Mahsulotga umumiy ko’rib chiqish
LMZBJ17-12 / LMZBJ17-12Q / 170 tokli transformator — o’rta kuchlanishli kommutatsion qurilmalar uchun ichki bir fazali epoksidli quyishli sim yoki shinali o’tkazgichli tokli transformator hisoblanadi. U 50 Hz yoki 60 Hz nominal chastotali o’zgaruvchan tok tizimlarida tokni o’lchash, elektr energiyasini hisoblash, liniya monitoringi va releli himoya uchun mo’ljallangan. Xalqaro loyiha hujjatlarida ushbu mahsulot 10 kV, 11 kV va 12 kV sinfli ichki kommutatsion qurilmalar uchun izolyatsiya muvofiqlik darajasi, tizim dizayni va loyiha talablari asosida qo’llanilishi mumkin.
Ushbu birlashtirilgan sahifa LMZBJ17-12Q / 170 va LMZBJ17-12Q/L modellarining texnik ma’lumotlarini bitta mahsulot sifatida birlashtiradi. Ikkalasi ham bir xil ichki epoksidli quyishli tokli transformator platformasiga tegishli bo’lib, kabel, mis sterjen yoki shina o’tkazish uchun katta bo’sh teshikdan foydalanadi. Farqi asosan o’rnatish o’lchamlari, teshik joylashuvi va L-o’lcham / mahkamlash tuzilmasida, elektr tanlov mantiqi esa o’xshash: 1A yoki 5A ikkilamchi chiqish, 12/42/75 kV izolyatsiya darajasi hamda loyiha talablariga ko’ra hisoblash/himoya aniqlik kombinatsiyalari.
Transformator korpusi epoksid smola bilan to’liq qoplangan. Birlamchi o’tkazgich markaziy teshik orqali o’tadi, magnit yadro va ikkilamchi o’ramalar esa smola korpusi ichida joylashgan. Bunday tuzilma ishonchli izolyatsiya, barqaror ikkilamchi chiqish hamda ixcham ichki o’rnatish talab qilinadigan yuqori tokli liniya zanjirlari, kirish paneli, shina hisoblagichi va himoya zanjirlari uchun mos keladi.
Mahsulot turi
| Element | Xususiyat |
|---|---|
| Mahsulot nomi | Ichki epoksid quyishli sim/shina o’tkazgichli tokli transformator |
| Model seriyasi | LMZBJ17-12 / LMZBJ17-12Q / 170 |
| Variyantlarning ko’rsatkichlari | LMZBJ17-12Q / 170 va LMZBJ17-12Q/L |
| Tuzilma | Katta bo’sh teshikli to’liq yopiq epoksid quyishli korpus |
| Kuchlanish sinfi | 10 kV, 11 kV va 12 kV sinfli ichki o’rta kuchlanishli tizimlar |
| Nominal izolyatsiya darajasi | 12/42/75 kV |
| Nominal chastota | 50 Hz / 60 Hz |
| Nominal ikkilamchi tok | 5 A yoki 1 A |
| Nominal birlamchi tok | 1500 A, 2000 A, 3000 A, 4000 A, 5000 A |
| Qo’llaniladigan standartlar | GB20840.1-2010, GB20840.2-2014, IEC61869-2:2003 hamda mijozning maxsus talablari |
Mahsulot namoyishi


LMZBJ17-12 seriyasi silindrsimon epoksid quyishli korpusga, kvadrat mahkamlash poydevoriga, katta markaziy teshikka ega bo’lib, ikkilamchi terminal bloklari old tomonda joylashgan. Birlamchi sim yoki shina teshik orqali o’tadi, ikkilamchi terminal esa hisoblagichlar, himoya releylari, monitoring qurilmalari yoki avtomatlashtirish tizimlariga ulanadi.
Qo’llash sohalari
- 10 kV, 11 kV va 12 kV sinfli ichki o’rta kuchlanishli kommutatsion qurilmalar
- Yuqori tokli liniya shkafchalari, kirish shkafchalari, chiqish panellari va hisoblagich shkafchalari
- Tokni o’lchash va elektr energiyasini hisoblash zanjirlari
- 5P10, 5P15, 5P20, 5P25 yoki 5P30 himoya xususiyatlarini talab qiluvchi releli himoya zanjirlari
- Ichki taqsimlash tizimlarida sim/shina orqali tok sezgichlari
- Sanoat transformator stansiyalari, tijorat taqsimlash xonalari, kommunal loyihalar hamda OEM kommutatsion qurilmalar to’plamlari
Xususiyatlari
- Birlashtirilgan 170-turli platforma: Veb-sayt kontenti va mahsulot tanlovida LMZBJ17-12Q / 170 va LMZBJ17-12Q/L bir mahsulot oilasi sifatida qaraladi.
