Product Overview
The GND5-12 is an indoor rotary-type high-voltage AC disconnector with single-sided earthing for three-phase 50 Hz systems rated 12 kV. Under voltage but without load it isolates lines, prevents mal-operation and earths the de-energised circuit, giving reliable separation from the main bus when a circuit breaker or other component is serviced. The rotating knife and the built-in earth contacts combine isolation and protective earthing in one compact frame for metal-enclosed switchgear, offered in 630 A and 1250 A grades with 210 mm rated phase spacing.
Product Display


Model Designation

Model format: G N D 5 – 12 / □
- G – disconnector
- N – place of use: indoor
- D – single-sided earthing
- 5 – design sequence number
- 12 – rated voltage, kV
- □ – rated current, A (630 / 1250)
Service Conditions
- Ambient temperature: upper limit +40 °C, lower limit -15 °C
- Altitude: not above 1000 m; for higher altitude the rated insulation level is raised accordingly
- Seismic intensity: not above 8 degrees
- Relative humidity: daily average not above 95%, monthly average not above 90%
- Site free from fire, explosion hazard, severe pollution, chemical corrosion and severe vibration
Construction
Each pole uses a rotating contact system on support and live-part insulators, so the knives make a clear visible break within a compact indoor envelope. Built-in single-sided earth contacts, the D feature, allow the isolated side to be earthed for maintenance safety.
Operation is by a manual mechanism interlocked with the associated circuit breaker; the switch cannot break load or short-circuit current. It provides reliable separation from the main circuit when a circuit breaker or other component is serviced, protecting operating personnel.
Technical Data
| Item | Unit | GND5-12/630 | GND5-12/1250 |
|---|---|---|---|
| Rated voltage | kV | 12 | 12 |
| Rated frequency | Hz | 50 | 50 |
| Rated current | A | 630 | 1250 |
| Rated phase spacing | mm | 210 | 210 |
| 4 s rated short-time withstand current | kA | 25 | 31.5 |
| Rated peak withstand current | kA | 63 | 80 |
Standards
The source datasheet quotes no specific product standard for the GND5-12; the rated electrical data are taken from the type datasheet. The disconnector is supplied to the manufacturer’s works specification and the agreed technical requirements, with the single-sided earthing contacts and interlock checked before commissioning.
Installation & Dimensions
Installation Diagram

Fix the disconnector frame to the cubicle mounting plane at the 210 mm rated phase spacing through the four Ø 13 mounting holes, keeping the rotating knives and the single-sided earth contacts clear of obstructions. Couple the poles to the manual operating mechanism, then verify free travel and full seating of the main and earth contacts, the complete visible break, and bonding of the frame to the earth network before energising.
| Dimension | Value (mm) |
|---|---|
| Rated phase spacing | 210 |
| Overall width | 730 |
| Overall height | 490 |
| Frame height | 465 |
| Base section (end / pole / end) | 80 – 210 – 210 – 210 – 80 |
| Side view (width x height) | 440 x 160 |
| Top view depth | 250 |
| Mounting holes | 4 x Ø 13 |
| Min. cable bend radius | > R150 |