ZN63(VS1)-24kV Handcart Indoor High Voltage Vacuum Circuit Breaker - featured

ZN63(VS1)-24kV Handcart Indoor High Voltage Vacuum Circuit Breaker

ZN63(VS1)-24: 24kV Handcart Indoor Vacuum Circuit Breaker

  • 24 kV handcart VCB for metal-enclosed switchgear
  • Rated currents 630 A, 1250 A and 1600 A options
  • Breaking capacity 20-31.5 kA with 125 kV impulse
  • Spring mechanism, optional permanent-magnet drive
  • Racked center-mounted or fixed mounting structure
  • 20000-op life, 60000 op with permanent magnet

Product Overview

The ZN63(VS1)-24 is a three-phase 50 Hz handcart (center-mounted) indoor high-voltage vacuum circuit breaker rated 24 kV, used for control and protection in power plants, substations and industrial or mining distribution systems. Rated currents of 630 A, 1250 A and 1600 A pair with breaking capacities of 20 kA, 25 kA and 31.5 kA, suiting frequent operation and important loads, including high-altitude sites.

Product Display

ZN63(VS1)-24kV Handcart Indoor High Voltage Vacuum Circuit Breaker - display

ZN63(VS1)-24kV Handcart Indoor High Voltage Vacuum Circuit Breaker - display

ZN63(VS1)-24kV Handcart Indoor High Voltage Vacuum Circuit Breaker - poster_display

Model Designation

ZN63(VS1)-24kV Handcart Indoor High Voltage Vacuum Circuit Breaker - model

Model format: ZN 63 − 24 / □ − □

  • Z — Vacuum circuit breaker
  • N — Indoor installation
  • 63 — Design sequence number
  • 24 — Rated voltage (kV)
  • First □ — Rated current (A)
  • Second □ — Rated short-circuit breaking current (kA)

Example: ZN63(VS1)-24 / 1250 − 25 denotes a 24 kV indoor vacuum circuit breaker with 1250 A rated current and 25 kA rated short-circuit breaking current. ZN63 is the GB type code; VS1 is the equivalent common trade name.

Service Conditions

  • Ambient temperature: −40 °C to +40 °C
  • Altitude: not above 1000 m (higher sites require a correspondingly raised insulation level)
  • Seismic intensity: not above degree 8
  • Relative humidity: daily average ≤ 95%, monthly average ≤ 90%
  • Environment: free from fire, explosion hazard, serious pollution, chemical corrosion and violent vibration

Construction

The arc is extinguished in a sealed, maintenance-free vacuum interrupter, giving long electrical life with no fire or explosion risk. The standard spring energy-storage mechanism is charged from AC or DC 220 V / 110 V or manually and provides stored-energy closing with reliable interlocking; an optional permanent-magnet mechanism extends mechanical life to 60000 operations for very frequent duty.

A front-to-back split structure lets the breaker serve either as a fixed mounting unit or as a center-mounted handcart racked on a chassis inside metal-enclosed switchgear. The primary circuit connects to the busbar through static contacts or cable lugs, and the secondary circuit is wired to the control and protection loop through the terminal block.

Technical Data

Item Unit 20kA 25kA 31.5kA
Rated Voltage kV 24
Rated Frequency Hz 50
Rated Current A 630 1250 1600
Rated Short-Circuit Breaking Current kA 20 25 31.5
Rated Short-Circuit Making Current (Peak) kA 50 63 80
Rated Short-Time Withstand Current (4 s) kA 20 25 31.5
Lightning Impulse Withstand Voltage (across open contacts) kV 125
Power Frequency Withstand Voltage 1 min (across open contacts) kV 65
Rated Operating Sequence — O – 0.3 s – CO – 180 s – CO
Mechanical Life Operations 20000 (60000 with permanent-magnet mechanism)
Rated Energy-Storage and Operating Voltage V AC/DC 220, 110
Closing / Opening / Total Breaking Time ms ≤ 100 / ≤ 50 / ≤ 65
Breaking Operations at Rated Short-Circuit Current Times 20
Selection note: select the breaking-capacity variant from the prospective short-circuit current at the installation point and confirm the making and 4 s short-time withstand ratings are also satisfied.

Standards

Designed and type-tested to GB/T 1984 and IEC 62271-100 for AC high-voltage circuit breakers, with manufacturing and inspection in accordance with DL/T 403 for indoor high-voltage vacuum circuit breakers 3.6 kV to 40.5 kV.

Technical note: values beyond the published tables are subject to technical agreement; final parameters follow the nameplate and the approved specification.

Installation & Dimensions

Installation Diagram

ZN63(VS1)-24kV Handcart Indoor High Voltage Vacuum Circuit Breaker - installation

The breaker is supplied as a handcart (center-mounted) unit for metal-enclosed switchgear and can be moved between connected, test and disconnected positions for safe isolation, or installed as a fixed mounting unit using the split structure. The breaker and its frame must be reliably earthed before commissioning.

Outline Dimension (mm) 1250 A · 800 Cubicle 2000–3150 A · 1000 Cubicle
Overall Height (side view) 806 806
Front Frame Width 638 838
Front Panel Width 650 852
Front Base Width 681 881
Handcart Base Length (side view) 444 ± 2 730
Pole Spacing (vertical) 310 310
Safety notice: installation, operation and maintenance must be carried out by qualified personnel. Verify type, rated voltage, rated current and breaking current against the nameplate before energising, keep the breaker open, earthed and de-energised during service, and never bypass the interlocks or commission a breaker with a lost-vacuum interrupter.

FAQs

Z denotes a vacuum breaker, N indoor use, 63 the design number and 24 the rated voltage in kV; the two following boxes give rated current in amperes and rated short-circuit breaking current in kiloamperes. ZN63 is the GB type code and VS1 the equivalent common trade name.

The standard mechanism is a spring energy-storage type charged from AC or DC 220 / 110 V or manually, giving stored-energy closing and reliable interlocking. A long-life permanent-magnet mechanism is available as an option for extremely frequent operation.

The spring-mechanism breaker has a mechanical life of 20000 operations; with the optional permanent-magnet mechanism the mechanical life reaches 60000 operations for very frequent duty.

Both. The front-to-back split structure allows the breaker to be racked on a chassis as a center-mounted unit that can be moved to a disconnected position for isolation, or installed as a fixed mounting unit.

Calculate the prospective three-phase short-circuit current at the installation point and select 20, 25 or 31.5 kA to cover it, checking that the making and short-time withstand currents of 50 / 63 / 80 kA and 4 s are also satisfied.

Please state rated voltage, rated current, rated short-circuit breaking current, short-time duration, operating mechanism (spring or permanent-magnet), the switchgear cubicle width and whether a racked or fixed unit is required, and any special service conditions.

Inquiry for ZN63(VS1)-24kV Handcart Indoor High Voltage Vacuum Circuit Breaker:

Send your project requirements. Our team will reply with technical details and quotation.

Fast response Technical support OEM / ODM