- Katta bo’sh teshik: O’tkazgich teshikli konstruktsiya yuqori tokli zanjirlarda sim, mis sterjen yoki shina o’rnatish imkonini beradi.
- To’liq yopiq epoksid smola quyish: Quyishli korpus izolyatsiya mustahkamligi, mexanik barqarorlik hamda ishonchli ichki xizmat ko’rsatishni ta’minlaydi.
- 5A va 1A ikkilamchi variantlari: Mahsulot an’anaviy 5A ikkilamchi zanjirlarni ham, past yuklama yoki uzunroq ikkilamchi simlar uchun 1A tizimlarini ham qo’llab-quvvatlaydi.
- Yuqori tok diapazoni: Nominal birlamchi tok variantlari katta liniya va shina uchun 1500 A dan 5000 A gacha qamrab oladi.
- Hisoblash va himoya kombinatsiyalari: Mahsulot 0.2S / 0.5 hisoblash yadrolari hamda 5P10 dan 5P30 gacha himoya yadrosi kombinatsiyalarini qo’llab-quvvatlaydi.
- O’lcham variantlari: Q/170 va Q/L variantlari kommutatsion qurilmalar tartibini moslashtirish uchun turli tashqi ko’rinish ko’rsatkichlari va L-o’lcham variantlarini taqdim etadi.
Prinsipi
LMZBJ17-12 tokli transformatori elektromagnit induksiya prinsipiga asoslanadi. Birlamchi sim, mis sterjen yoki shina markaziy teshik orqali o’tib, birlamchi tokni olib boradi. Tok ichki yadrodagi magnit oqimini hosil qiladi va ikkilamchi o’ramaga ulangan hisoblagichlar, himoya releylari yoki monitoring qurilmalari uchun proporsional 5A yoki 1A signalini hosil qiladi.
Hisoblash uchun foydalanishda tokli transformator tanlangan yuklama ostida nisbat va fazani aniqlik darajasini saqlashi kerak. Himoya uchun foydalanishda 5P-sinfli himoya yadrosi nosozlik toklari sharoitida ishonchli tok signali berishi kerak. Aniq o’lchash va ishonchli himoya ishlashi uchun ikkilamchi tok, aniqlik kombinatsiyasi, nominal quvvat hamda yuklamani to’g’ri tanlash muhimdir.
Model belgilash
| Kod | Ma’nosi |
|---|---|
| L | Tokli transformator |
| M | Shina / sim o’tkazgichli tuzilma |
| Z | Epoksid smola izolyatsiyasi |
| B | Himoya sinfi konfiguratsiyasi mavjud |
| J | Kuchaytirilgan / mustahkamlangan tuzilma seriyasi |
| 17 | Dizayn ketma-ketligi kodi |
| 12 | Nominal kuchlanish sinfi: 12 kV |
| Q | Kuchaytirilgan tur / tuzilma varianti |
| 170 / L | Variant tanlovida foydalaniladigan teshik yoki o’rnatish o’lchami ko’rsatkichi |
Texnik ma’lumotlar
| Element | Xususiyat |
|---|---|
| Nominal kuchlanish sinfi | 12 kV sinfi; loyiha tasdiqlashiga ko’ra 10 kV, 11 kV va 12 kV sinfli ichki tizimlar uchun mos |
| Nominal izolyatsiya darajasi | 12/42/75 kV |
| Nominal chastota | 50 Hz / 60 Hz |
| Nominal ikkilamchi tok | 5 A yoki 1 A |
| Nominal birlamchi tok | 1500 A, 2000 A, 3000 A, 4000 A, 5000 A |
| Aniqlik sinfi | 0.2S, 0.5, 5P10, 5P15, 5P20, 5P25, 5P30 |
| Nominal quvvat | Nisbat, ikkilamchi tok va aniqlik kombinatsiyasiga qarab 10 VA dan 75 VA gacha |
| Atrof-muhit harorati | -25°C dan +40°C gacha |
| O’rnatish turi | O’rta kuchlanishli kommutatsion qurilmalarda ichki sim/shina o’tkazgichli o’rnatish |
| Standart ko’rsatkichi | GB20840.1-2010, GB20840.2-2014, IEC61869-2:2003 hamda loyiha talablari |
Tanlov jadvali
Quyidagi tanlov ma’lumotlari katalogda ko’rsatilgan 5A va 1A ikkilamchi tok konfiguratsiyalarini birlashtiradi. Uzoq aniqlik va quvvat kataklari veb-saytda yaxshiroq ko’rinadigan bo’lishi uchun bir necha qatorga bo’lingan.
