Mahsulotga umumiy ko’rib chiqish
LZZB8-35W / LZZBW8-35 / LZZBJ71-35W GY tashqi epoksiyli qattiq rezina tok transformatori — o’rta va yuqori kuchlanishli taqsimlash tizimlarida tokni o’lchash, energiya hisobini yuritish hamda releli himoya uchun mo’ljallangan 35 kV sinfli tashqi yuqori kuchlanishli tok transformatoridir. Xalqaro loyihalar uchun ushbu mahsulot oilasi 35 kV / 40,5 kV jihozlar sinfi sifatida tasvirlanishi kerak bo’lib, uning izolyatsiya darajasi 40,5/95/185 kV yoki IEC talablari asosida loyiha uchun belgilangan impulsga chidamlilik darajasiga ega bo’ladi.
Ushbu seriya yuqori yuzaki yo’l uzunligi (creepage distance) va kuchli ifloslanishga chidamliligi bilan ajralib turadigan 35 kV tashqi epoksiyli qattiq rezina tok transformatori sifatida pozitsiyalangan. Moyli temir korpusli tok transformatorlariga nisbatan u quruq turdagi, moydan xoli va texnik xizmat ko’rsatish jihatidan sodda. Kichikroq 24 kV tashqi epoksiyli tok transformatorlariga qaraganda esa u yuqori kuchlanish platformasi, kattaroq izolyatsiya masofasi, tashqi muhit uchun yuqori yuzaki yo’l talabi hamda qattiqroq atrof-muhit sharoitlari uchun mo’ljallangan.
Mahsulot turi


| Parametr | Xususiyatlari |
|---|---|
| Mahsulot nomi | Tashqi epoksiyli qattiq rezina tok transformatori |
| Model diapazoni | LZZB8-35W / LZZBW8-35 / LZZBJ71-35W GY |
| O’rnatish sharti | Tashqi |
| Tuzilma | To’liq yopiq ustunli / pillarli epoksiyli qattiq rezina tuzilma |
| Izolyatsiya vositasi | Tashqi foydalanish uchun epoksiy rezina, quruq turdagi izolyatsiya |
| Qo’llanilishi | Tokni o’lchash, energiya hisobini yuritish hamda releli himoya |
| Xalqaro kuchlanish sinfi | 35 kV / 40,5 kV sinfli yuqori kuchlanishli elektr tizimi |
| Nominal izolyatsiya darajasi | 40,5/95/185 kV standart; loyiha talabiga ko’ra 40,5/95/190 kV mavjud |
| Nominal ikkilamchi tok | 5 A yoki 1 A |
| Tashqi izolyatsiya xususiyati | Yuqori ifloslanishga chidamli versiyalarda yuzaki yo’l uzunligi 1200 mm dan ortiq |
Modelni izohlash

- L: Tok transformatori.
- Z: Ustunli / pillarli tuzilma.
- Z: Epoksiyli qattiq rezina izolyatsiyasi.
- B: Himoya g’altagi bilan jihozlangan / o’lchash va himoya uchun mo’ljallangan tok transformatorlari seriyasi.
- 8 / 71: Loyiha tartibi yoki ishlab chiqaruvchi tomonidan berilgan tuzilma kodi.
- 35: 35 kV nominal kuchlanish sinfi, odatda tizimning eng yuqori 40,5 kV kuchlanishiga mos keladi.
- W: Tashqi o’rnatish uchun.
- GY: Ba’zi ishlab chiqaruvchilar tomonidan foydalaniladigan tashqi yuqori kuchlanish / yuqori ifloslanishga chidamli tuzilma kodi.
- 5A yoki 1A: Nominal ikkilamchi tok varianti.
- Aniqlik sinfi: O’lchash uchun 0,2; 0,2S; 0,5; 0,5S kabi aniqlik sinflari hamda himoya uchun 5P yoki 10P kabi aniqlik sinflari loyiha talablariga qarab belgilanadi.
