LMZ-6/10, LM-6/10 Indoor Through Hole Current Transformer

LMZ-6/10, LM-6/10 Indoor Through Hole Current Transformer

Indoor through-hole epoxy resin cast current transformers for 6kV, 10kV, 11kV and 12kV switchgear

  • LMZ-6/10, LM-6/10 CTs for indoor air-insulated switchgear
  • 7.2/32/60kV insulation level for 6kV class and 12/42/75kV for 10kV-12kV class
  • Primary conductor passes through the central window
  • 5A or 1A secondary output, 0.5/1/3/10P classes
  • Wiring options: single, dual, tapped secondary & multi-core outputs

Product Overview

The LMZ-6 / LMZ-10 / LM-6 / LM-10 current transformer is an indoor, single-phase, epoxy resin cast, through-hole current transformer designed for air-insulated medium-voltage switchgear. It is used for current measurement, electric energy metering, feeder monitoring, and relay protection in 6kV, 10kV, 11kV, and 12kV class power systems with rated frequency of 50Hz or 60Hz.

This series is a busbar or conductor-through type current transformer. The primary conductor passes through the central window, while the secondary winding and magnetic core are encapsulated in epoxy resin casting insulation. The structure is compact and suitable for installation in air-insulated switchgear, ring main units, load switch panels, metering cabinets, and other indoor MV distribution equipment. The product can be supplied for measurement-only, protection-only, or combined measuring/protection applications according to project requirements.

Product Type

Item Specification
Product name Indoor Through-Hole Epoxy Resin Cast Current Transformer
Model series LMZ-6 / LMZ-10 / LM-6 / LM-10
Product structure Indoor single-phase, through-hole, epoxy resin cast current transformer
Voltage class 6kV, 10kV, 11kV, and 12kV medium-voltage systems
Rated insulation level 7.2/32/60kV for 6kV class; 12/42/75kV for 10kV-12kV class
Rated frequency 50Hz / 60Hz
Rated secondary current 5A or 1A according to project requirement
Rated primary current 50A to 630A reference range; customized ratios available by technical agreement
Application type Current measurement, energy metering, relay protection, and switchgear monitoring
Installation location Indoor air-insulated switchgear, RMU panels, metering cabinets, and distribution equipment
Applicable standard IEC 61869-1 / IEC 61869-2; IEC 60044-1 can be referenced for legacy projects

Product Display

Product Display

Applications

  • 6kV, 10kV, 11kV, and 12kV indoor medium-voltage distribution systems
  • Air-insulated switchgear, load switch cabinets, and ring main units
  • Current measurement and electric energy metering circuits
  • Relay protection and feeder monitoring circuits
  • Compact switchgear where the primary conductor passes through the CT window
  • MV metering assemblies requiring combined metering and protection secondary outputs

Features

  • Through-hole structure: The primary conductor or busbar passes through the central window, simplifying primary wiring and reducing primary winding complexity.
  • Epoxy resin casting: The magnetic core and secondary winding are encapsulated in cast resin to improve insulation strength, mechanical stability, and moisture resistance.
  • 6kV and 10kV versions: LMZ-6 / LM-6 are used for 6kV class systems, while LMZ-10 / LM-10 are used for 10kV, 11kV, and 12kV class switchgear applications.
  • Metering and protection outputs: The CT can be configured with 0.5 / 1 / 3 measuring classes and 10P protection output according to project requirements.
  • Compact circular body: The round through-hole body supports easy installation around busbars, conductors, or insulated primary parts in MV panels.
  • Customizable configurations: Non-standard current ratios, secondary current, burden, terminal layout, and winding configuration can be confirmed by technical agreement.

Working Principle

The LMZ / LM series current transformer operates according to electromagnetic induction. The primary conductor passing through the central window generates magnetic flux in the magnetic core. The secondary winding outputs a proportional current signal to measuring instruments, energy meters, protection relays, or monitoring devices. The epoxy resin casting provides insulation and mechanical protection for the secondary winding and core.

For metering applications, the transformer should maintain the required accuracy within the rated burden. For relay protection applications, the protection winding should provide a reliable secondary current signal under fault conditions and coordinate with the relay setting, rated burden, and system short-circuit requirement.