| Nominal
Tok Nisbati (A) |
Aniqlik
Sinfi Kombinatsiyasi |
Nominal
Quvvat (VA) |
Ikkilamchi
Tok |
|---|---|---|---|
| 1500/5 | 0.2S / 0.5 / 5P15 / 5P15 0.2S / 0.5 / 5P20 / 5P20 0.2S / 0.5 / 5P25 / 5P25 |
15/20/40/40 15/20/30/30 15/20/15/15 |
5A |
| 2000/5 | 0.2S / 0.5 / 5P15 / 5P15 0.2S / 0.5 / 5P20 / 5P20 0.2S / 0.5 / 5P25 / 5P25 |
15/20/50/50 15/20/30/30 15/20/20/20 |
|
| 3000/5 | 0.2S / 0.5 / 5P15 / 5P15 0.2S / 0.5 / 5P20 / 5P20 0.2S / 0.5 / 5P25 / 5P25 0.2S / 0.5 / 5P30 / 5P30 |
20/30/50/50 20/30/30/30 20/30/20/20 20/30/15/15 |
|
| 4000/5 | 0.2S / 0.5 / 5P15 / 5P15 0.2S / 0.5 / 5P20 / 5P20 0.2S / 0.5 / 5P25 / 5P25 0.2S / 0.5 / 5P30 / 5P30 |
30/40/50/50 30/40/30/30 30/40/20/20 30/40/10/10 |
|
| 5000/5 | 0.2S / 0.5 / 5P15 / 5P15 0.2S / 0.5 / 5P20 / 5P20 0.2S / 0.5 / 5P25 / 5P25 0.2S / 0.5 / 5P30 / 5P30 |
30/40/60/60 30/40/30/30 30/40/20/20 30/40/10/10 |
|
| 1500/1 | 0.2S / 0.5 / 5P10 / 5P10 0.2S / 0.5 / 5P15 / 5P15 0.2S / 0.5 / 5P20 / 5P20 |
10/15/40/40 10/15/25/25 10/15/15/15 |
1A |
| 2000/1 | 0.2S / 0.5 / 5P10 / 5P10 0.2S / 0.5 / 5P15 / 5P15 0.2S / 0.5 / 5P20 / 5P20 |
10/15/50/50 10/15/30/30 10/15/20/20 |
|
| 3000/1 | 0.2S / 0.5 / 5P10 / 5P10 0.2S / 0.5 / 5P15 / 5P15 0.2S / 0.5 / 5P20 / 5P20 |
10/15/50/50 10/15/30/30 10/15/15/15 |
|
| 4000/1 | 0.2S / 0.5 / 5P10 / 5P10 0.2S / 0.5 / 5P15 / 5P15 |
15/20/50/50 15/20/30/30 |
|
| 5000/1 | 0.2S / 0.5 / 5P20 / 5P20 | 10/10/15/15 |
Eslatma: Agar loyiha talablari ro’yxatlangan diapazondan tashqari bo’lsa, yakuniy parametrlar ishlab chiqaruvchi va xaridor o’rtasidagi texnik kelishuv asosida belgilanadi.
Variyant o’lchamlari
| Variyant | O’lcham
Ko’rsatkichi |
Qo’llash
Eslatma |
|---|---|---|
| LMZBJ17-12Q / 170 | Old terminal tartibi va kvadrat mahkamlash poydevori bilan katta teshik ko’rsatkichi | 170-turli ochiq teshik hamda yuqori tokli birlamchi o’tkazgich uchun yetarli joy talab qilinadigan sim/shina o’tkazgichli ilovalarda foydalaniladi. |
| LMZBJ17-12Q/L | L-o’lcham varianti, jumladan OTC.300.1076.1: 230 va OTC.300.1076.2: 270 ko’rsatkichlari | Kommutatsion qurilmalar tartibi aniq o’q uzunligi yoki mahkamlash chuqurligini talab qilganda foydalaniladi. |
| Umumiy tashqi ko’rinish ko’rsatkichlari | Umumiy uzunlik, mahkamlash plastinasi, 4-Ø14 mahkamlash teshiklari, terminal maydoni hamda tasdiqlangan chizmaga ko’ra teshik o’lchami | Yakuniy o’lchamlar shkaf ishlab chiqarishdan oldin tasdiqlanishi kerak. |
Xizmat ko’rsatish sharoitlari
- O’rnatish joyi: ichki o’rta kuchlanishli kommutatsion qurilmalar
- Nominal kuchlanish: loyiha tasdiqlashiga ko’ra 10 kV, 11 kV va 12 kV sinfli tizimlar
- Nominal chastota: 50 Hz / 60 Hz
- Atrof-muhit harorati: -25°C dan +40°C gacha
- O’rnatish muhiti kuchli titrash, korroziyaga sababchi gazlar, portlovchi muhit, o’tkazuvchi chang, og’ir ifloslanish hamda nozik kondensatsiyadan xoli bo’lishi kerak.
- Yuqori balandlik, sohil, nam yoki og’ir ifloslanish sharoitlarida buyurtma berishdan oldin texnik tasdiqlash tavsiya etiladi.
