LZZBJ9-12/175b/2S, AS12 Indoor Epoxy Cast-Resin Current Transformer

LZZBJ9-12/175b/2S, AS12 Indoor Epoxy Cast-Resin Current Transformer

12kV indoor cast-resin CT with 175b/2S dual-secondary structure

  • 175b support body for medium-width switchgear installation
  • Also supplied as AS12/175b/2S for IEC-style 12kV projects
  • Two secondary circuits for metering and relay protection
  • 1A or 5A output with project-based burden and accuracy classes
  • Optional live display device for suitable two-secondary configurations

Product Overview

The LZZBJ9-12/175b/2S current transformer, also referenced as AS12/175b/2S is an indoor epoxy resin cast, fully enclosed, post-type current transformer designed for medium-voltage switchgear applications. It is used for current measurement, electric energy metering, feeder monitoring and relay protection in 10kV, 11kV and 12kV class power systems.

The 175b version is positioned as a medium-width support CT for switchgear layouts that need more terminal clearance and stronger primary-connection space than compact body designs. Its epoxy resin casting integrates insulation, mechanical support and environmental protection into one body, helping the CT maintain stable performance in indoor cabinets exposed to humidity, dust or long-term thermal cycling.

Product Type

Item Specification
Product name Indoor Epoxy Resin Cast Current Transformer
Model series LZZBJ9-12/175b/2S / AS12/175b/2S
Structure Indoor, fully enclosed, post-type, epoxy cast-resin insulated structure
Voltage class 10kV, 11kV and 12kV class medium-voltage systems
Rated insulation level 12/42/75kV
Rated frequency 50Hz / 60Hz
Secondary current 5A or 1A
Secondary structure 2S two-secondary configuration
Installation Indoor switchgear / center-mounted switchgear installation
Applications Current measurement, energy metering, relay protection and feeder monitoring

Product Display

LZZBJ9-12/175b/2S, AS12 Indoor Epoxy Cast-Resin Current Transformer Product Display

Applications

  • Indoor 12kV-class switchgear used in 10kV, 11kV and 12kV distribution networks
  • Center-mounted or withdrawable switchgear requiring post-type CT installation
  • Metering cabinets where one secondary circuit is used for measurement or energy metering
  • Protection panels where the second secondary circuit is connected to feeder or transformer protection relays
  • Retrofit projects needing a 175b body size with confirmed mounting and terminal layout
  • Switchgear designs requiring optional live display device coordination

Features

  • 175b medium-width body: Provides more practical space for primary terminal arrangement and busbar connection than compact-width variants.
  • Epoxy resin cast insulation: The fully enclosed insulation body improves moisture resistance, surface insulation stability and mechanical protection inside switchgear.
  • Two-secondary design: The 2S arrangement is suitable for combined metering and protection circuits without requiring a larger multi-core CT body.
  • Reliable primary fastening: The primary conductor is tightened by bolts during installation, supporting stable contact resistance and reducing connection heating risk.
  • Optional live display interface: For projects with no more than two secondary windings, a live display device can be integrated according to the cabinet scheme.
  • IEC-style 12kV application: Suitable for international 10kV, 11kV and 12kV class networks using 12/42/75kV insulation coordination.

Principle

During operation, the primary current passes through the primary conductor path and establishes magnetic flux in the CT core. The secondary winding converts this magnetic flux into a standardized low-current signal for meters, relays or monitoring devices. The cast-resin body provides the required insulation distance between the medium-voltage primary side and the low-voltage secondary side.

For the 175b/2S configuration, the two secondary circuits can be assigned to different functions. One core may be used for accurate measurement or energy metering, while the other may be selected for protection duty. The rated burden, accuracy class and short-circuit withstand values must be checked together to avoid accuracy loss or protection misoperation.

