LFZ2-10 Epoxy Resin Cast Multi-Turn-Through Current Transformer

LFZ2-10 Epoxy Resin Cast Multi-Turn-Through Current Transformer

10kV 11kV 12kV indoor multi-turn-through cast-resin CT for metering and protection

  • Multi-turn-through epoxy resin structure for indoor switchgear installation
  • Designed for 10kV class systems and international 11kV / 12kV applications
  • Semi-enclosed cast-resin body with mounting plate and earthing bolt
  • Suitable for current measurement, energy metering and relay protection
  • Vertical or horizontal mounting for different cabinet layouts

Product Overview

The LFZ2-10 current transformer is an indoor, semi-enclosed, multi-turn-through type epoxy resin cast current transformer for medium-voltage AC systems. It is designed for current measurement, electric energy metering, and relay protection in power systems with rated frequency of 50Hz and rated voltage class of 10kV. For international medium-voltage projects, the product can be positioned for 10kV, 11kV and 12kV class indoor switchgear applications, subject to insulation level, system design and project specification confirmation.

The LFZ2-10 series adopts a multi-turn primary winding structure with epoxy resin cast insulation. The primary winding and secondary winding are wound on the core, and the secondary winding assembly is cast into the resin body for insulation and mechanical protection. The product body includes a mounting plate, rating plate, warning plate, earthing bolt and mounting holes, allowing vertical or horizontal installation in indoor switchgear and cabinet structures.

Product Type

Item Specification
Product name Indoor Multi-Turn-Through Epoxy Resin Cast Current Transformer
Model series LFZ2-10
Product structure Semi-enclosed, multi-turn-through type, epoxy resin casting insulation
Voltage class 10kV, 11kV and 12kV class indoor medium-voltage systems
Rated frequency 50Hz
Installation Indoor switchgear; vertical or horizontal mounting
Typical applications Current measurement, electric energy metering, relay protection, switchgear instrumentation

Product Display

Product Display

Applications

  • 10kV, 11kV and 12kV class indoor medium-voltage distribution systems
  • Medium-voltage switchgear, metering cabinets and feeder panels
  • Current measurement and electric energy metering circuits
  • Relay protection circuits requiring a reliable secondary current signal
  • Indoor wall-through or panel-mounted CT applications
  • Industrial substations, distribution rooms and complete electrical equipment

Features

  • Multi-turn-through structure: The primary winding uses a constructed multi-turn-through design, suitable for medium-voltage current transformation where a compact indoor CT is required.
  • Epoxy resin cast insulation: The secondary winding and core assembly are cast with epoxy resin for insulation stability, mechanical protection and indoor environmental resistance.
  • Semi-enclosed construction: The structure provides practical insulation and protection while keeping the product suitable for switchgear mounting and installation access.
  • Vertical or horizontal mounting: The mounting plate and installation holes allow flexible installation according to the cabinet layout.
  • Clear terminal marking: Primary terminals are marked P1 / P2, and secondary terminals are marked according to the metering or protection winding configuration.
  • Metering and protection use: The product is suitable for current measurement, energy metering and relay protection in indoor medium-voltage systems.

Principle

The LFZ2-10 current transformer operates according to electromagnetic induction. The primary current passing through the multi-turn primary winding generates magnetic flux in the core. The secondary winding then outputs a proportional current signal to connected meters, relays or monitoring devices. The epoxy resin insulation separates the primary medium-voltage circuit from the secondary low-voltage measurement circuit.

For metering applications, the selected ratio and accuracy class should match the connected meter burden and required measurement range. For relay protection applications, the protection winding and burden must be coordinated with relay settings and expected fault-current conditions.

Model Designation

The model code can be interpreted as follows:

Code Meaning
L Current transformer
F Constructed multi-turn-through type
Z Epoxy resin casting insulation
2 Design sequence code
10 Rated voltage class: 10kV class

Technical Data

Item Specification
Rated voltage class 10kV class; applicable to 10kV, 11kV and 12kV class indoor systems by project confirmation
Rated frequency 50Hz
Insulation type Epoxy resin casting insulation
Product structure Semi-enclosed multi-turn-through type
Primary terminal marking P1 / P2
Secondary terminal marking S1 / S2 for metering winding; protection winding marking according to order configuration
Installation method Vertical or horizontal mounting with mounting plate and fixing holes
Service altitude Not over 1000m under standard service conditions
Ambient temperature -5°C to +40°C
Relative humidity Less than 85% at 20°C reference condition
Service environment No explosive atmosphere, severe vibration, corrosive vapor or insulation-damaging environment

Terminals

The outlet markings of LFZ2-10 follow standard current transformer polarity conventions. The primary terminals are marked as P1 / P2. For a single metering secondary winding, the secondary terminals are commonly marked as S1 / S2. If the product includes an additional protection secondary winding, the second secondary circuit can be marked separately according to the project requirement.

Terminal
Marking
Function Application
Note
P1 / P2 Primary terminals When primary current flows from P1 to P2, secondary current flows from S1 to the external circuit.
S1 / S2 Metering secondary winding Used for current measurement or electric energy metering circuits.
Protection secondary Relay protection winding Terminal marking depends on the selected protection winding configuration.
Earthing bolt Grounding point Used for product grounding according to the project wiring and safety requirements.