Standartlar va moslik
LMZBJ17-12 seriyali tokli transformatori GB20840.1-2010, GB20840.2-2014, IEC61869-2:2003 hamda mijozning maxsus talablari asosida ishlab chiqilgan. Oddiy loyiha hujjatlari kelishilgan standartga ko’ra nisbat testi, polarlik tekshiruvi, aniqlik testi, izolyatsiya testi hamda sanoat chastotasida chidamlilik testini o’z ichiga oladi.
O’rnatish va o’lchamlar

Ushbu mahsulot ichki kommutatsion qurilmalarga o’rnatiladi, bunda sim yoki shina markaziy teshik orqali o’tadi. Shkaf ishlab chiqarishdan oldin ochiq teshik o’lchami, mahkamlash plastinasi o’lchamlari, o’tkazgich yo’nalishi, fazaviy tindiqlik, tebranish masofasi, terminal yo’nalishi hamda ikkilamchi simlar kirish joyi tasdiqlangan chizmaga ko’ra tekshirilishi kerak. Q/170 va Q/L versiyalari orasidan tanlov qilishda mexanik o’rnatish chuqurligi hamda o’tkazgich tartibi elektr xususiyatlari bilan birga tekshirilishi kerak.
Xavfsizlik eslatmalari
- Ishlab chiqarishdan oldin nisbat, ikkilamchi tok, aniqlik kombinatsiyasi, nominal quvvat hamda teshik o’lchamini tasdiqlang.
- Sim, mis sterjen yoki shina teshikdan yetarli joy bilan o’ta olishini tekshiring.
- Mahkamlash teshiklarining joylashuvi, o’rnatish tindiqligi, terminal yo’nalishi hamda ikkilamchi simlar uchun joy mavjudligini tekshiring.
- Birlamchi tok oqayotganda tokli transformatorning ikkilamchi zanjiri ochiq zanjir bo’lishi mumkin emas.
- Hisoblagich yoki releylarni ulashdan oldin ikkilamchi zanjirni tasdiqlangan qisqich qurilmasi bilan qisqa tutash kerak.
- Ikkilamchi zanjirning bitta nuqtasi loyiha elektr xavfsizligi amaliyotiga ko’ra yerga ulanishi kerak.
- O’rnatish va ishga tushirish malakali o’rta kuchlanishli elektr mutaxassislari tomonidan amalga oshirilishi kerak.
Buyurtma ma’lumotlari
- Mahsulot modeli: LMZBJ17-12 / LMZBJ17-12Q / 170
- Variyant talabi: Q/170 yoki Q/L
- Nominal birlamchi tok hamda nominal ikkilamchi tok: 5A yoki 1A
- Har bir ikkilamchi yadro uchun aniqlik sinfi kombinatsiyasi hamda nominal quvvat
- Talab qilinadigan himoya sinfi: 5P10, 5P15, 5P20, 5P25, 5P30 yoki loyihaga xos talab
- Sim yoki shina o’lchami hamda teshik talabi
- Mahkamlash chizmasi, terminal yo’nalishi hamda kommutatsion qurilmalar tartibi
- Qo’llaniladigan standart, oddiy test hisoboti hamda sertifikat talablari
- Miqdori, yorliq tili, qadoqlash hamda loyiha hujjatlari talablari
Tanlov qo’llanmasi
- Kuchlanish sinfini tasdiqlang: Izolyatsiya muvofiqlik darajasi tasdiqlangandan so’ng ushbu mahsulotni ichki 10 kV, 11 kV va 12 kV sinfli kommutatsion qurilmalar uchun foydalaning.
- Tok nisbatini tanlang: Liniya toki, shina quvvati hamda himoya sozlamalariga ko’ra 1500 A dan 5000 A gacha tanlang.
- Ikkilamchi tokni tanlang: An’anaviy ikkilamchi zanjirlar uchun 5A yoki past yuklama yoki uzunroq sim uzunligi talab qilinadigan hollarda 1A foydalaning.
- Teshik hamda chuqurlikni tekshiring: Sim, mis sterjen yoki shina teshikdan o’ta olishini hamda Q/170 yoki Q/L o’lchamlari kommutatsion qurilmalar tartibiga mos kelishini tasdiqlang.
- Yadrolarni belgilang: Rele sxemasiga ko’ra hisoblash uchun 0.2S / 0.5 va himoya uchun 5P sinflaridan foydalaning.
- Nominal quvvatni tekshiring: Ulangan hisoblagich, rele hamda sim yuklamalari tanlangan nominal quvvatdan oshmasligiga ishonch hosil qiling.
- Chizmalarni tasdiqlang: Shkaf ishlab chiqarishdan oldin teshik, mahkamlash teshiklari, terminal tartibi hamda poydevor o’lchamlarini tasdiqlang.