LA-10Q, LFZ-10Q, LFZB1-10Q Wall-Through Cast Resin Current Transformer

LA-10Q, LFZ-10Q, LFZB1-10Q Wall-Through Cast Resin Current Transformer

10kV 11kV 12kV semi-enclosed and fully enclosed wall-through CT

  • 5-200/5A uses semi-enclosed resin casting for compact indoor switchgear
  • 300-1500/5A uses fully enclosed casting for higher-current circuits
  • Designed for humid, polluted and tropical indoor service conditions
  • Metering classes 0.2, 0.5, 1 and protection class 10P10 available
  • Current-ratio based structure selection with matching outline dimensions

Product Overview

The LA-10Q / LFZ-10Q / LFZB1-10Q current transformer is an indoor wall-through epoxy resin cast current transformer designed for medium-voltage AC power systems. It is used for current measurement, electric energy metering, feeder monitoring, and relay protection in indoor switchgear and distribution equipment. The product is designed for 10kV class systems and can be positioned for 10kV, 11kV and 12kV class international indoor applications when insulation coordination, service condition, and project standards are confirmed.

This product family is defined by two construction ranges. The 5-200/5A ratios use a semi-enclosed cast-resin structure, which is suitable for lower-current circuits and compact switchgear installation. The 300-1500/5A ratios use a fully enclosed cast-resin structure, providing stronger external insulation and better suitability for higher-current circuits. This makes the series suitable for all-condition indoor applications, including humid, polluted, condensation-prone, and tropical environments.

Product Type

Item Specification
Product name Indoor Semi-Enclosed and Fully Enclosed Wall-Through Cast Resin Current Transformer
Model series LA-10Q / LFZ-10Q / LFZB1-10Q
Product structure Wall-through type, epoxy resin casting insulation, reinforced Q-type structure
Structure range 5-200/5A: semi-enclosed type; 300-1500/5A: fully enclosed type
Voltage class 10kV class; applicable to 10kV, 11kV and 12kV class indoor systems by project confirmation
Rated insulation level 11.5/42/75kV
Rated secondary current 5A
Applications Current measurement, energy metering, relay protection, switchgear instrumentation

Product Display

Product Display

The catalogue identifies this series as LA-10Q, with corresponding designations LFZ-10Q and LFZB1-10Q. The selection shall be made according to current ratio, structure type, accuracy class, rated output, and confirmed outline drawing.

Applications

  • 10kV, 11kV and 12kV class indoor medium-voltage switchgear
  • Incoming and outgoing feeder panels in distribution rooms
  • Current measurement and electric energy metering circuits
  • Relay protection circuits requiring 10P10 performance
  • Indoor environments with humidity, condensation, surface dew point, or pollution requirements
  • Retrofit projects where older wall-through CT structures require dimensional and electrical review

Features

  • Two construction ranges: 5-200/5A adopts semi-enclosed casting, while 300-1500/5A adopts fully enclosed casting.
  • All-condition insulation design: The resin casting structure is suitable for indoor applications with humidity, surface condensation, or pollution considerations.
  • Wall-through installation: The product is designed for through-panel mounting in indoor switchgear and cabinet structures.
  • Reinforced Q-type structure: The stiffened construction improves mechanical support and external insulation performance.
  • Metering and protection classes: Accuracy classes include 0.2, 0.5, 1 and 10P10 for measurement and relay protection.
  • Current-ratio based selection: The current ratio directly affects structure type, outline dimensions, rated output, and short-circuit withstand data.

Principle

The LA-10Q / LFZ-10Q / LFZB1-10Q current transformer operates according to electromagnetic induction. Current flowing through the primary conductor generates magnetic flux in the core, and the secondary winding outputs a proportional 5A current signal to meters, relays, or monitoring devices. The resin casting insulation separates the medium-voltage primary circuit from the low-voltage secondary circuit.

