LA-10, LFZ1-10, LFZB1-10 Semi-Enclosed Cast-Resin Wall-Through Current Transformer

LA-10, LFZ1-10, LFZB1-10 Semi-Enclosed Cast-Resin Wall-Through Current Transformer

10kV 11kV 12kV semi-enclosed wall-through cast-resin CT for metering and protection

  • Semi-enclosed cast-resin structure for 200A and below applications
  • Fully enclosed structure available for 300A to 1500A current ranges
  • Wall-through design for indoor switchgear and metering cabinet installation
  • 5A secondary output for measurement, energy metering and relay protection
  • 11.5/42/75kV insulation level for medium-voltage indoor applications

Product Overview

LA-10 (LFZ1-10, LFZB1-10) is an indoor semi-enclosed cast-resin wall-through current transformer for medium-voltage distribution systems. It is designed for current measurement, electric energy metering, and relay protection in AC circuits with rated frequency 50Hz and rated voltage up to 10kV. For international documentation, it can be described for 10kV, 11kV and 12kV class indoor switchgear applications, subject to final project confirmation.

This series uses a wall-through structure in which the primary conductor passes through the transformer body and the secondary winding outputs a standardized signal for meters, relays, and monitoring devices. According to the catalogue description, 200A and below adopts a semi-enclosed resin-cast structure, while 300A and above adopts a fully enclosed resin-cast structure. This structural division allows the product to cover compact metering circuits as well as larger feeder protection applications.

From an engineering perspective, the LA-10 series combines compact installation, epoxy resin insulation, and dependable electromagnetic performance. It is particularly suitable for indoor switchgear where the transformer must maintain stable ratio accuracy, adequate insulation strength, and secure mounting within limited panel space.

Product Type

Item Specification
Product name Semi-Enclosed Cast-Resin Wall-Through Current Transformer
Model LA-10 (LFZ1-10, LFZB1-10)
Structure Wall-through type; semi-enclosed for 200A and below, fully enclosed for 300A and above
Insulation Epoxy resin cast insulation
Voltage class 10kV, 11kV and 12kV class indoor systems
Rated insulation level 11.5/42/75kV
Rated frequency 50Hz
Rated secondary current 5A
Typical use Current measurement, energy metering, relay protection
Installation Indoor wall-through mounting

Product Display

Product Display

The LA-10 series includes multiple structural sizes for different current ranges. Lower-current versions are compact and suitable for cabinet metering circuits, while higher-current versions provide larger conductor accommodation and stronger body structure for feeder protection applications.

Applications

  • 10kV, 11kV and 12kV class indoor medium-voltage distribution systems
  • Indoor switchgear, ring main units, metering panels, and feeder cabinets
  • Current measurement and electric energy metering circuits
  • Relay protection circuits requiring stable secondary current output
  • Retrofit and replacement of wall-through type CTs in existing switchgear

Features

  • Semi-enclosed cast-resin design: The 200A-and-below range uses a semi-enclosed structure, balancing compact size and insulation performance.
  • Wall-through construction: The product is designed for switchgear partitions or plates where the primary conductor passes through the CT body.
  • Wide current range: The series covers both smaller metering circuits and higher-current feeder applications.
  • Reliable insulation: Epoxy resin casting improves insulation integrity and mechanical stability for indoor service.
  • Metering and protection suitability: The CT can be specified for measurement duty or protection duty with the appropriate class and burden.
  • Clear terminal identification: Marked primary and secondary terminals help maintain polarity and wiring correctness.

Principle

The LA-10 current transformer operates on electromagnetic induction. When current flows through the primary conductor, magnetic flux is generated in the core. The secondary winding induces a proportional 5A current signal for connected meters, relays, or monitoring equipment. This allows the medium-voltage primary circuit to be safely isolated from the low-voltage secondary circuit while preserving the defined current ratio.