Qo’llanilish sohalari
- 35 kV / 40,5 kV tashqi podstantsiyalar va ulovchi baytlar
- Tashqi tok o’lchash hamda energiya hisobini yuritish nuqtalari
- UlOVCHILAR, transformatorlar va kondensator banklari uchun releli himoya
- Sanoat va kon-metallurgiya korxonalari uchun 35 kV elektr taqsimlash tizimlari
- Quyosh, shamol hamda energiya saqlash loyihalari uchun qayta tiklanadigan energiya podstantsiyalari
- Moyli o’lchov transformatorlarisiz tashqi elektr tarmog’iga ulanish nuqtalari
- Namlik, ifloslanish yoki dengiz yaqinidagi muhitlarda yuzaki yo’l uzunligini oshirish talab qilinadi
Xususiyatlari
- Tashqi quruq turdagi izolyatsiya: To’liq yopiq epoksiyli qattiq rezina quyish transformator moyini yo’q qiladi va sizish bilan bog’liq texnik xizmat ko’rsatish muammolarini kamaytiradi.
- 35 kV xalqaro kuchlanish platformasi: IEC uslubidagi loyihalar hamda xalqaro tender hujjatlari uchun 35 kV / 40,5 kV sinfi sifatida yoziladi.
- Yuqori yuzaki yo’l dizayni: Yuzaki yo’l uzunligi ifloslik, namlik hamda iz hosil bo’lishiga qarshi chidamlilikni oshirish uchun 1200 mm dan ortiq bo’lishi mumkin.
- Yuqori aniqlik: Hisob-kitob, o’lchash hamda monitoring dasturlari uchun 0,2; 0,2S; 0,5 va 0,5S kabi o’lchash sinflari qo’llab-quvvatlanadi.
- Himoyaning barqarorligi: Releli himoya, qisqa tutashuvni aniqlash hamda tarmoq nosozliklarini boshqarish uchun 5P va 10P himoya sinflari qo’llab-quvvatlanadi.
- Yuqori dinamik termal chidamlilik: Qisqa muddatli nosozlik toklari sharoitida elektr hamda mexanik barqarorlikni saqlash uchun mo’ljallangan.
- Moslashuvchan o’rnatish: Ustunli to’liq yopiq tuzilma ixcham, namlikka chidamli bo’lib, tashqi joylashtirish talablariga qarab o’rnatilishi mumkin.
Ish prinsipi
LZZB8-35W / LZZBW8-35 / LZZBJ71-35W GY tok transformatori 35 kV zanjirining yuqori birlamchi tokini standartlashtirilgan ikkilamchi tokka (odatda 5 A yoki 1 A) aylantiradi. Ikkilamchi chiqish o’lchov asboblari, relelar yoki monitoring jihozlari uchun ta’minlanadi. Epoksiyli qattiq rezina izolyatsiya tanasi yuqori kuchlanishli birlamchi zanjir hamda past kuchlanishli ikkilamchi zanjirlar orasida elektr ajratishni ta’minlaydi.
O’lchash uchun TK tanlangan aniqlik sinfi hamda nominal yuklama doirasida nisbat aniqligi hamda fazaviy siljishni saqlashi kerak. Himoya uchun himoya g’altagi talab qilingan aniqlik chegarasi doirasida nosozlik tok signallarini takrorlashi kerak. Shuning uchun tok nisbati, ikkilamchi tok, aniqlik sinfi, nominal quvvat, qisqa muddatli termal tok hamda dinamik tok birgalikda tanlanishi kerak.