Selection Table

The final current ratio, accuracy class, rated output and protection configuration should be selected according to the connected meter, relay, secondary wiring burden and switchgear fault level. Long table headers are wrapped into multiple lines for responsive website display.

Selection

Item

Common

Requirement

Engineering
Note
Rated voltage 10kV class For 10kV, 11kV and 12kV class indoor systems, confirm insulation level and applicable standard.
Rated frequency 50Hz 60Hz applications should be confirmed separately before ordering.
Current ratio Project-specific Select according to load current, metering range and relay protection setting.
Secondary current 5A or 1A by order 5A is common for short secondary wiring; 1A may reduce burden for long wiring circuits.
Accuracy class Metering or protection class Specify each secondary winding separately when both metering and protection are required.
Rated burden Project-specific VA Total meter, relay and cable burden must not exceed the rated output of each secondary core.

Note: Final technical parameters shall be confirmed according to the nameplate, approved drawing, technical agreement and factory test report.

Service Conditions

  • Installation location: indoor medium-voltage switchgear
  • Altitude: not over 1000m under standard service conditions
  • Ambient temperature: -5°C to +40°C
  • Relative humidity: less than 85% at 20°C reference condition
  • The installation environment should be free from explosive atmosphere, severe vibration, corrosive vapor and insulation-damaging conditions.
  • For high altitude, high humidity, heavy pollution or special switchgear conditions, technical confirmation is recommended before ordering.

Standards and Compliance

The LFZ2-10 current transformer is designed for indoor medium-voltage current transformer applications. Project requirements may specify IEC or GB current transformer standards according to the final technical agreement. Routine inspection normally includes appearance inspection, ratio test, polarity verification, accuracy test, insulation resistance test and power-frequency withstand test where required.

Installation and Dimensions

Installation and Dimensions

Installation and Dimensions

The LFZ2-10 current transformer can be installed vertically or horizontally according to the switchgear layout. The product body includes a mounting plate, rating plate, warning plate, earthing bolt and four mounting holes. Before cabinet production, the mounting position, primary conductor path, secondary terminal direction and insulation clearance should be confirmed with the approved outline drawing.

Dimensions

Item Dimension / Note
Installation direction Vertical or horizontal installation
Mounting structure Mounting plate with four fixing holes
Primary connection Primary terminals P1 / P2 according to product drawing
Secondary connection Secondary terminal block according to metering/protection configuration
Drawing confirmation Final outline and hole dimensions shall be confirmed before cabinet production

Safety Notes

  • Confirm the model, voltage class, current ratio, secondary current, accuracy class and rated burden before installation.
  • Check mounting plate position, conductor clearance, secondary terminal access and earthing arrangement before assembly.
  • Install the transformer vertically or horizontally according to the approved switchgear layout.
  • Connect primary and secondary terminals according to terminal markings and the project wiring diagram.
  • The secondary circuit of a current transformer must not be open-circuited when the primary circuit is energized.
  • Before disconnecting meters or relays, short-circuit the CT secondary circuit using an approved shorting block.
  • Installation and maintenance shall be performed by qualified medium-voltage electrical personnel.

Ordering Info

Please provide the following information when ordering or requesting a quotation:

  • Product model: LFZ2-10
  • Rated voltage and system voltage class
  • Rated primary current and rated secondary current
  • Accuracy class and rated burden for each secondary winding
  • Metering or relay protection application requirement
  • Installation direction: vertical or horizontal
  • Installation drawing, mounting hole requirement and terminal direction
  • Service condition if altitude, humidity, pollution level or vibration requirement is special
  • Quantity, certificates, test reports, labeling and packaging requirements

Selection Guide

  1. Confirm voltage class: Select LFZ2-10 for indoor medium-voltage systems around 10kV class, including international 10kV, 11kV and 12kV class applications after insulation confirmation.
  2. Confirm structure: Use this model when a multi-turn-through epoxy resin cast CT is required for indoor switchgear.
  3. Select current ratio: Choose the current ratio according to feeder load, metering range and protection setting.
  4. Specify core function: Define whether the secondary winding is used for measurement, energy metering or relay protection.
  5. Check burden: The total burden of meters, relays and secondary wiring should not exceed the rated output of the CT.
  6. Confirm drawing: Check mounting plate, hole positions, conductor path, terminal direction and maintenance access before production.

FAQs

It is used for current measurement, electric energy metering and relay protection in indoor medium-voltage switchgear and distribution systems.

Multi-turn-through type means the primary circuit uses a constructed winding or multiple turns through the magnetic core. This helps match lower or project-specific primary current ratings while maintaining the required secondary output.

It can be considered for 10kV, 11kV and 12kV class indoor applications only after confirming insulation level, system voltage, applicable standard and approved drawing. Final selection shall follow the nameplate and technical agreement.

The current ratio should be selected according to feeder rated current, normal load range, metering requirement and relay protection setting. The selected ratio should provide sufficient accuracy without unnecessary oversizing.

Yes. The product can be installed vertically or horizontally. The final installation direction should follow the cabinet layout, primary conductor direction, terminal access and approved outline drawing.

When the primary circuit is energized, an open CT secondary circuit may generate dangerous high voltage across the secondary terminals. This can damage insulation and create safety risks. The secondary circuit should be short-circuited before disconnecting meters or relays.

Please provide the model, voltage class, current ratio, secondary current, accuracy class, rated burden, installation direction, mounting drawing, terminal direction, service conditions and required test documents.