For metering circuits, the selected accuracy class and VA output must match the connected meter and wiring burden. For protection circuits, the 10P10 core must maintain the required accuracy limit performance under fault-current conditions. Relay burden, cable resistance, and the required protection accuracy limit factor should be checked together.

Model Designation

The model code can be interpreted as follows:

Code Meaning
L Current transformer
A Wall-through type
10 Rated voltage class: 10kV class
Q Stiffening / reinforced type
LFZ-10Q Corresponding wall-through cast-resin CT designation
LFZB1-10Q Corresponding reinforced or fully enclosed wall-through cast-resin CT designation

Technical Data

Item Specification
Rated insulation level 11.5/42/75kV
Rated frequency 50Hz
Rated secondary current 5A
Primary current range 5/5A to 1500/5A
Structure by ratio 5-200/5A semi-enclosed; 300-1500/5A fully enclosed
Accuracy class 0.2, 0.5, 1 and 10P10
Burden power factor 0.8, lagging
Artificial pollution class Class 2
Partial discharge Apparent partial discharge not more than 50pC according to GB5583-85 and IEC44-4 reference
Installation type Indoor wall-through mounting

Selection Table

The following table uses current ratio as the main selection basis. The structure column clearly separates the semi-enclosed and fully enclosed ranges, so the product can be selected according to both electrical rating and cabinet installation requirement.

Current Ratio

Rated

Primary Current

Structure

Type

Accuracy

0.2

Output

Accuracy

0.5

Output

Class 1

Output

10P10

Output

1s Thermal

Current

Ith

Dynamic

Current

Idyn

5/5, 10/5, 15/5, 20/5, 30/5, 40/5, 50/5, 75/5, 100/5, 150/5, 200/5 Semi-enclosed
resin casting type
5-10VA 10VA 10VA 15VA 90 x In 160 x In
300/5, 400/5 Fully enclosed
resin casting type
15VA 25VA 25VA 15VA 75 x In 135 x In
500/5 Fully enclosed
resin casting type
15VA 25VA 25VA 15VA 60 x In 110 x In
600/5, 800/5, 1000/5, 1500/5 Fully enclosed
resin casting type
25VA 25VA 25VA 20VA 50 x In 90 x In

Note: The selection data is based on the catalogue table. Final current ratio, accuracy class, rated output, outline dimension, short-time withstand data, and partial discharge requirement shall be confirmed according to the approved drawing, nameplate, and factory test report.

Structure Range

Current Range Structure Engineering Meaning
5-200/5A Semi-enclosed resin casting Suitable for lower-current circuits where compact size, metering accuracy, and normal indoor insulation conditions are the main requirements.
300-1500/5A Fully enclosed resin casting Suitable for higher-current circuits requiring stronger external insulation, improved environmental resistance, and higher short-circuit withstand capability.

Protection Curve

The catalogue provides an accuracy limit factor curve for class 10P. For protection applications, relay burden, secondary cable resistance, and the required protection accuracy limit factor should be evaluated together. A larger secondary burden may reduce the available accuracy limit factor, so the selected CT output should be checked against the actual relay circuit burden.

Service Conditions

  • Installation location: indoor medium-voltage switchgear
  • Rated frequency: 50Hz
  • System voltage: 10kV class, with 10kV, 11kV and 12kV class project application subject to insulation confirmation
  • Suitable for indoor environments where condensation, surface dew point, or tropical humidity may need to be considered
  • Artificial pollution class: Class 2 reference
  • The installation environment should be free from severe vibration, explosive medium, corrosive gas, heavy conductive dust, and abnormal mechanical stress.

Standards and Compliance

The LA-10Q / LFZ-10Q / LFZB1-10Q current transformer catalogue references GB5583-85 and IEC44-4 for partial discharge related requirements, with apparent partial discharge not more than 50pC. For international projects, the applicable IEC / GB standard combination, routine test items, insulation requirements, and acceptance criteria should be confirmed in the technical agreement.