Model Designation

LZZBJ9 12 172B 2S current transformer modle type 1

The model code can be interpreted as follows:

Code Meaning
L Current transformer
Z Indoor type / post-type structure
Z Epoxy resin cast insulation / fully enclosed structure
B With protection level
J Strengthened design
9 Design serial number
12 Maximum operating voltage / 12kV class
175b Nominal width / structure dimension code
2S Secondary schematic code / two-secondary configuration
AS12 Alternative 12kV series designation for the same indoor epoxy cast-resin CT platform

Technical Data

Item Specification
Rated voltage class 10kV, 11kV and 12kV class indoor systems
Rated insulation level 12/42/75kV
Rated frequency 50Hz / 60Hz
Rated primary current 1A to 1200A reference range according to sample data; other ratios subject to agreement
Rated secondary current 5A or 1A
Accuracy combination 0.2S/10P, 0.2/10P, 0.5/10P, 0.2S/0.5, 0.5/0.5 or project-specific metering/protection combinations
Rated output 10VA / 20VA / 30VA reference according to current ratio, accuracy class and core configuration
Ambient temperature -5°C to +40°C
Insulating medium Epoxy resin
Installation type Indoor support-type / switchgear installation
Applicable standards GB 20840.1-2010, GB 20840.2-2014, IEC 61869-2:2012 and special project requirements

Terminals

The 2S schematic structure indicates a two-secondary arrangement. The product may be supplied with separate secondary circuits for metering and protection. Typical terminal markings include P1 / P2 for the primary side and 1S1 / 1S2, 2S1 / 2S2 for secondary cores. Final terminal arrangement shall be confirmed according to the approved drawing and nameplate.

Terminal
Marking
Function Application
Note
P1 / P2 Primary terminals Primary current direction and busbar connection shall follow the project wiring diagram.
1S1 / 1S2 First secondary core Usually used for metering, measurement or the first specified secondary circuit.
2S1 / 2S2 Second secondary core Usually used for relay protection or additional monitoring circuit.
Live display terminal Optional voltage indication device Available when the secondary winding quantity is two or less and the project requires live display indication.

Selection Table

The following table is arranged by rated primary current range and common metering/protection configurations. Long accuracy and output data are wrapped into multiple lines to improve readability on website pages and mobile layouts.

Rated

Primary

Current (A)

Accuracy

Class

Combination

Rated

Output(VA)

Short-Time

Thermal

Current

Rated

Dynamic

Current (kA)

1 0.2S / 10P
0.2 / 10P
0.5 / 10P
0.2S / 0.5
0.5 / 0.5
10 / 20
10 / 30
20 / 20
1.0kA 2.5
10 5kA 12.5
20 10kA 25
30 12kA 30
40 16kA 40
50 10 / 20
10 / 30
20 / 20
20 / 30
18kA 45
60 20kA 50
75 31.5kA 80
100 45kA 112.5
150–300 45kA 112.5
400–600 63kA 150
800–1200 80kA 180

Note: The above values are for technical selection reference. If project requirements exceed the listed range, final parameters shall be confirmed by agreement between manufacturer and purchaser. Nameplate data, approved drawings and factory test reports shall prevail.

Structure Reference

Structure Application
Reference
Selection
Note
175b Medium-width support structure Suitable for switchgear layouts requiring stronger body support and larger internal clearance than compact 150b designs.
2S Two-secondary schematic arrangement Used for metering/protection or dual-secondary requirements.
Live display option Optional device integration Can be added when the secondary winding quantity is two or less and the project requires voltage indication.

Service Conditions

  • Installation location: indoor medium-voltage switchgear
  • System voltage: 10kV, 11kV and 12kV class networks
  • Rated frequency: 50Hz / 60Hz
  • Ambient temperature: -5°C to +40°C
  • The installation environment should be free from severe vibration, conductive dust, corrosive gas, explosive medium, heavy pollution and abnormal condensation.
  • For high altitude, humid, coastal, high-pollution or special switchgear conditions, technical confirmation is required before ordering.

Standards and Compliance

The LZZBJ9-12/175b/2S current transformer can be supplied according to GB 20840.1-2010, GB 20840.2-2014, IEC 61869-2:2012 and special project requirements. Routine tests typically include ratio test, polarity verification, accuracy test, dielectric withstand test, insulation inspection and appearance inspection. Additional project-specific test documents can be confirmed according to the technical agreement.