For metering duty, the CT must keep the specified ratio and phase accuracy under rated burden. For protection duty, the CT must maintain sufficient output under fault conditions so that relay devices receive a dependable signal. This is why correct selection of accuracy class, rated output, thermal current, and dynamic current is essential.

Model Designation

Model Designation

The model code LA-10 (LFZ1-10, LFZB1-10) can be interpreted as follows:

Code Meaning
L Current transformer
A Wall-through type
10 Rated voltage class: 10kV
LFZ1-10 / LFZB1-10 Associated manufacturer designations for cast-resin wall-through indoor CT variants

Technical Data

Item Specification
Rated voltage class 10kV class; suitable for 10kV, 11kV and 12kV class indoor applications by project confirmation
Rated insulation level 11.5/42/75kV
Rated frequency 50Hz
Rated secondary current 5A
Rated primary current 5A to 1500A depending on model size and structure
Accuracy classes 0.2, 0.5, 1, 10P10 depending on specification
Rated output Project-dependent; typical metering and protection burdens available
Thermal current Up to 90 × I1n / 75 × I1n / 60 × I1n / 50 × I1n depending on current range
Dynamic current Up to 160 × I1n / 135 × I1n / 110 × I1n / 90 × I1n depending on current range
Operating overcurrent The current transformer can keep working at rated current of 1.1 times
Power-frequency withstand Secondary-to-earth withstand voltage 2kV for 1 minute

Selection Table

The table below is optimized for web display. Long headers are wrapped into multiple lines for better readability in responsive layouts.

Rated

Primary

Current (A)

Is Short Time

Thermal

Current (Ith)

Dynamic

Current

(Idyn)

Accuracy Class

and

Rated Output

Rated

Secondary

Current(A)

Frequency

(Hz)

Insulation

Level

(kV)

5, 10, 15, 20,
30, 40, 50,
75, 100, 150, 200
90 × I1n 160 × I1n 0.2 / 0.5 / 1 / 10P10
Rated output according to metering or protection requirement
5 50 11.5/42/75
300 75 × I1n 135 × I1n 0.2 / 0.5 / 1 / 10P10
Typical metering and protection burdens available
500 60 × I1n 110 × I1n 0.2 / 0.5 / 1 / 10P10
Select output according to connected burden
600, 800,
1000, 1500
50 × I1n 90 × I1n 0.2 / 0.5 / 1 / 10P10
Final output and class per approved specification

Structure Range

Current Range Structure Type Engineering Description
5A to 200A Semi-enclosed cast-resin structure Suitable for compact indoor wall-through applications, especially metering and lower-current protection circuits.
300A to 1500A Fully enclosed cast-resin structure Suitable for larger primary conductors and higher-current feeder circuits requiring stronger body integrity and insulation support.

Windings & Terminal Marking

The catalogue indicates standard polarity and terminal marking practice. The primary terminals are marked P1 and P2. The secondary terminals are marked according to winding function, such as metering and protection windings. One secondary winding may be configured for measurement and another for protection, depending on the ordered specification.

Marking Function Wiring Note
P1 / P2 Primary terminals Correct polarity must be maintained for metering accuracy and relay direction.
1S1 / 1S2 Secondary winding 1 Commonly used for metering duty, depending on ordered class.
2S1 / 2S2 Secondary winding 2 Commonly used for protection duty, depending on ordered configuration.
Ground point Protective grounding One point of the secondary circuit should be grounded according to the system wiring standard.

Service Conditions

  • Altitude: not over 1000m above sea level
  • Ambient temperature: -30°C to +40°C
  • Relative humidity: less than 85% at 20°C
  • Indoor installation only
  • No severe vibration, corrosive gas, explosive medium, or conductive contamination

Standards and Compliance

The catalogue information indicates a 10kV-class indoor current transformer for measurement and protection applications. For project execution, compliance should be confirmed according to the required technical standard set, such as applicable GB current transformer standards or internationally specified IEC instrument transformer standards. For export projects, the technical description can be aligned with 10kV, 11kV and 12kV class switchgear requirements when insulation coordination and project conditions are verified.