Installation and Dimensions

Installation and Dimensions

Installation and Dimensions

The product uses wall-through installation and includes different hole and overall dimension groups according to current range. The 5-200/5A and 300-1500/5A structures should not be treated as the same mechanical layout. Before switchgear production, the selected current ratio, structure type, mounting hole, terminal direction, conductor path, and clearance shall be checked with the approved outline drawing.

Dimensions

Current Range Dimension Group Installation Note
5-200/5A Semi-enclosed structure drawing group Use the lower-current hole dimension and overall dimension reference shown for the semi-enclosed version.
300-1500/5A Fully enclosed structure drawing group Use the higher-current outline drawing and confirm the L dimension according to current range.
300-400A L = 340mm reference Confirm against final drawing before cabinet drilling.
500-600A L = 410mm reference Confirm against final drawing before cabinet drilling.
800-1500A L = 370mm reference Confirm against final drawing before cabinet drilling.

Safety Notes

  • Confirm current ratio, structure type, accuracy class, rated output, and short-circuit withstand data before installation.
  • Use the correct semi-enclosed or fully enclosed outline drawing according to the selected current ratio.
  • Check cabinet cut-out, conductor clearance, mounting holes, terminal direction, and maintenance access before production.
  • The CT secondary circuit must not be open-circuited when the primary circuit is energized.
  • Before disconnecting instruments or protection relays, short-circuit the secondary circuit using a suitable shorting terminal.
  • Installation and maintenance shall be carried out by qualified medium-voltage electrical personnel.

Ordering Info

Please specify the following information when ordering:

  • Product model: LA-10Q / LFZ-10Q / LFZB1-10Q
  • Current ratio and rated secondary current
  • Structure type if required: semi-enclosed or fully enclosed
  • Accuracy class and rated output
  • Short-time thermal current and dynamic current requirements
  • Insulation level, pollution class, and service condition
  • Cabinet opening, mounting layout, terminal direction, and outline drawing requirement
  • Quantity, certificates, test reports, labeling, and packaging requirements

Selection Guide

  1. Confirm voltage class: Use this product for indoor 10kV class systems and international 11kV or 12kV class projects after insulation verification.
  2. Choose current ratio: Select the ratio according to feeder current, metering range, and protection settings.
  3. Select structure: Use semi-enclosed structure for 5-200/5A and fully enclosed structure for 300-1500/5A.
  4. Define core function: Select 0.2, 0.5, or 1 for metering/measurement, and 10P10 for protection circuits.
  5. Check burden: Confirm that the connected meter, relay, and cable burden do not exceed the selected VA output.
  6. Verify fault withstand: Match Ith and Idyn with the switchgear short-circuit level.
  7. Confirm drawing: Select the correct outline dimension group before drilling or cabinet fabrication.

FAQs

It is used for current measurement, energy metering, and relay protection in indoor medium-voltage switchgear and distribution systems.

The 5-200/5A range uses a semi-enclosed resin casting structure, while the 300-1500/5A range uses a fully enclosed resin casting structure. The fully enclosed type provides stronger external insulation and is used for higher-current circuits.

The current ratio should be selected according to feeder rated current, normal load range, metering requirement, and relay protection setting. The selected ratio also determines whether the semi-enclosed or fully enclosed structure is used.

The catalogue includes accuracy classes 0.2, 0.5, 1 and 10P10. Metering and measurement circuits normally use 0.2, 0.5 or 1, while relay protection circuits use 10P10.

The available protection accuracy limit factor depends on the secondary burden. If relay burden and cable resistance are too high, the CT may not maintain the required protection accuracy under fault-current conditions.

Check the selected structure type, current ratio, outline drawing, cabinet cut-out, mounting holes, terminal direction, conductor clearance, and maintenance access before switchgear production.

It can be considered for 10kV, 11kV and 12kV class indoor applications, but the final use must be confirmed by insulation level, applicable standard, service condition, and approved technical documentation.