Installation and Dimensions

LZZBJ9 12 172B 2S current transformer installation size

The product adopts an indoor support-type structure with top primary terminals and lower secondary terminal arrangement. The 175b structure shall be selected according to switchgear mounting space, terminal direction, busbar clearance and secondary terminal access. The approved drawing shall be used before switchgear production or replacement.

Dimensions

Item Dimension / Note
Structure code 175b support-type design
Secondary schematic 2S two-secondary arrangement
Primary terminal arrangement Confirmed according to current ratio and approved drawing
Secondary terminal arrangement Terminal box / lower terminal block according to drawing
Mounting holes Confirmed according to outline drawing
Drawing confirmation Required before switchgear production or replacement

Safety Notes

  • Confirm model, current ratio, secondary current, accuracy combination, rated output and insulation level before installation.
  • Check mounting space, busbar connection, primary terminal position, secondary terminal layout and phase clearance before assembly.
  • Tighten the primary bolts properly during installation to ensure reliable electrical contact.
  • Use the approved drawing for the selected 175b/2S structure and terminal arrangement.
  • Connect P1/P2 and secondary terminals according to polarity markings and the project wiring diagram.
  • The secondary circuit of a current transformer must not be open-circuited when the primary circuit is energized.
  • Before disconnecting meters or relays, short-circuit the secondary circuit through an approved shorting terminal block.

Ordering Info

  • Product model: LZZBJ9-12/175b/2S or AS12/175b/2S
  • Rated primary current and rated secondary current
  • Accuracy class combination and rated output for each secondary core
  • Rated insulation level and applicable standard
  • Required short-time thermal current and dynamic current
  • Secondary core quantity, schematic code and terminal marking requirement
  • Live display device requirement if needed
  • Switchgear layout, mounting dimensions and primary terminal direction
  • Quantity, certificates, routine test reports, labeling and packaging requirements

Selection Guide

  1. Confirm naming: Use LZZBJ9-12/175b/2S or AS12/175b/2S according to the project document, drawing and nameplate requirement.
  2. Check cabinet fit: Verify whether the 175b body size matches the switchgear depth, busbar position and secondary terminal access.
  3. Define two secondary circuits: Assign each secondary core clearly, such as measurement + protection or metering + protection.
  4. Select ratio and burden: Match the primary current, secondary current and rated burden with the connected instruments, relays and cable length.
  5. Confirm protection duty: Check protection accuracy class and short-circuit withstand level against relay setting and switchgear fault current.
  6. Review live display need: Confirm whether the optional live display device is required and whether it is compatible with the selected two-secondary arrangement.
  7. Approve drawing first: Confirm primary terminal spacing, mounting holes, terminal box position and polarity markings before production.

FAQs

Yes. AS12/175b/2S can be used as an alternative model designation for the same 12kV indoor epoxy cast-resin CT platform. The final naming should follow the nameplate, approved drawing and project specification.

The 175b/2S structure is suitable for indoor switchgear that requires a medium-width support CT body with two secondary circuits, commonly used for one metering or measurement core and one protection core.

Yes. With 12/42/75kV insulation coordination, it is suitable for common international 10kV, 11kV and 12kV class indoor medium-voltage switchgear applications.

The live display option can be considered when the project requires voltage indication and the secondary winding quantity is two or less. The interface and wiring arrangement must be confirmed on the approved drawing.

Each secondary core should be specified separately, including secondary current, accuracy class, rated output and function. Typical configurations include metering plus protection or measurement plus protection.

Proper primary bolt tightening helps maintain reliable electrical contact, reduces contact resistance and lowers the risk of heating at the primary connection during long-term switchgear operation.

Please confirm the model name, current ratio, 1A or 5A secondary output, accuracy class, rated burden, live display requirement, terminal markings, mounting dimensions, Ith/Idyn requirement and required test certificates.