Installation and Dimensions

Installation and Dimensions

The LA-10 series is intended for indoor wall-through installation. Different hole dimensions and overall dimensions apply to different current ranges. The catalogue distinguishes the installation outline for the 5–200A range and the 300–1500A range. Before switchgear fabrication, the opening size, hole center distance, conductor path, terminal direction, and installation clearance should be confirmed against the approved drawing.

Hole Dimension

Model Range Hole Dimension Type Application Note
LA-10 (5–200/5) Dimension A For semi-enclosed lower-current structure used in compact indoor wall-through installation.
LA-10 (300–1500/5) Dimension B For higher-current structure with larger conductor passage and different mounting arrangement.

Dimensions

Model Range Overall Dimension Type Reference Note
LA-10 (5–200/5) Overall Dimension A Used for the compact semi-enclosed structure.
LA-10 (300–1500/5) Overall Dimension B Used for larger-current fully enclosed structure.
Approx. product weight About 13.5kg Reference value shown in the catalogue image; actual value may vary by configuration.

Safety Notes

  • Confirm the model, current ratio, accuracy class, rated output, and installation dimension before switchgear production.
  • Check the conductor opening, hole spacing, mounting direction, and insulation clearance before installation.
  • Wire the primary and secondary terminals strictly according to terminal markings and the approved schematic.
  • The secondary circuit of a current transformer must never be open-circuited while the primary circuit is energized.
  • Before removing meters or relays, short-circuit the CT secondary side using an approved shorting device.
  • One point of the CT secondary circuit should be grounded according to local electrical safety practice.
  • Installation and commissioning shall be carried out by qualified medium-voltage electrical personnel.

Ordering Info

  • Product model: LA-10 (LFZ1-10, LFZB1-10)
  • Rated primary current / rated secondary current
  • Accuracy class and rated output for each secondary winding
  • Application type: metering, protection, or combined duty
  • Required Ith and Idyn values according to system short-circuit level
  • Installation drawing, hole dimension, and conductor arrangement
  • Service environment, altitude, and any special technical requirements

Selection Guide

  1. Confirm system voltage: Use this model for indoor medium-voltage systems in the 10kV, 11kV and 12kV class range after confirming insulation coordination.
  2. Choose the current range: Select the semi-enclosed 5–200A range for smaller circuits and the larger structure for 300–1500A circuits.
  3. Define the function: Confirm whether the CT is for metering, relay protection, or both.
  4. Select the ratio: Match the rated primary current to the actual feeder or circuit current.
  5. Specify accuracy and burden: Metering and protection duties require different accuracy classes and rated outputs.
  6. Verify withstand capability: Ith and Idyn must be compatible with the switchgear fault level.
  7. Confirm dimensions: Check hole dimensions and overall dimensions before panel manufacturing.

FAQs

The LA-10 is used for current measurement, electric energy metering, and relay protection in indoor medium-voltage switchgear and distribution systems.

Because the lower-current range, especially 200A and below, adopts a semi-enclosed cast-resin structure. This design provides insulation and mechanical support while keeping the product compact for indoor wall-through installation.

Yes. In international documentation it can be positioned for 10kV, 11kV and 12kV class indoor applications, but the final selection must be based on insulation level, system design, and project confirmation.

You should define whether the winding is intended for metering, protection, or both, and then specify the current ratio, accuracy class, rated output, and any protection-class requirement such as 10P10.

You should confirm the correct hole dimension type, mounting hole spacing, conductor passage size, terminal direction, and overall clearance according to the approved drawing for the selected current range.

If the CT secondary is open while primary current is flowing, dangerous high voltage can be induced at the secondary terminals. This can damage insulation and create serious safety risk for personnel and equipment.

Please provide the model, current ratio, secondary current, accuracy class, rated output, application type, Ith and Idyn requirements, installation dimensions, quantity, and any special project or testing requirements.