Product Overview
The ZW8-12(G) is a 12 kV 50 Hz three-phase outdoor vacuum circuit breaker for rural distribution networks, urban grids and small power systems, controlling and protecting feeders against load, overload and short-circuit currents. A 630 A rated current combines with breaking capacities of 6.3, 12.5 and 20 kA, and the metal-enclosed, SMC-insulated design withstands severe pollution sites; the G variant integrates an isolating switch for visible sectionalising.
Product Display


Model Designation

Model format: ZW 8 − 12 G / 630 − □
- Z — Vacuum circuit breaker
- W — Outdoor type
- 8 — Design sequence number
- 12 — Rated voltage (kV)
- G — With integrated isolating switch
- /630 — Rated current (A)
- □ — Rated short-circuit breaking current (kA)
Service Conditions
- Ambient temperature: −40 °C to +40 °C
- Altitude: not exceeding 3000 m (insulation adjustments required above this)
- Pollution: suitable for Grade V environments including dust, smoke and salt mist
- Wind speed: not exceeding 34 m/s (equivalent to 700 Pa pressure)
- Negligible external vibration or seismic impact assumed; custom environments available on request
Construction
The ZW8-12(G) uses a three-phase pillar-type dry design with fully sealed construction and SMC insulating materials, giving high phase-to-phase and phase-to-ground insulation strength and reliable service in hot, humid climates. The metal-enclosed body houses the three-phase vacuum interrupters, and the G variant adds an integrated isolating switch so the unit can serve as a sectionaliser.
A CT23 spring-operated mechanism provides manual and electric operation, with primary terminals marked P1/P2 and secondary terminals S1/S2 for the built-in current transformers. A built-in potential transformer with per-phase fuses and a zero-sequence current transformer support metering and earth-fault protection.
Technical Data
| Item | Unit | 6.3 kA | 12.5 kA | 20 kA |
|---|---|---|---|---|
| Rated Voltage | kV | 12 | 12 | 12 |
| Rated Current | A | 630 | 630 | 630 |
| Rated Short-Circuit Breaking Current | kA | 6.3 | 12.5 | 20 |
| Rated Short-Circuit Making Current (peak) | kA | 16 | 31.5 | 50 |
| Rated Peak Withstand Current | kA | 16 | 31.5 | 50 |
| Rated Short-Time Withstand Current | kA | 6.3 | 12.5 | 20 |
| Lightning Impulse Withstand Voltage (peak) | kV | 75 | 75 | 75 |
| Power Frequency Withstand Voltage (1 min) | kV | 42 | 42 | 42 |
| Rated Operating Sequence | — | O-0.3s-C/O-180s-C/O | O-0.3s-C/O-180s-C/O | O-0.3s-C/O-180s-C/O |
| Mechanical Life | Operations | 10000 | 10000 | 10000 |
| Breaking Times at Rated Breaking Current | Times | 30 | 30 | 30 |
| Closing / Opening Voltage of Mechanism | V | 110, 220 | 110, 220 | 110, 220 |
| Contact Distance | mm | 11 ± 1 | 11 ± 1 | 11 ± 1 |
| Overtravel (contact spring compression) | mm | 3 ± 0.3 | 3 ± 0.3 | 3 ± 0.3 |
| Phase Discrepancy of Closing and Opening | ms | ≤ 2 | ≤ 2 | ≤ 2 |
| Contact Closing Bounce Time | ms | ≤ 2 | ≤ 2 | ≤ 2 |
| Average Closing Speed | m/s | 1.0 ± 0.2 | 1.0 ± 0.2 | 1.0 ± 0.2 |
| Average Opening Speed | m/s | 0.7 ± 0.15 | 0.7 ± 0.15 | 0.7 ± 0.15 |
| Opening Time at Max Operating Voltage | ms | 15-50 | 15-50 | 15-50 |
| Opening Time at Min Operating Voltage | ms | 30-60 | 30-60 | 30-60 |
| Closing Time | ms | 25-50 | 25-50 | 25-50 |
| Main Circuit Resistance per Phase | μΩ | ≤ 120 (with G ≤ 200) | ≤ 120 (with G ≤ 200) | ≤ 120 (with G ≤ 200) |
| Permitted Cumulative Contact Wear | mm | 3 | 3 | 3 |
| Weight | kg | 152 (with G 180) | 152 (with G 180) | 152 (with G 180) |
| Phase Centre Distance | mm | 175 ± 1.5 | 175 ± 1.5 | 175 ± 1.5 |
Standards
Manufactured and tested in accordance with IEC and GB standards for high-voltage AC circuit breakers, including IEC 62271-100 and GB 1984.
Installation & Dimensions
Installation Diagram


The breaker is mounted on a stable support structure with adequate clearance for operation and maintenance, and contact-blade alignment is verified during installation to avoid mechanical stress. Main components: contact blade, contact base, contact blade support, insulated pull rod, operating handle, isolating-switch support and circuit breaker.
| Dimension | Value (mm) |
|---|---|
| Phase Centre Distance | 175 ± 1.5 |
| Contact Distance | 11 ± 1 |
| Overtravel | 3 ± 0.3 |