Texnik ma’lumotlar
| Parametr | Xususiyatlari |
|---|---|
| Model diapazoni | LZZB8-35W / LZZBW8-35 / LZZBJ71-35W GY |
| Mahsulot turi | Tashqi epoksiyli qattiq rezina tok transformatori |
| Nominal kuchlanish sinfi | 35 kV / 40,5 kV |
| Nominal izolyatsiya darajasi | 40,5/95/185 kV standart; loyiha talabiga ko’ra 40,5/95/190 kV |
| Nominal chastota | 50 Hz yoki 60 Hz |
| Nominal birlamchi tok | 15 A dan 2000 A gacha standart diapazon |
| Nominal ikkilamchi tok | 5 A yoki 1 A |
| Aniqlik sinfi | 0,2; 0,2S; 0,5; 0,5S; 5P; 10P |
| Nominal quvvat | 10 VA, 20 VA yoki 50 VA standart; loyiha uchun maxsus yuklama mavjud |
| Quvvat koeffitsienti | cosφ = 0,8 orqaga siljish standarti |
| Ikkilamchi g’altaklar soni | Loyiha konfiguratsiyasiga qarab 1 dan 5 tagacha |
| Yuzaki yo’l uzunligi | Yuqori ifloslanishga chidamli versiyalarda 1200 mm dan ortiq |
| Ish harorati | -40°C dan +40°C gacha standart; boshqa diapazonlar kelishuv asosida |
| Dengiz sathidan balandligi | Berilgan ma’lumotlarga ko’ra ≤ 3000 m standart; yuqori balandlik loyiha tasdiqlashiga qarab |
| Ifloslanish sinfi | Ayrim versiyalar uchun IV-sinf standart; loyiha talabiga ko’ra 3 yoki 4-sinf |
| Taxminiy maksimal o’lchamlar | Bog’liq texnik ma’lumotlardan 435 × 610 × 330 mm standart |
| Qo’llaniladigan standartlar | IEC 61869-1, IEC 61869-2, GB/T 20840.1, GB/T 20840.2; kelishuv asosida eski IEC 185 / GB1208 standartlari ham qo’llanilishi mumkin |
Tanlov jadvali
Quyidagi jadval berilgan ma’lumotlardan qayta tashkil etilgan hamda veb-sayt namoyishi uchun optimallashtirilgan. Uzun sarlavhalar hamda takrorlanadigan qiymatlar jadvalning buzilishini oldini olish uchun soddalashtirilgan.
| Model | Nominal Birlamchi Tok (A) |
Aniqlik Sinfi Kombinatsiyasi |
Nominal Quvvat (VA) |
Nominal Qisqa Muddatli Termal Tok |
Nominal Dinamik Tok |
|---|---|---|---|---|---|
| LZZB8-35W | 15 | 0.2 / 10P10 0.5 / 10P10 |
0.2: 10VA 0.5: 20VA 10P10: 50VA |
2.25kA / 2s | 5.6kA |
| 20 | 3.0kA / 2s | 7.5kA | |||
| 30 | 4.5kA / 2s | 11.25kA | |||
| 40 | 6.0kA / 2s | 15kA | |||
| 50 | 7.5kA / 2s | 18.75kA | |||
| 75 | 0.2: 10VA 0.5: 20VA 10P10: 50VA |
11.25kA / 2s | 28kA | ||
| 100 | 15kA / 2s | 37.5kA | |||
| 150 | 31.5kA / 1s | 80kA | |||
| LZZB8-35W | 200 | 0.2 / 10P10 0.5 / 10P10 |
0.2: 10VA 0.5: 20VA 10P10: 50VA |
31.5kA / 2s | 80kA |
| 300 | 31.5kA / 3s | 80kA | |||
| 400 | 0.2: 15VA 0.5: 30VA 10P10: 50VA |
31.5kA / 3s | 80kA | ||
| 500 | 31.5kA / 3s | 80kA | |||
| 600 | 0.2: 15VA 0.5: 30VA 10P10: 50VA |
31.5kA / 4s | 80kA | ||
| 800 | 0.2: 50VA 0.5: 50VA 10P10: 50VA |
31.5kA / 4s | 80kA | ||
| 1000–2000 | 40kA / 4s | 100kA |
Eslatma: Jadval dastlabki tanlov uchun. Yakuniy tok nisbati, nominal quvvat, aniqlik sinfi, ikkilamchi g’altaklar soni, qisqa muddatli termal tok hamda dinamik tok nomplatakka, tasdiqlangan chizmaga hamda zavod sinov hisobotiga ko’ra tasdiqlanishi kerak.
