli TT uchun sanoat standarti |
| GB/T 13384-2008 | Elektr jihozlari uchun umumiy talablari | Umumiy elektr jihozlari talablari |
Zavod sinovlari talablarga mos kelishi
- Doimiy sinovlar tegishli GB talablari bo’yicha (ko’rsatilgan sinf va yuklama bo’yicha polarlikni, nisbatni va aniqlikni tekshirishni o’z ichiga oladi)
- Dielektrik sinovlar izolyatsiya muvofiqligi talablari bo’yicha
- Ko’rik va o’lchov tekshiruvi belgilash va ishlab chiqarish sifatiga mos kelishni o’z ichiga oladi
- Tur sinovlari loyiha texnik xususiyatlariga ko’ra talab qilinadi
O’rnatish va o’lchamlar

- Chet o’lchamlari va o’rnatish tafsilotlari quyidagi o’lchov chizmalarida keltirilgan
- Transformator montaj plastinkasidagi belgilangan mahkamlash teshiklari orqali mustahkam o’rnatilishi kerak
- Birlamchi o’tkazgichni ulash shinalar yoki kabelni yadro teshigidan o’tkazish orqali amalga oshiriladi
- Izolyatsiya butunligi va texnik xizmat ko’rsatishga kirish uchun yetarli bo’sh joy saqlanishi kerak
Chet o’lchamlari
| Turi | d (mm) | A (mm) | B (mm) | D (mm) | G (mm) | H (mm) | L (mm) |
|---|---|---|---|---|---|---|---|
| RCT-35 | 35 | 95 | 80 | 78 | 45 | 90 | 54 |
| RCT-58 | 58 | 110 | 88 | 100 | 45 | 113 | 56 |
| RCT-90 | 90 | 110 | 88 | 135 | 38 | 147 | 40 |
| RCT-110 | 110 | 110 | 88 | 163 | 38 | 177 | 40 |
Xavfsizlik eslatmalari
- Transformator tok uzatilayotganda ikkilamchi zanjiri hech qachon ochiq qoldirilmasin, chunki ikkilamchi terminalda xavfli yuqori kuchlanish paydo bo’lishi mumkin
- Tekshiruv yoki texnik xizmat ko’rsatish paytida ikkilamchi zanjirni istalgan asbobni uzishdan oldin qisqa tutashish kerak
- Ikkilamchi zanjirning bitta nuqtasi tegishli standartlarga muvofiq ishonchli tarzda yerga ulanishi kerak
- Barcha o’rnatish va texnik xizmat ko’rsatish ishlari mahalliy elektr xavfsizligi qoidalariga rioya qilinishi kerak
Buyurtma ma’lumotlari
Buyurtma berishda mahalliy elektr talablari, qo’llaniladigan standartlar va loyiha texnik xususiyatlariga muvofiq kerakli konfiguratsiya ko’rsatilishi kerak. Quyidagi parametrlar texnik tasdiqlash va ishlab chiqarishni boshlash uchun aniq ko’rsatilishi kerak:
- Nominal birlamchi tok / transformatsiya nisbati (masalan, 100/5, 200/5)
- Nominal ikkilamchi tok (standart 5 A)
- Aniqlik sinfi (hisob-kitob va/yoki himoya dasturlari uchun 0,5 yoki 1,0)
- Nominal yuklama (VA) ikkilamchi zanjir uchun
- Yadro teshigi hajmi (birlamchi o’tkazgich kesimiga asoslanib φ35, φ58, φ90 yoki φ110)
Qanday tanlash kerak:
- Zanjir yuklamasi reytingi va kutilayotgan ishlash diapazoniga asoslanib nominal birlamchi tokni (Ip) aniqlang
- Aniqlik sinfini tanlang (hisob-kitob uchun 0,5; himoya yoki umumiy o’lchash uchun 1,0)
- Ulangan hisoblagichlar/relelar va simlar qarshiligiga asoslanib nominal yuklamani (VA) tasdiqlang
- Yadro teshigi hajmining birlamchi o’tkazgich (shinalar yoki kabel) kesimiga mos kelishini tekshiring
Agar mahalliy elektr ta’minot kompaniyasi yoki loyiha talablari qo’llansa (masalan, maxsus izolyatsiya darajasi, terminal tartibi, o’rnatish cheklovlari, hujjatlar tilini yoki talab qilinadigan sertifikatlarni), ularni buyurtma bosqichida ko’rsating. Maxsus konfiguratsiyalar ishlab chiqarishdan oldin texnik kelishuv orqali tasdiqlanishi kerak.
Tez-tez so’raladigan savollar
S1: RCT ichki tok transformatorining asosiy qo’llash sohalari qanday?
J: RCT nominal kuchlanishi 0,66 kV yoki undan past bo’lgan past kuchlanishli elektr tizimlarida aniq tok o’lchash, energiya hisob-kitobi va releli himoya qilish uchun ishlatiladi.
S2: RCT transformatorini tashqi muhitda ishlatish mumkinmi?
J: Yo’q, RCT transformatori faqat ichkarida foydalanish uchun mo’ljallangan. Tashqi muhitda foydalanish uchun mos atrof-muhitni himoya qilish reytingiga ega transformatorlar talab qilinadi.
S3: RCT transformatorining maksimal nominal kuchlanishi qancha?
J: RCT transformatori nominal kuchlanishi 0,66 kV yoki undan past bo’lgan tizimlarda ishlatish uchun mo’ljallangan.
S4: Mos yadro teshigi hajmini qanday tanlash kerak?
J: Yadro teshigi hajmi (φ35, φ58, φ90 yoki φ110) o’rnatish uchun yetarli bo’sh joyni ta’minlash maqsadida birlamchi o’tkazgich (shinalar yoki kabel) ko’ndalang kesim o’lchamlariga asoslanib tanlanishi kerak.
S5: RCT transformatori uchun qanday aniqlik sinflari mavjud?
J: RCT transformatori aniqlik sinfi 0,5 (aniq hisob-kitob uchun) va 1,0 (himoya va umumiy o’lchash dasturlari uchun) da mavjud.
S6: RCT transformatorini sozlash mumkinmi?
J: Ha, RCT transformatorini turli tok nisbatlari, aniqlik sinflari va nominal yuklamalar bilan maxsus ishlatish talablariga moslashtirish mumkin.
S7: Majburiy ikkilamchi ishlash talablari qanday?
J: Tok uzatilayotganda TT ikkilamchi zanjirini ochmang. Ikkilamchi zanjirni loyiha amaliyotiga muvofiq qisqa tutash va yerga ulang. Hisob-kitob va himoya aniqligini ta’minlash uchun to’g’ri terminal polarligiga e’tibor bering.