Model Designation

Model Designation

The model designation identifies the current transformer type, indoor structure, cast-resin insulation, and voltage class.

Code Meaning
L Current transformer
M Busbar / through-hole type structure
Z Cast-resin insulated structure
6 6kV class version, normally using 7.2/32/60kV insulation level
10 10kV class version, applicable to 10kV, 11kV, and 12kV systems with 12/42/75kV insulation level

Model coverage: This product page covers LMZ-6, LMZ-10, LM-6, and LM-10. Final selection should be confirmed according to system voltage, current ratio, accuracy class, rated output, insulation level, installation window, and switchgear drawing.

Technical Data

Item LMZ-6 / LM-6 LMZ-10 / LM-10
Voltage class 6kV class 10kV, 11kV, and 12kV class
Rated insulation level 7.2/32/60kV 12/42/75kV
Rated frequency 50Hz / 60Hz 50Hz / 60Hz
Rated primary current 50A to 630A reference range 50A to 630A reference range
Rated secondary current 5A or 1A 5A or 1A
Accuracy class 0.5 / 1 / 3; 10P protection available 0.5 / 1 / 3; 10P protection available
Rated output 3.75VA for measuring reference; 5VA for 10P reference 3.75VA for measuring reference; 5VA for 10P reference
Surface creepage distance 134mm reference 175mm reference
Weight Approx. 4kg Approx. 5kg
Insulation medium Epoxy resin casting insulation Epoxy resin casting insulation
Installation method Indoor through-hole conductor installation Indoor through-hole conductor installation

Terminal Marking

The LMZ / LM series can be supplied with single-core or multi-core secondary winding configurations. The wiring diagram may include single secondary output, dual secondary output, tapped secondary output, or multiple secondary groups according to the required metering and protection circuits.

Terminal Marking Function Application Note
P1 / P2 Primary direction marking The reference primary current direction is normally defined from P1 to P2 through the CT window.
S1 / S2 Single secondary winding Used for single measuring, metering, or protection output.
1S1 / 1S2 First secondary group Usually used for metering or measurement circuit.
2S1 / 2S2 Second secondary group Usually used for relay protection or additional monitoring circuit.
S1 / S2 / S3 Tapped secondary winding Used when a tapped secondary ratio or special wiring arrangement is required.

Terminal markings follow standard CT polarity conventions. Correct terminal identification shall be observed to ensure metering accuracy, relay protection performance, and safe maintenance. The secondary circuit must not be open-circuited when the primary circuit is energized.

Selection Table

Model Rated

Current

Ratio

Accuracy

Class &

Rated Output

10P

Rated

Output

Rated

Insulation

Level

Creepage

Distance

Weight
LMZ-6 / LM-6 50-630A / 5A or 1A 0.5 / 1 / 3: 3.75VA 10P: 5VA 7.2/32/60kV 134mm Approx. 4kg
LMZ-10 / LM-10 12/42/75kV 175mm Approx. 5kg

Note: The table is for preliminary engineering selection. If the required current ratio, accuracy class, burden, secondary current, creepage distance, insulation level, or terminal arrangement exceeds the listed range, final parameters shall be confirmed by technical agreement, approved drawing, nameplate, and factory test report.

Wiring Diagram

Wiring Diagram

The LMZ / LM series can support different secondary wiring arrangements according to metering and protection requirements. Typical configurations include one secondary winding, two independent secondary groups, tapped secondary outputs, and multi-core metering/protection outputs.

Service Conditions

  • Installation location: indoor medium-voltage switchgear
  • System voltage: 6kV, 10kV, 11kV, or 12kV class
  • Rated frequency: 50Hz / 60Hz
  • Ambient temperature: -5°C to +40°C reference range
  • Suitable for air-insulated switchgear with controlled humidity and pollution level
  • The installation site should be free from severe vibration, corrosive gas, explosive medium, heavy conductive dust, and abnormal condensation.
  • For high altitude, high humidity, coastal, high-pollution, or compact switchgear conditions, technical confirmation is recommended before ordering.

Standards and Compliance

The LMZ-6 / LMZ-10 / LM-6 / LM-10 current transformer can be supplied according to IEC 61869-1 and IEC 61869-2. IEC 60044-1 may be referenced for legacy project specifications. Routine tests, dielectric tests, polarity verification, ratio test, accuracy test, insulation resistance, and partial discharge requirements should be confirmed according to the final technical agreement.