Oddiy ish sharoitlari
| Parametr | Qiymat |
|---|---|
| O’rnatish joyi | Tashqi |
| Atrof-muhit harorati | -40°C dan +40°C gacha standart |
| Dengiz sathidan balandligi | ≤ 3000 m standart; loyiha talabiga ko’ra balandlik to’g’rilanishi kerak |
| Ifloslanish darajasi | Loyiha talabiga qarab 3-sinf / 4-sinf yoki IV-sinf standart |
| Atmosfera sharoiti | Tashqi namlik, ifloslik hamda izga chidamli izolyatsiya qo’llash uchun mos |
| O’rnatish sharti | Tasdiqlangan loyihaning chegaralaridan tashqari kuchli zarba, noaniq tebranish yoki mexanik yuklama bo’lmasa kerak |
O’rnatish hamda o’lchamlar

Mahsulot barqaror tashqi poydevorga, metall konstruksiyaga, ustunli qo’llab-quvvatlashga yoki podstantsiya kronshteyniga vertikal ravishda o’rnatilishi kerak. O’rnatishdan oldin poydevor o’rnatish teshiklari, birlamchi terminal yo’nalishi, o’tkazgich burchagi, yerlov nuqtasi, ikkilamchi terminal qutisi hamda kerakli elektr izolyatsiya masofasini tekshiring.
| O’lcham / O’rnatish elementi | Standart qiymat / Tavsiya etilgan tekshirish nuqtasi |
|---|---|
| Umumiy balandligi | Berilgan chizmadan taxminan 602 mm standart |
| Yuqori terminal yo’nalishi | Chizmada ko’rsatilgan 45° yo’nalish standarti |
| Old poydevor eni | Taxminan 240 ± 0,5 mm standart |
| Yon tananing eni | Taxminan 275 ± 0,5 mm / 295 mm standart |
| Maksimal tashqi kontur standarti | Bog’liq texnik ma’lumotlardan 435 × 610 × 330 mm standart |
| Terminal plastinkalari | 5–750/5 va 800–2000/5 tok diapazonlari uchun turli terminal plastinka o’lchamlari |
| O’rnatish teshiklari | To’rtta o’rnatish teshigi, Ø13 berilgan chizmadan standart |
| O’rnatishni tekshirish | Elektr energiyasini ulashdan oldin kronshteyn mustahkamligi, elektr izolyatsiya masofasi, yerlov hamda kabel chiqishini tekshiring. |
G’altaklar hamda terminal belgilari
Mahsulot bitta yoki bir nechta ikkilamchi g’altaklar bilan jihozlanishi mumkin. Odatiy terminal belgilari o’lchash hamda himoya zanjiri funksiyalariga mos keladi. Yakuniy terminal tartibi tasdiqlangan simlov sxemasi hamda nomplatakka amal qilishi kerak.
| Terminal belgilari | Funksiyasi | Qo’llash uchun eslatma |
|---|---|---|
| P1 / P2 | Birlamchi terminallar | Birlamchi tok yo’nalishi hamda polarlikka nisbatan standart sifatida ishlatiladi. |
| S1 / S2 | Bitta ikkilamchi g’altak | Bitta o’lchash yoki himoya chiqishi uchun ishlatiladi. |
| 1S1 / 1S2 | Birinchi ikkilamchi g’altak | Odatda o’lchash yoki tokni o’lchash uchun ajratiladi. |
| 2S1 / 2S2 | Ikkinchi ikkilamchi g’altak | Odatda releli himoya uchun ajratiladi. |
| 3S1 / 3S2 | Belgilangan holda qo’shimcha g’altak | Mustaqil monitoring, zaxira himoyasi yoki alohida o’lchash zanjiri uchun ishlatiladi. |
| Yerlov nuqtasi | Ikkilamchi / poydevor yerlovi | Ikkilamchi zanjirning bitta nuqtasi hamda transformator poydevori loyiha amaliyotiga ko’ra yerlovlanishi kerak. |
Standartlar hamda moslik
Yangi xalqaro hujjatlarda ushbu 35 kV tashqi epoksiyli qattiq rezina tok transformatorlari oilasi IEC 61869-1 hamda IEC 61869-2 standartlari asosida belgilanishi kerak. Xitoy standartlari hujjatlari uchun GB/T 20840.1 hamda GB/T 20840.2 foydalanilishi mumkin. Eski kataloglarda IEC 185, GB1208 yoki GB1208-1997 tilga olinishi mumkin; ular faqat tender yoki mijoz solishtirish hujjatlari talab qilganda eski standart sifatida saqlanishi mumkin.
Xavfsizlik eslatmalari
- O’rnatishdan oldin kuchlanish sinfi, izolyatsiya darajasi, tok nisbati, ikkilamchi tok, aniqlik sinfi hamda nominal yuklamani tekshiring.
- O’lchov asboblari yoki himoya relelarini ulashdan oldin P1 / P2 polarligi hamda ikkilamchi terminal belgilarini tekshiring.
- Elektr energiyasini ulashdan oldin tashqi elektr izolyatsiya masofasi, yuzaki yo’l uzunligi, o’rnatish mustahkamligi hamda o’tkazgichning mexanik yuklamasini tekshiring.
- Transformator poydevori hamda ikkilamchi zanjirning bitta nuqtasini podstantsiya yerlov loyihasiga ko’ra yerlovlang.
- Birlamchi tok oqayotganda TK ikkilamchi zanjiri ochiq zanjir bo’lishi mumkin emas.
- O’lchov asboblari, relelar yoki sinov jihozlarini uzishdan oldin ikkilamchi zanjirni tasdiqlangan qisqartirish qurilmasi bilan qisqartiring.
- Simlovdan keyin ikkilamchi terminal qutisini suv kirishini kamaytirish hamda tashqi ishonchlilikni saqlash uchun yoping.
- O’rnatish hamda ishga tushirish malakali yuqori kuchlanishli elektr mutaxassislari tomonidan amalga oshirilishi kerak.
Tanlov bo’yicha qo’llanma
- Kuchlanish platformasini tasdiqlang: Xalqaro IEC uslubidagi mahsulot sahifalari hamda tenderlar uchun 35 kV / 40,5 kV dan foydalaning.
- Izolyatsiya darajasini tasdiqlang: Standart sifatida 40,5/95/185 kV dan foydalaning; loyiha talab qilganda 40,5/95/190 kV dan foydalaning.
- Tuzilma kodini tanlang: Umumiy tashqi epoksiyli quyish turi uchun LZZB8-35W, tashqi yuqori kuchlanishli epoksiyli quyish turi uchun LZZBW8-35 hamda yuqori yuzaki yo’l hamda tashqi ifloslanishga chidamlilikni ta’kidlamoqchi bo’lsangiz LZZBJ71-35W GY dan foydalaning.
- Tok nisbatini tanlang: Birlamchi tokni ulovchi yuk, o’lchash diapazoni hamda releli himoya sozlamasiga moslang.
- Aniqlik kombinatsiyasini belgilang: Yuqori darajadagi o’lchash aniqligi uchun 0,2 / 0,2S, umumiy o’lchash uchun 0,5 / 0,5S hamda himoya uchun 5P / 10P dan foydalaning.
- Yuzaki yo’l talabini tekshiring: Iflos yoki nam hududlar uchun yuzaki yo’l uzunligini 1200 mm dan ortiq qiling yoki ifloslanish sinfiga qarab tasdiqlang.
- Chizmalarni tasdiqlang: Ishlab chiqarishdan oldin tashqi kontur o’lchamlari, birlamchi terminal burchagi, o’rnatish teshiklari, terminal qutisi tartibi hamda simlov sxemasini tasdiqlang.