Installation and Dimensions

Installation and Dimensions

The LMZ / LM series is designed for indoor through-hole installation. The central window, primary conductor size, secondary terminal box, mounting holes, creepage distance, and electrical clearances shall be confirmed according to the approved outline drawing before switchgear design or batch production.

Outline Data

Item Selection Note
Mechanical structure Indoor through-hole epoxy resin cast current transformer
Primary conductor Primary conductor, busbar, or insulated conductor passes through the central window
Secondary terminals Terminal block arrangement according to selected winding configuration
Mounting method Switchgear-mounted installation according to outline drawing
Drawing confirmation Final window size, outline, terminal direction, and mounting dimensions shall be confirmed before production

Safety Notes

  • Confirm the model, voltage class, current ratio, secondary current, accuracy class, rated output, insulation level, and wiring arrangement before installation.
  • Check the primary conductor diameter, busbar clearance, phase-to-ground clearance, and switchgear layout against the approved drawing.
  • Connect secondary terminals according to terminal markings and the project wiring diagram.
  • The secondary circuit of a current transformer must not be left open when the primary circuit is energized.
  • During meter or relay maintenance, short-circuit the CT secondary circuit before disconnecting any secondary wiring.
  • Secondary grounding shall follow the project specification and local electrical safety requirements.
  • Installation and maintenance shall be performed by qualified medium-voltage electrical personnel.

Ordering Info

Please provide the following information when ordering or requesting a quotation:

  • Product model: LMZ-6, LMZ-10, LM-6, or LM-10
  • System voltage: 6kV, 10kV, 11kV, or 12kV
  • Rated primary current / current transformation ratio
  • Rated secondary current: 1A or 5A
  • Accuracy class and rated output requirement
  • Protection class requirement, if 10P output is needed
  • Primary conductor diameter, busbar size, or through-hole size requirement
  • Wiring diagram requirement: single secondary, dual secondary, tapped secondary, or multi-core output
  • Insulation level and applicable IEC standard
  • Switchgear type, installation layout, terminal direction, and required outline drawing
  • Quantity, labeling, certificates, routine test reports, and packaging requirements

Selection Tips

  1. Confirm voltage class: Select LMZ-6 / LM-6 for 6kV systems and LMZ-10 / LM-10 for 10kV, 11kV, and 12kV systems.
  2. Check insulation level: Use 7.2/32/60kV for 6kV class and 12/42/75kV for 10kV-12kV class applications.
  3. Confirm primary conductor size: The conductor or busbar must match the CT window and the switchgear clearance requirement.
  4. Select secondary current: Choose 5A or 1A according to meter, relay, cable length, and burden calculation.
  5. Define accuracy requirement: Use 0.5 / 1 / 3 for measurement or metering and 10P for relay protection circuits.
  6. Confirm wiring diagram: Verify whether the project requires single secondary, dual secondary, tapped secondary, or multi-core output.
  7. Confirm drawings: Check outline dimensions, terminal direction, and installation space before production.

FAQs

It is used for current measurement, electric energy metering, feeder monitoring, and relay protection in indoor 6kV to 12kV medium-voltage switchgear systems.

LMZ-6 is used for 6kV class systems with 7.2/32/60kV insulation level, while LMZ-10 is used for 10kV, 11kV, and 12kV systems with 12/42/75kV insulation level.

A through-hole CT means the primary conductor or busbar passes through the central window of the current transformer. The CT senses the primary current and outputs a proportional secondary current.

The rated secondary current can be selected as 5A or 1A according to the connected meter, relay, cable length, and burden requirement.

Yes. Standard current ratios are available, and customized primary current ratios, secondary current, rated output, terminal arrangement, and wiring configuration can be supplied according to project requirements.

Yes. In addition to measuring classes such as 0.5, 1, and 3, the product can provide 10P protection output according to the selected configuration.

When the primary circuit is energized, an open secondary circuit may generate dangerous high voltage across the secondary terminals. The secondary circuit should be short-circuited before disconnecting meters, relays, or secondary wiring.